Professional Documents
Culture Documents
Robust Damping Control of Power Systems With TCSC A Multi-Model BMI Approach With H 2 Performance
Robust Damping Control of Power Systems With TCSC A Multi-Model BMI Approach With H 2 Performance
4, JULY 2014
Abstract—This paper presents the robust damping control that the root locus approaches can also be applied to FACTS
of power systems with thyristor-controlled series compensator devices for low frequency oscillation damping [5], [6]. How-
(TCSC). A SISO output feedback controller is to be designed for ever, in a multi-machine system, root locus sometimes can be
TCSC to improve the damping of inter-area oscillations under
multiple operating points. The robust damping control problem is
complicated since it is difficult to find a path for the damping
formulated as a multi-objective optimization problem considering and synchronizing torques. A multi-variable root locus method
both regional pole placement and H performance for multi-model is proposed in [7] for coordination control of multiple PSSs
system. The multi-objective criterions are described by a set of for a multi-machine system. However, the robustness is not di-
bilinear matrix inequalities (BMI) regarding different system rectly considered in the design approach. In consideration of real
models at multiple operating points; then, a two-step method power system operation, it is mandatory that the damping con-
is introduced to solve the BMI optimization problem via linear
matrix inequality (LMI) algorithm. The proposed controller is
troller should have some degree of robustness to work against
evaluated by simulations on real-time digital simulator (RTDS). system uncertainties.
Numerical results from the simulations show that the proposed Over the years, many robust damping control approaches
controller can increase the damping of inter-area oscillations have been proposed for large power systems with multiple
under different system operating conditions. inter-area oscillation modes. The optimization of H and
Index Terms—BMI, H , inter-area oscillations, LMI, multi-ob- H norm is widely used for robustness design, disturbance
jective, multiple operating points, robust damping control, RTDS, rejection and control effort reduction: robust power system
TCSC, two-step method. stabilizer designs based on H performance are proposed in
[8] and [9]; mixed sensitivity H and mixed H approach
are proposed for the design of FACTS damping controllers in
I. INTRODUCTION [10]–[14]. Most of these designs are based on nominal oper-
ating point; control objectives from regional pole placement
T HE small-signal stability problems caused by low fre-
quency oscillations draw great attention in the last few
decades [1]. Much effort has been made to the damping control
to H and H performances are only guaranteed around one
particular operating point. However, on some occasions, the
system might not be operating under a nominal operating point,
studies to prevent system failure that might be caused by low
and the controller might not work as expected.
frequency oscillations. In large inter-connected power systems,
To address the above problem, robust damping control
low frequency oscillations can be classified as local oscillation
designs of a set of bilinear matrix inequalities (BMI) consid-
mode and inter-area oscillation mode: local mode (0.7–2.0 Hz)
ering multiple operating points or off-nominal operating points
is associated with rotor angle oscillations of a single generator
are introduced. In [15], an LMI based two-step method for
or single plant against the rest of the power system; inter-area
STATCOM damping controller design considering multiple op-
mode (0.1–0.7 Hz) is involved with subgroups of generators
erating points was proposed where a common output feedback
swinging against each other in different areas [2]. It is common
controller was determined in order to place the weakly damped
to find that local and inter-area oscillation modes may appear
poles of all system models into a desired LMI region. The
in a large system at the same time. The conventional root locus
drawback of this method is that the controller output effort is
damping control approaches in [3] and [4] show that installing
not limited which sometimes could cause numerical instability.
PSS on generator excitation system can provide supplemen-
In this paper, a multi-objective robust damping control design
tary control to damp out low frequency oscillations. With the
approach considering multiple operating points is proposed to
fast development of the FACTS technology, it has been proved
significantly improve the method in [15] by incorporating H
performance so that the controller output effort can be reduced
Manuscript received October 23, 2012; revised March 09, 2013 and under all operating points while avoiding the numerical insta-
September 13, 2013; accepted November 03, 2013. Date of publication January
09, 2014; date of current version June 16, 2014. Paper no. TPWRS-01188-2012. bility of the approach proposed in [15]. The control problem
The authors are with the School of Electronic, Electrical and Computer En- is initially formulated as synthesis optimization problem in
gineering, University of Birmingham, Edgbaston, Birmingham, B15 2TT, U.K. BMIs. However, for system with multiple operating points, it
(e-mail: dengjingchao0108@gmail.com; x.p.zhang@bham.ac.uk).
