Professional Documents
Culture Documents
Authorized licensed use limited to: UNIVERSIDADE DO ESTADO DO RIO DE JANEIRO. Downloaded on August 18,2021 at 15:46:43 UTC from IEEE Xplore. Restrictions apply.
International Conference on Energy, Communication, Data Analytics and Soft Computing (ICECDS-2017)
designed by using block diagram as shown in fig (1) A similar equation can be written for other phases.
given below. Hence no fault condition can be discriminated by
function
Ψcos(a)=
ିଵ ሺ
ሺݎ݁ݏ݆݅ܫሻ
ሺݎ݁ݏ݆݅ܫሻ=
ିଵ ሺͲሻ=90° (8)
326
Authorized licensed use limited to: UNIVERSIDADE DO ESTADO DO RIO DE JANEIRO. Downloaded on August 18,2021 at 15:46:43 UTC from IEEE Xplore. Restrictions apply.
International Conference on Energy, Communication, Data Analytics and Soft Computing (ICECDS-2017)
error due to line charging currents.These schemes are C. Result under normal operating condition
able to discriminate faulty phase reliably.
Results for phase angle comparison of different
In order to enhance conventional differential conditions as given below .But these results as same
protection scheme, a new protection algorithm was as for cosine angle comparison.Under normal
implemented combining concept discussed above in operating condition, when no fault on system
section 2. relaydoes not send any tripping signal to the circuit
breaker. Fig (4) shows results of sending end current
A. Operation during internal faults.
and receiving end of line current(ampere)& fig. (5)
Relay logic of phase angle comparison scheme shows phase difference between sending & receiving
and cosine angle comparison will operate during an end series current(ampere).
internal fault to a bus. When an internal faults occur
in a system if the phase difference is other than 200
Phase A
C u rren t
threshold value indicates an fault. When this 0
happens, relay will trip.This will ensure fast & secure -200
operation during internal fault conditions. Time(seconds)
200
Phaser B
C u rre n t
B. Operation during external faults.
0
During the faults external to the bus, relay logic -200
of phase angle comparison and cosine angle Time(seconds)
200
Phase C
C u rren t
comparison will not operate. Even, if the phase
0
difference is other than threshold value. This will
-200
result no trip condition. The threshold values ensure 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
that the relay is always stable for external faults Time(seconds)
without affecting its performance on internal faults.
Fig 4:- Performance of LLLG fault during normal condition.
V .SIMULATION RESULTS
A. Designing of a differential relay
Circuit breaker which is used for the protection
purpose in power system. It cannot operate by its
own decision. There must be a relay that sends
tripping signal to circuit breaker after comparing
phase angle difference at both ends of transmission
line.
B. Logic behind the operation of differential relay.
As per differential protection principle ,current
get compare at both ends of transmission line but as
per phase angle comparison schemes we can
compare phase angle with each other in very
systematic manner in sending end and receiving end
of phase A & then result of comparison sends to
relay logic for final operation. The same procedure
with rest of two phases. Fig (3) shows relay logic of
secure phase comparison scheme.
327
Authorized licensed use limited to: UNIVERSIDADE DO ESTADO DO RIO DE JANEIRO. Downloaded on August 18,2021 at 15:46:43 UTC from IEEE Xplore. Restrictions apply.
International Conference on Energy, Communication, Data Analytics and Soft Computing (ICECDS-2017)
5000 0
C urren t
0 -5000
0
0.15 0.2 0.05
0.25 0.3 0.1
0.35 0.4
Time(seconds)
-5000
Time (seconds) Fig 8.:- Performance during (LLLG) external fault for phase
5000 a,b,c.(line current)
C u rre n t C u rre n t
0
-5000
Time(seconds)
5000
0
-5000
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time(seconds)
Fig 6:- Performance during (LLLG) internal fault for phase a, b,
and c.(line current)
328
Authorized licensed use limited to: UNIVERSIDADE DO ESTADO DO RIO DE JANEIRO. Downloaded on August 18,2021 at 15:46:43 UTC from IEEE Xplore. Restrictions apply.
