Professional Documents
Culture Documents
PROTECTION IN
POWER
SYSTEM
1
On completion of this lesson, a student
should be able to:
2
TOPIC OUTLINE
Introduction
Basic Components of Protection System
The Concept of Protection System
Fuse
Computer Relaying
Zone of Protection
3
INTRODUCTION
4
INTRODUCTION
The primary function of a protection system in an electrical power
network is to ensure the continuity of the electricity supply.
To achieve this, the protection system must be able to:
Detect the abnormal condition in an electrical circuit or piece of
equipment
Identify the location of the fault
Isolate the faulty section of the circuit or the faulty equipment only
without the electricity supply to the rest of the network.
5
INTRODUCTION
Requirements To Protective System Provide For
Basis To Design Criteria
6
BASIC COMPONENTS
OF PROTECTION
SYSTEM
7
BASIC COMPONENTS
Protection systems have 3 basic components:
1. Instrument transformers
2. Protective Relays
3. Circuit breakers
A simple overcurrent
protection schematic with:
9
BASIC COMPONENTS
Instruments Transformer
In general, there are 2 basic types of instruments transformers:
Current Transformer (CT)
Voltage Transformer (Potential Transformer) (VT)
10
BASIC COMPONENTS
12
BASIC COMPONENTS
The function of the CT is to reproduce in its secondary
winding a current I’ that is proportional to the primary
current I.
The CT converts primary currents in the kilo ampere range
to secondary currents in the 0-5 ampere range for
convenience of measurement, with the following
advantages.
Safety: Instrument transformers provide electrical isolation
from the power system so that personnel working with relays
will work in a safer environment.
Economy: Lower-level relay inputs enable relays to be smaller,
simpler and less expensive.
Accuracy: Instrument transformers accurately reproduce power
system currents and voltages over wide operating ranges.
13
BASIC COMPONENTS
Currents transformers are divided into 2 main types:-
Protection currents transformer
Measuring current transformer
Example:
A CT with a specification of 800/5A, 15 VA, Class 0.5, means that the rated primary
current is 800A, the secondary current is 5A (when primary is 800A), the burden is 15
VA, and it is a measuring CTs with a current ratio error of 5% at the rated current.
15
BASIC COMPONENTS
Currents transformer used in distribution system have a single-turn
primary windings and multi-turn secondary windings
The 2 most common types of current transformer are:
a) The primary winding is a straight copper bar (round or rectangular) the
secondary windings is wound round this bar.
b) A round iron core which the secondary winding is wound. Also known as a ring
CTs. This types usually used extensively in the low voltage systems.
16
CURRENT TRANSFORMER
17
BASIC COMPONENTS
Table 1: Standard CT Ratios
Current Ratios
50:5 100:5 150:5 200:5 250:5 300:5 400:5
18
BASIC COMPONENTS
Ideally, the CT secondary is connected to a current-sensing device with
zero impedance, such that the entire CTs secondary current flows through
the sensing device.
In practice, the secondary current divides, with most flowing through the
low-impedance sensing device and some flowing through the CT shunt
excitation impedance.
CT excitation impedance is kept high in order to minimize excitation
current.
An approximate equivalent circuit of a CT is shown in Figure 3, where:-
Z' = CT secondary leakage impedance
Xe = (Saturable) CT excitation reactance
ZB = Impedance of terminating device (relay, including leads)
19
BASIC COMPONENTS
20
BASIC COMPONENTS
Determine Current Transformer Performance
21
BASIC COMPONENTS
CT Error
Where,
Ie=CT Secondary excitation current
I’=CT Secondary output current
22
EXAMPLE 1
Evaluate the performance of the multi-ratio CT in
Figure 3 with a 100:5 CT ratio, for the following
secondary output currents and burdens:
a) I’ = 5 A and ZB = 0.5 ohm.
b) I’ = 8 A and ZB = 0.8 ohm.
c) I’ = 15 A and ZB = 1.5 ohm.