Color versions of one or more of the figures in this paper are available online
is impossible to solve the BMI problem by transferring it into
at http://ieeexplore.ieee.org. an LMI problem via system parameterization directly due to
Digital Object Identifier 10.1109/TPWRS.2013.2292067 the fact that the system state matrices are varying with system
0885-8950 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
DENG AND ZHANG: ROBUST DAMPING CONTROL OF POWER SYSTEMS WITH TCSC 1513
Combining (1) and (2), the synchronous generator and excita- (9)
tion system dynamics can be obtained as follows:
Equation (9) can be rewritten by scaling the value of the TCSC
(3)
reactance to the percentage compensation:
where .
The linearized stator algebraic equations of the corresponding (10)
generators are given in matrix form:
where % and is the reactance of
(4) the line that TCSC installed on.
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
1514 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014
(11)
Fig. 2. Close-loop system with regulated H output.
(12)
(13)
(14)
where and are the bus voltages for bus and bus .
Equation (11)–(14) can be rewritten by using non-generator bus
voltage
(15)
(16)
(17) Fig. 3. Pole placement region.
(18)
III. PROBLEM FORMULATION WITH MULTIPLE OBJECTIVES
D. Overall System In order to secure the robustness of the design, a common
output feedback controller is to be found for the multi-model
The overall system model is derived by combining the gen- system. Regional pole placement and H performance are em-
erator, exciter, network power flow and TCSC models, which ployed to increase the close-loop system damping and reduce
include (5), (6), (7), (8), (10) and (15)–(18). Equations (5) and the control effort. A block diagram of the close-loop system with
(10) are dynamic differential equations while the rest are linear H performance output is shown in Fig. 2.
algebraic equations. Substituting (15)–(18) into (8) and elimi-
nating the variables between (6), (7) and (8), the A. Regional Pole Placement
overall system model can be described by differential equations:
The damping performance of the close-loop system is highly
(19) related with the location of poles. With the controller, the weakly
damped poles should be placed in a specified conic sector region
(20) on the complex plane, as shown in Fig. 3, to satisfy the system
damping specifications. The damping ratio boundary can be de-
Combining (19) and (20), the overall system model can be rep- termined by the inner angle of the conic sector. Then, the pole
resented as placement region can be defined as an LMI region , as given
in (23), in order to incorporate with the multi-model system ma-
(21) trix variables to form the pole placement constraints in BMIs:
(24)
B. H Performance
where is the index of operating points and is the total number
of operating points. The H performance measures the overall energy of a
Combining these LTI systems, a multi-model system sharing system relating the input disturbance to the output response.
the same state vector and system output could be formed con- By choosing regulated as the H performance output, the
taining dynamic characteristics of different operating points. controller output energy against the disturbance can be
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
DENG AND ZHANG: ROBUST DAMPING CONTROL OF POWER SYSTEMS WITH TCSC 1515
reduced when the H norm is minimized In the first step, a state feedback controller is deter-
subject to , where is the weight mined by convex LMI method so that the close-loop system sat-
function. is usually selected as a high-pass filter or a isfies all design objectives. In the second step, the state feedback
small constant for H performance to reduce the control effort gain matrix variable obtained in the first step is plugged into
in the high frequency range [18]. In this paper, is set to the output feedback controller to find the matrix variable and
scalar 1 for the ease of the design. so that output feedback controller is equal or comparable to
It is known that the close-loop system is stable and the state feedback controller obtained in the first step.
holds if and only if there exist Lya-
punov matrix and a symmetric matrix such that [16] A. First Step: Determination of K
The close-loop system with the state feedback is given by
(28)
(25)
where
where Trace is the sum of the diagonal of matrix is
the close-loop system matrix for H output and denote entries
that follow from the symmetry. The control effort then could (29)
be reduced by minimizing subject to BMI con-
straints in (25). Substitute (29) into (24) and (25), the determination of in this
step is finally transferred into a multi-objective LMI optimiza-
tion problem:
IV. SOLVING THE BMI OPTIMIZATION: AN LMI BASED
TWO-STEP APPROACH
The synthesis problem of pole placement and H perfor-
mance can be formulated as a multi-objective BMI optimization
problem. For nominal model system, system parameterization
and transformation are applied to transfer the BMIs into LMIs
so that they could be solved by convex LMI solver. However,
this method is not applicable for multi-model system since
the state-space matrices are varying with different operating
points. Followed the techniques in [16], an LMI based two-step (30)
approach is proposed to solve the multi-objective BMI opti-
mization problem. where . The state feedback
The state-space realization of the multi-model system can be gain matrix is obtained as
written as
(31)
(27) where
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
1516 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014
(34)
(35)
where
(36)
and V. CONTROLLER DESIGN IMPLEMENTATION
A. Two-Area System
The proposed controller design is first implemented on a two-
area system [2], as shown in the Fig. 4. It is a simple testing
system consists of 4 synchronous generator and 10 buses; the
(37)
two areas are connected by two parallel tie lines between bus 7
and bus 8; TCSC is installed on one of the tie lines, providing
Now, the existence of structured Lyapunov matrix is decided by 25% line compensation for steady state operation. G1 and G3
the stability of matrices , which is already guaranteed are equipped with PSS to increase the damping of the local oscil-
in the first step. lation modes; however, the inter-area oscillation mode between
The determination of and can be considered to be the two areas is still weakly damped. With different load con-
finding a solution of the multi-objective LMI optimization figurations on bus 7 and bus 8, multiple operating points can be
problem, shown in (38) at the bottom of the page, where generated to form the multi-model system. Table I shows the
. The controller variable four operating points used in the following design for two-area
matrices and are obtained as system. A minimum damping ratio of 15% is selected as the
boundary of the pole placement region to make sure that the
settling time is less than 15 s.
