You are on page 1of 48

ZTE DC POWER SYSTEM

Dept of Infra Planning & Special Project


October 2020
Arip Zaenal Aripin
Power Planning
ariep.arifin@smartfren.com
CONTENT

 DC SYSTEM ARCHITECTURE
 ZXDU68 S301 DC POWER SYSTEM
 ZXDU68 W201 DC POWER SYSTEM
 ZXDU68 W001 DC POWER SYSTEM
 ZXDU48 H002 DC POWER SYSTEM
 AGM BATTERY
 ZTE LITHIUM (LFP) BATTERY
 DC POWER SYSTEM CONFIGURATION
 ALARM DRY CONTACT
DC POWER SYSTEM ARCHITECTURE
DC Power/Rectifier is an electrical device that converts alternating
current (AC) to direct current (DC).
Controller

Enode B

TX, FAN, TEC


ZXDU68 S301 DC POWER SYSTEM
ZXDU68 S301 DC POWER SYSTEM
ZXDU68 S301 AC & DC DISTIBUTION
ZXDU68 S301 ZXDU3000V5
ZXDU68 S301 ZXDU3000V5 INDICATOR
ZXDU68 S301 CSU500
ZXDU68 S301 SIB BOARD
ZXDU68 W201 DC POWER SYSTEM
ZXDU68 W201 DC POWER SYSTEM
ZXDU68 W201 AC&DC DISTRIBUTION
ZXDU68 W201 ZXD3000V5 & CSU500
ZXDU68 W201 PLACEMENT
ZXDU68 W201 SIB BOARD
ZXDU68 W001 DC POWER SYSTEM
ZXDU68 W001 DC POWER SYSTEM
ZXDU68 W001 SPECIFICATION
ZXDU48 H002 DC POWER SYSTEM
ZXDU48 H002 DC POWER SYSTEM
ZXDU48 H002 DIMENSION
ZXDU48 H002 PLACEMENT
ZXDU48 H002 AC&DC DISTRIBUTION
ZXDU48 H002 - ZXD1500
ZXDU48 H002 CSU520B
ZXDU48 H002 SIB BOARD
AGM BATTERY
AGM BATTERY

Negative Terminal -48 V

Positive Terminal -48 V

- Battery AGM type (dry battery)


- Battery Capacity 150 Ah
- Battery Voltage 12 Volt
- Temperature Range -10 C to 45 C
(recommended 25 C)
- To 48V need 4 blocks and serial connection Inter Cell Battery
LITHIUM (LFP) BATTERY
ZTE ZXDC48 FB101
ZTE ZXDC48 FB100C1
ZTE LITHIUM BATTERY PARAMETER
DC POWER SYSTEM CONFIGURATION
ZXDU68 S301 CONFIGURATION
ZXDU68 S301 3Re-2*150Ah ZXDU68 S301 3Re-2*100Ah

3 modules (3Re) 3 modules (3Re)

1*150 Ah (4 blocks)
1*LFP 100 Ah (1 unit)

1*150 Ah (4 blocks)
1*LFP 100 Ah (1 unit)
ZXDU68 W201 CONFIGURATION
ZXDU68 W201 3Re-2*150Ah ZXDU68 W201 3Re-2*100Ah

3 modules (3Re) 3 modules (3Re)

1*150 Ah (4 blocks)
1*LFP 100 Ah
(1 unit)
1*150 Ah (4 blocks) 1*LFP 100 Ah
(1 unit)
ZXDU68 W001 CONFIGURATION
ZXDU68 W001 3Re-2*150Ah ZXDU68 W001 3Re-2*100Ah

3 modules (3Re) 3 modules (3Re)

1*150 Ah (4 blocks) 1*LFP 100 Ah


(1 unit)
1*150 Ah (4 blocks) 1*LFP 100 Ah
(1 unit)
ZXDU48 H002 CONFIGURATION
ZXDU48 H002 3Re-1*150Ah
ZXDU48 H002 3Re-1*100Ah

3 modules (3Re)

3 modules (3Re)

1*150 Ah (4 blocks)

1*LFP 100 Ah (1 unit)


ALARM DRY CONTACT
DRY CONTACT CONNECTION
DRY CONTACT CONNECTION
S301 & W201 PIN CONNECTION
 ZXDU68 S301/ZXDU68 W201 on Supervision  ZTE BBU Input Alarm Cable
interface Board (SIB).

Port 1 (+) & 14 (-) = DryContact 1


Port 2 (+) & 15 (-) = DryContact 2
Port 3 (+) & 16 (-) = DryContact 3
Port 4 (+) & 17 (-) = DryContact 4
Port 5 (+) & 18 (-) = DryContact 5
Port 6 (+) & 19 (-) = DryContact 6
Port 7 (+) & 20 (-) = DryContact 7
Port 8 (+) & 20 (-) = DryContact 8
S301 & W201 SETTING PARAMETER
After installation, login to ZXDU68 S301/W201 CSU by Laptop to change :
1. Rectifier Module Failure Alarm Set to A1 on Out Rly
2. DC Low Voltage Alarm Set to A2 on Out Rly
3. Battery & Load Fuse Alam set to A3 on Out Rly
4. High Temp alarm set to A4 on Out Rly
H002 PIN CONNECTION
 Output Relay ZXDU48 H002 installed on SIB  ZTE BBU Input Alarm Cable

Port 1 (+) & 14 (-) = DryContact 1


Port 2 (+) & 15 (-) = DryContact 2
Port 3 (+) & 16 (-) = DryContact 3
Port 4 (+) & 17 (-) = DryContact 4
Port 5 (+) & 18 (-) = DryContact 5
Port 6 (+) & 19 (-) = DryContact 6
Port 7 (+) & 20 (-) = DryContact 7
Port 8 (+) & 20 (-) = DryContact 8
DB25 CONVERTER

Port 1 (+) & 14-20 (-) = DryContact 1


Port 2 (+) & 14-20 (-) = DryContact 2
Port 3 (+) & 14-20 (-) = DryContact 3
UNUSE PORT
Port 4 (+) & 14-20 (-) = DryContact 4
Port 5 (+) & 14-20 (-) = DryContact 5
Port 6 (+) & 14-20 (-) = DryContact 6
Port 7 (+) & 14-20 (-) = DryContact 7
Port 8 (+) & 14-21 (-) = DryContact 8
Terima Kasih.
PLN CALCULATION
PLN CALCULATION

Enode B FDD&TDD : 2511 Watt


Battery : 2*100Ah
Current Limit Battery : 10 %
Total Load DC POWER : 2511+2*100*10%*48
: 3471
Apply PLN : Total Load DC POWER /Efficiency/Pf
: 3471 Watt/0.935/0.998
: 3719.8 VA
: 4400 – 5500VA