Ie = 0.25 A
25
SOLUTION
2.91 V
0.25 A
Ie = 0.4 A
27
SOLUTION
7.06 V
0.4 A
Ie = 5 A
29
SOLUTION
23.73 V
5A
31
EXAMPLE 2
An overcurrent relay set to operate at 8 A is connected to the multiratio
CT with a 100:5 CT ratio. Will the relay detect a 200 A primary fault
current if the burden ZB is
a) 0.8 ohm
b) 3 ohm
32
BASIC COMPONENTS
Voltage Transformer (VT)
33
BASIC COMPONENTS
The variation of voltage is a electricity network
usually very small (5%) so the operating range of a
measuring voltage transformer is small compare with
that of a measuring.
However, if a fault occurs, the voltage drops to a very
low value. Protection VT must be able to operate
over a wide range from as low as 5% to 190% of the
rated voltage.
34
BASIC COMPONENTS
There are 2 types of construction for voltage
transformer:-
35
VOLTAGE TRANSFORMER
36
BASIC COMPONENTS
Protective Relays
38
BASIC COMPONENTS
5. Frequency relays: Operate at a predetermined
frequency. These include over frequency and under
frequency relays.
6. Temperature relays: Operate at a predetermined
temperature in the protected component.
7. Differential relays: Operate according to the scalar
or vectorial difference between two quantities such
as current, voltage, etc.
8. Distance relays: Operate according to the "distance"
between the relay's current transformer and the
fault. The "distance" is measured in terms of
resistance, reactance, or impedance.
39
BASIC COMPONENTS
Electromechanical and Induction Disc Relays
41
BASIC COMPONENTS
ф Keeper
Disc
IS
Main coil
Figure 5: Electromagnet Plunger type I
Electromagnet
5 .фL .фR
4
6 Magnet
plugs
42
Induction Disc Relay
This relay Inverse Definite Minimum Time (IDMT).
The operating characteristic of a standard IDMT relay is defined
as:
0.14 TMS
t
PSM 0.02 1
TMS – time multiplier setting
PSM – plug setting multiplier
I I – measured current
PSM Is – relay setting current
Is
43
Induction Disc Relay
Example:
Determine the time of operation of a 1 A, 3 s overcurrent relay having a Plug
Setting of 125% and a Time Multiplier of 0.6. The supplying CT is rated 400:1 A
and the fault current is 4000 A.
Solution
the relay coil current for the fault
1
I 4000 10 A
The nominal relay coil current 400
125
Is 1 A 1.25 A
100
44
Induction Disc Relay
The plug setting multiplier
10
PSM 8
1.25
the time of operation
0.14 TMS
t
PSM 0.02 1
0.14 0.6
0.02
8 1
1.98 s
45
BASIC COMPONENTS
Circuit Breaker (CB)
CB is a reusable device that may be rest after operation.
It set to protect circuit and equipment from over current
resulting from overloads and short circuits.
Electrically, CB connected in series with the load and
carry load current under normal condition.
Have three operation condition ON (Contact closed)
allowing, load current to flow through breaker, OFF
(Contact open) breaker contact open , circuit is
deernergized and TRIPPED ( Contact open need reset)
when overcurrent and overload occur or by the operation
of the shunt trip on under voltage.
46
BASIC COMPONENTS
Bimetal Circuit breaker
contacts
Current
Current
in
Spring out
Latch
Normal Tripped
A. Thermal
Latch
Circuit breaker
contacts
Current
Spring out
Armature
Electromagnetic
coil Electromagnetic
Current in coil
Normal B. Magnetic Tripped
48
TRANSFORMER PROTECTION
A number of fault conditions can arise within a power transformer.
Earth fault
Core faults
Inter turn faults
Phase to phase faults
Tank fault
In addition to the fault condition cause stresses on the transformer,
such as overloading, system faults , over voltages and under
frequency operation
49
TRANSFORMER PROTECTION
PROTECTED
I I
APPARATUS
im1 im2
Relay
A
A
B B
C C
Example of Differential
Relay Protection of a Δ/Y
R
o
R
transformer.