(39) The controller input is selected from signals which contain
invaluable information of the inter-area oscillation mode, such
where are the optimal solutions of (38). as active line power flow, generator power output and generator
(38)
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
DENG AND ZHANG: ROBUST DAMPING CONTROL OF POWER SYSTEMS WITH TCSC 1517
TABLE II
DAMPING RATIO AND FREQUENCIES OF INTER-AREA MODES
Fig. 5. Frequency responses of the original system and reduced system for op-
erating point 1.
TABLE III
DAMPING RATIO AND FREQUENCIES OF INTER-AREA MODES
(40) area 1 and G10 to G13 belong to area 2; G14, G15 and G16 are
equivalent representation of area 3, area 4 and area 5. TCSC is
In the multi-model system, each linearized open-loop system installed between bus 50 and bus 52, providing 40% line com-
model and the output feedback controller to be designed will pensation for steady state operation. A nominal operating point
be in the order of 35; if H performance weights are included, is selected with 300 MW active power transferring from Area 1
the order will be even higher. To ease the design for the BMI to Area 2, detailed system parameters can be found in the PST
approach and reduce the complexity of the final controller, the packages attached to [20]. Similar to the two-area system, mul-
system models should be simplified in advance. Hankel norm tiple operating points can be generated by different load config-
approximation [18] is employed here to reduce the order of urations. Table IV shows the four operating points which form
system models to 7 without losing much information around the the multi-model system.
frequency of inter-area modes. A comparison of frequency re- Small-signal analysis is carried out to study the inter-area os-
sponse between the original system and the reduced system is cillation characteristics of the open-loop system. From Table V,
shown in Fig. 5 for operating point 1. it is clear that the 68-bus system has 4 dominant inter-area os-
When the controller is obtained, Hankel norm approximation cillation modes. By calculating the participation factors of the
is employed again for a further reduction of the controller. A state variables to each inter-area mode, it is known that mode 1
controller in the order of 5th, as shown in Appendix A, is finally is between Area 1, 2 and Area 3, 4, 5; mode 2 is between Area
acquired. In the end, a washout filter with the time constant of 1, 3 and 5; mode 3 is between Area 1 and 2; mode 4 is between
10 seconds is added to the controller to remove the d.c. signals Area 3, 5 and 4. A minimum damping ratio of 10% is used here
as it is suggested for inter-area mode in [4]. as the boundary of pole placement region for all the inter-area
Eigenvalue analysis is carried out to examine the close-loop oscillation modes.
system performance with the proposed controller, a compar- The choice of controller input signal is based on controlla-
ison of damping ratio and damping frequency between the bility, observability and residue analysis presented in [18]. In
open-loop system and the close-loop system with respect to dif- this case, the active power flow of the line adjacent to the TCSC
ferent operating points is shown in Table II. Furthermore, a com- (Line 50–51) is selected as the controller input.
parison of the close-loop system performance between the pro- In the multi-model system, each linearized model will be in
posed controller and a controller obtained via Xue’s approach the order of 148. Hankel norm approximation is employed here
[15] is shown in Table III. It is clear that the proposed con- to reduce the system order for further design. Table VI shows the
troller is robust against different operating points that we se- inter-area oscillation modes of the reduced system (7th order).