International Conference on Energy, Communication, Data Analytics and Soft Computing (ICECDS-2017)
1) Set input line parameters, frequency and trip systems,” IEEE Trans. Smart Grid,vol. 1,no 1,pp. 20- 27,
Jun.2010.
value for relay setting. [10]. W.Li,T. Bi, Z Xu, and Q.YANG, “A phase selector for
2) Check phase angle difference at both ends of transmission line protective relaying using the multi
parameter comparison criteria,” in Proc.Int.Conf.Adv.
transmission line. Power Syst. Autom.Protect, Oct 2011, vol 1,pp.673-676.
[11]. Y.G.Paithankar “Fundamentals of power system
3) Obtain phase angle difference using discrete protection”, PHI learning New Delhi march 2013.
fourier transform Iijlineabc . [12]. Trupti p. Hinge, Sanjay S.Dambhare “Secure phase
comparison schemes for transmission line protection using
4) Calculate series current for phase a, b ,c at both synchrophasors ” IEEE Trans. Power Del, vol 30,no 4 Aug
ends of transmission line. 2015.
[13]. Thorat .A.R and JadhavNilesh S., “Design of differential
5) For phase angle comparison technique check if relay for 1000-kv transmission line” using MATLAB.
phase angle difference is other than threshold [14]. HamzahEteruddin, Abdullah Asuhaimi bin
value .If yes then trip otherwise no trip. MohdZin,Belyamin, “Line differential protection modeling
with composite current & voltage signal comparison
6) For cosine angle comparison technique, method”.
calculate cosine of angle of series branch
current for phase a, b, c.
7) Check if phase angle difference is other than
threshold value. If yes then trip else no trip.
8) For both the methods mentioned in step 5 and
step 7 , if Ψcos(phase) &Ψser (phase) other than
threshold value then issue a trip decision and
send trip decision other end also.Else go back to
step 4.
VII.CONCLUSION
This paper proposes two secure phase comparison
schemes for protection of transmission line which
based on the working principle of differential relay
protection. Both schemes compensates the phase
angle error due to line charging currents and are able
to discriminate the faulty phase reliably. Also it
contains simulation model specially design for 400kv
transmission line. Also these schemes are able to
distinguish between internal and external faults.
REFERENCES
[1]. Y. Ge,W . Anding T. Huiliang, “Phase comparison pilot
relays using fault superimposed components,” in proc.
Inst.Ele.Eng.Int. ConfAdv. Power System
ControlOper.Manage, Hong Kong,China, Nov.1991,vol2.
833-838.
[2]. A.AGirgis,D. G.Hart, and W.L. Peterson, “A new fault
location technique for two & three terminals lines,” IEEE
Trans. Power Del., vol7, no1,pp98-107 ,Jan 1992.
[3]. J.J. Grainger and W.D .Stevenson, Power system analysis.
New York,USA: McGraw-Hill, 1994 vol 31.
[4]. B.KasztennyI.Voloh, “Rebirth of the phase comparison
line protection principle,” presented at the 59 Annu.
Conf.Protect.Relay Eng, college Station,TX,USA,2006.
[5]. F.Namdari,S.Jamali,P.A.Crossley, “Power differential
based wide area protection” ELSEVIER, Sciencedirect,
Electric power system research 77 (2007) 1541-1551.
[6]. Sunil.S.Rao “Switchgear & protection” Khanna
publishers. Oct 2008 13th edition.
[7]. S.Dambhare, S.Soman, and M. Chandorkar, “Adaptive
current differential protection schemes for transmission line
protection,” IEEE Trans. Power Del, vol 24 no4,pp. 1832-
1841, Oct. 2009.
[8]. M.Eissa,M.Masoud, and M.Elanwar, “Anovelback up wide
area protection technique for power transmission grids
using phasor measurement units”,IEEE Trans.PowerDel.vol
25,no 1,pp.270-278, Jan 2010.
[9]. J.De La Ree,V,Centeno, J,S.Thorp, and A. G. Phadke,
“Synchronized phasor measurement applications in power
329
Authorized licensed use limited to: UNIVERSIDADE DO ESTADO DO RIO DE JANEIRO. Downloaded on August 18,2021 at 15:46:43 UTC from IEEE Xplore. Restrictions apply.