Phase A
o
R R
Phase B
o
R R Phase C
52
EXAMPLE 3
Consider a Δ/Y connected, 20 MVA, 33/11 kV transformer with differential protection applied, for
the current transformer ratios shown in Figure 10. Calculate the relay currents on full load. Find
the minimum relay current setting to allow 125 percent overload.
Figure 10
53
SOLUTION
The primary line current is given by
20MVA
Ip 349.91 A
3 33kV
20MVA
Is 1049.73 A
3 11kV
54
SOLUTION
The C.T. current on the primary side is thus
5
i p 349.91 5.832 A
300
The C.T. current in the secondary side is
5
is 1049.73 A 3 4.545
2000
Note that we multiply by to obtain 3the values on the line side of the Δ connected C.T.’s. The
relay current on normal load is therefore
55
TRANSFORMER PROTECTION
Buchholz Protection
it is common practice in transformer protection to
employ gas-actuated relays for alarm and tripping.
One such a relay is the Buchholz relay. Faults within a
transformer will result in heating and decomposing of
the oil in the transformer tank.
The decomposition produces gases such as hydrogen,
carbon monoxide, and light hydrocarbons, which are
released slowly for minor faults and rapidly for severe
arcing faults.
In the gas activated relay named after its inventor,
this phenomenon is utilized.
56
TRANSFORMER PROTECTION
The relay is connected into the pipe leading to the conservator tank.
ø As the gas
accumulates, the oil
level falls and a float F
is lowered and
operates a mercury
switch to sound an
alarm.
ø Sampling the gas and
performing a chemical
analysis provide a
means for classifying
57
the types of fault.
TRANSFORMER PROTECTION
Buchholz protection provides an alarm for a number of
fault conditions including:
1. Inter turn faults or winding faults involving only
lower power levels.
2. Core hot spots due to short circuits on the
lamination insulation.
3. Faulty joints.
4. Core bolt insulation failure.
58
BUSBAR PROTECTION
Bus bars are an essential link in the electric power system, and short
circuits in their zone have to be interrupted in the shortest possible
time.
In distribution systems (6-20 kV) with supply through transformers,
overcurrent time-relays provide an easy protection mechanism.
The relays interrupt the supply to the bus bars if one or more supplies
conducting a fault current.
Power direction relays are used in the transformer supply side to
respond to a fault at the bus bars.
59
BUSBAR PROTECTION
Differential protection is the most reliable method of protection for bus
bars.
60
GENERATOR PROTECTION
There are a number of abnormal conditions that may occur with
rotating equipment, including:
1. Faults in the windings.
2. Loss of excitation.
3. Motoring of generators.
4. Overload.
5. Overheating.
6. Overspeed.
7. Unbalanced operation.
8. Out-of-step operation.
61
GENERATOR PROTECTION
Various types of faults that may occur in the insulation
system of a generator's windings.
The faults shown are identified as:
62
GENERATOR PROTECTION
Allocation of Protective
Devices for the Stator,
Rotor and Prime Mover.
63
TRANSMISSION LINE PROTECTION
It is necessary to provide the desired selectivity such
that relay operation result in the least service
interruption while isolating the fault.
The excessive currents accompanying a fault are the
basis of over current protection scheme.
In transmission line protection system, it is necessary
to provide the desired selectivity such that relay
operation result in the least service interruption
while isolating the fault.
In transmission line protection scheme, relay
coordination is MUST.
64
TRANSMISSION LINE PROTECTION
Three methods of relay grading:
Current Grading.
Time Grading
Inverse Time Over Current Relaying
CURRENT GRADING
1. Operates at suitable
graded current
2. Fault current are
higher near the
source.
3. Relays are set that
decreases as distance
from the source is
65 increased.
TRANSMISSION LINE PROTECTION
Time Grading
1. Ensure the breaker
nearest to the fault open
first, by choosing an
appropriate time setting
for each of the relay.
2. Time setting increase as
the relay get closer to the
source.
67
TRANSMISSION LINE PROTECTION
Radial System Protection
Many radial systems are protected by time delay overcurrent relays.
Adjustable time delays can be selected such that the breaker closest to
the fault opens, while other upstream breakers with larger time delays
remain closed.
That is, relays can be coordinated to operated in sequence so as to
interrupt minimum load during faults.
Successful relay coordination is obtained when fault currents are much
larger than normal load currents
Also, coordination of overcurrent relays usually limits the maximum
number of breakers in a radial system to five or less, otherwise the relay
closet to the source may have an excessive time delay
68
TRANSMISSION LINE PROTECTION
Consider a fault at P1 to the right of breaker B3 for the radial system of Figure 10.
We want breaker B3 to open while B2 and B1 remains closed.
Under these condition, only load L3 is interrupted
We could select a longer time delay for the relay at B2 so that B3 operates first
Thus, for any fault to the right of B3, B3 provides primary protection
If B3 fails to open, B2 will open after time delay, thus providing backup protection
69 Figure
10
TRANSMISSION LINE PROTECTION
Similarly, consider a fault at P2, we want B2 to open while B1 remains closed
Under these conditions, loads L2 and L3 are interrupted
Since the fault is closer to the source, the fault current will be larger than for the
previous fault considered
We also select the B1 relay with a longer time delay than B2, so that B2 opens first.
Thus, B2 provides primary protection for faults between B2 and B3, as well as back up
protection for faults to the right of B3.
70 Figure
10
TRANSMISSION LINE PROTECTION
Similarly, B1 provides primary protection for faults between B1 and B2, as well as
back up protection for further downstream faults
The coordination time interval is the time interval between the primary and remote
backup protective devices
It is the different between the time that the backup relaying operates and the time
that circuit breakers clear the fault under primary relaying
Typical time interval between 0.2 to 0.5 seconds are selected to account in most
practical applications
71 Figure
10
EXAMPLE 4
The CO-8 relay with a current tap setting of 6 amperes and time dial setting of 1 is used
with the 100:5 CT in Example 7.1. Determine the relay operating time for each case.
Solution:
I' 5
I ' 5A; 0.83
Ip 6
The relay does not operate. It remains in the blocking position.
72
SOLUTION
I' 8
b) I ' 8A ; 1.33
Ip 6
Using curve 1 in Figure 11, toperating = 6 seconds
I ' 15
c) I ' 15A; 2.5
Ip 6
73
Figure 11: CO-8 time delay overcurrent relay characteristic
74
EXAMPLE 5
An 11 kV, 50 Hz radial system is shown in Figure 12. Assuming a CO-7 relay with relay
characteristic given in Figure 13 and the same power factor for all loads, select relay
settings to protect the system with coordination time interval 0.3 seconds.
Figure 12
75
76 Figure 13
SOLUTION
The load currents are calculated as
77
SOLUTION
With the given CT ratios, the normal relay currents are
78
SOLUTION
Choosing the nearest setting higher than the normal current
79
SOLUTION
Next, select the intentional delay indicated by TDS
(Time Dial Setting). Utilize the short circuit currents to
coordinate the relays
The current in the relay at 1 on short circuit is
Choose the lowest TDS for this relay for fastest action.
Thus,
TDS1 = ½
80
SOLUTION
Referring to the relay characteristic, for TDS1 = ½ and
10.42 ratio, the operating time for the relay 1 for a fault
at 1 is obtained as T11 = 0.15 s.
To set the relay at 2 responding to a fault at 1, allow
breaker operating time,
81
SOLUTION
Short circuit for a fault at 1 as a multiple of the CTs
at 2 is
82
SOLUTION
For TDS2 = 2 and 7.5 ratio, from relay characteristic,
T22 = 0.5 s
Allowing the same margin for relay 3 to respond for a fault
at 2, as for relay 2 responding to a fault at 1,
83
FUSE
84
FUSE
Fuse is a device connected in series with the
conductors that caries the full load current
supplied to the load.
Under the normal condition, the load current is less
than the ampere rating of the fuse, and the fuse
remain intact to connect the load to the source.
When overload or short circuit occurs, the current
through link will also increase. Once the link totally
melted, an open circuit exist in the fuse, an open
circuit exist and the circuit will remain open.
Then it must be replaced. Fuse are “one time”
device.
85
FUSE
Reduced area of link Reduced area of link
Filler material
A. Non-Current Limiting , Non-Time
Delay Fuse B. Current Limiting Non-Time
Delay Fuse
Connector
86
FUSE
During normal operation, when the fuse is operating below
its continuous current rating, the resistance of the link is so
low
If an overload current occurs and persists for more than a
short interval of time, the temperature of the link eventually
reaches a level that causes a restricted segment of the link
to melt.
A gap is then formed and an electric arc is established.
As the arc causes the link metal to burn back, the gap width
increases.
The resistance of the arc eventually reaches such a high level
that the arc cannot be sustained and it is extinguished.
The current flow within the fuse is then completely cut off.
87
FUSE
88
FUSE
Fuse specification is normally based on the following four factors.
89
Example
A 415 V distribution system is shown in Figure 14.
Select the suitable rating of fuse for each load and
incoming circuit using fuse time-current characteristic
in Figure 15.
90 Figure 14
Example
91 Figure 15
92 EET301 POWER SYSTEM ENGINEERING Figure 15
Solution
Fuse selection for each circuit
Lighting load:
20kW
I lighting 27.8 A
3 415V
select 32 A fuse
Heating load:
30kW
I heating 41.7 A
3 415V
select 50 A fuse
93
Solution
Motor load:
Pout 30 kW
Pin 32.6 kW
0.92
The motor full load current is
32.6kW
I motor 54.7 A
3 415V 0.83
I 7 54.7 383A
94
Solution
From the time-current curve, an 80 A fuse would
withstand 383 A for only 6 seconds.
Therefore, for a 100 A fuse, which would withstand 383 A
for longer than 10 seconds, would be necessary.
To provide discrimination the fuse at incoming circuit
must meet the following requirements:
It must carry the normal load current:
I 27.8 41.7 54.7 124.2A
It must carry the load + the starting current of the motor
I 27.8 41.7 383 452.5A for 10 s
From time-current curve, a 125 A fuse would withstand
452.5 A for more than 10 s.
95
COMPUTER
RELAYING
96
COMPUTER RELAYING
The electric power industry has been one of the earliest
users of the digital computer as a fundamental aid in
the various design and analysis aspects of its activity.
There are many perceived benefits of a digital
relaying system:
1. Economics: cost effective
2. Reliability: continuously active providing a high level of
self-diagnosis.
3. Flexibility: Revisions or modifications made necessary by
changing operational conditions
4. System interaction: The availability of digital hardware
that monitors continuously the system performance at
remote substations.
97
COMPUTER RELAYING
Example of Functional Block of Digital Relay
98
ZONE OF
PROTECTION
99
ZONE OF PROTECTION
Power system configurations, a fundamental concept is the division of a
system into protective zones.
If a fault occurs anywhere within a zone, action will be taken to isolate
that zone from the rest of the system. Zones are defined for:
Generators
Transformers
Buses
Transmission and distribution lines
Motors
100
ZONE OF PROTECTION
Each zone is defined by a closed, dashed line. As shown
in Figure 16, Zone 1 for example, contains a generator
and connecting leads to a transformer ,.
In some cases a zone may contain more than one
component.
For example, Zone 3 contains a generator-transformer
unit and connecting leads to a bus, and Zone 10 contains a
transformer and a line.
Protective zones have the following characteristics:
Zones are overlapped.
Circuit breakers are located in the overlap regions.
For a fault anywhere in a zone, all circuit breakers in
that zone open to isolate the fault.
101
ZONE OF PROTECTION