lected. Moreover, the close-loop system damping ratio with the Note that only 3 inter-area modes (mode 1–3) are included in the
proposed controller is much closer to our specified boundary reduced system for the robust pole placement. This is because
which means the controller output effort has been reduced. single FACTS damping controller sometimes is insufficient for
the damping of all inter-area oscillation modes in a large system
B. 68-Bus System and forcing the pole placement of all the modes may result in
In order to explore the feasibility of the proposed method an infeasible solution.
for larger power system, the controller design is consequently When the controller is obtained, Hankel norm approximation
implemented on a 68-bus system [20]. The 68-bus system, as is employed again for further reduction of the controller. A con-
shown in Fig. 6, is the reduced system of New England–New troller in the order of 6, as shown in Appendix B, is finally
York interconnected system. The system has been divided into acquired. A washout filter identical to the one in the two-area
5 different areas; synchronous generators G1 to G9 belong to system design is added here to remove d.c. signals.
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
1518 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014
TABLE VIII
TABLE V MULTIPLE OPERATING POINTS
DOMINANT INTER-AREA OSCILLATION MODES FOR OPEN-LOOP SYSTEM
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
DENG AND ZHANG: ROBUST DAMPING CONTROL OF POWER SYSTEMS WITH TCSC 1519
TABLE IX
DOMINANT INTER-AREA OSCILLATION MODES FOR OPEN-LOOP SYSTEM
TABLE X
DOMINANT INTER-AREA OSCILLATION MODES FOR CLOSE-LOOP
SYSTEM WITH MULTI-MODEL CONTROLLER
TABLE XI Fig. 7. Active power on Line 7: (a) operating point 1; (b) operating point 4.
DOMINANT INTER-AREA OSCILLATION MODES FOR CLOSE-LOOP
SYSTEM WITH NOMINAL MODEL CONTROLLER
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
1520 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014
Fig. 9. Active power on Line 7: (a) switching from operating point 1 to 4; Fig. 11. Active power on Line 1–2 and Line 8–9: (a) Line 1–2; (b) Line 8–9.
(b) switching from operating point 4 to 1.
Fig. 12. Active power on Line 8–9: switching from operating point 1 to 4;
(b) switching from operating point 4 to 1.
Fig. 10. Active power on Line 50–52: (a) operating point 1; (b) operating point
4.
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.
DENG AND ZHANG: ROBUST DAMPING CONTROL OF POWER SYSTEMS WITH TCSC 1521
(B)
transferred into LMI optimization by system parameterization, [9] H. Werner, P. Korba, and T. C. Yang, “Robust tuning of power system
and then solved by convex LMI solver. However, system pa- stabilizers using LMI-techniques,” IEEE Trans. Control Syst. Technol.,
vol. 11, no. 1, pp. 147–152, 2003.
rameterization is not applicable for multi-model system due to [10] M. Chilali and P. Gahinet, “H design with pole placement con-
the fact that system state matrices are varying with respect to straints: An LMI approach,” IEEE Trans. Autom. Control., vol. 41,
different models. Following the techniques presented in [16], pp. 358–367, 1996.
[11] M. M. Farsangi, Y. H. Song, and M. Tan, “Multi-objective design of
we proposed a two-step approach to solve the BMI optimiza- damping controllers of FACTS devices via mixed H with re-
tion problem with both regional pole placement and H perfor- gional pole placement,” Int. J. Elect. Power Energy Syst., vol. 25, no.
mance via LMI techniques. The proposed method has been im- 5, pp. 339–346, 2003.
plemented on the TCSC damping controller design for a two- [12] B. Chaudhuri and B. C. Pal, “Mixed-sensitivity approach to H con-
trol of power system oscillations employing multiple facts devices,”
area system and a 68-bus system. Analytical results showed IEEE Trans. Power Syst., vol. 18, no. 3, pp. 1149–1156, Aug. 2003.
that the proposed multi-model controllers were capable to im- [13] B. Chaudhuri and B. C. Pal, “Robust damping of multiple swing modes
prove the damping ratio of weakly damped inter-area oscillation employing global stabilizing signals with a TCSC,” IEEE Trans. Power
Syst., vol. 19, no. 1, pp. 499–506, Feb. 2004.
modes under different operating points with better performance [14] Y. Li and C. Rehtanz, “Wide-area robust coordination approach of
than the robust damping controllers designed on a nominal op- HVDC and FACTS controllers for damping multiple interarea oscil-
erating point. Finally, the proposed controllers have been vali- lations,” IEEE Trans. Power Del., vol. 27, no. 3, pp. 1096–1105, Jul.
2012.
dated on the 68-bus system by real-time simulations on RTDS. [15] C.-F. Xue and X.-P. Zhang, “Design of STATCOM damping control
Tests with different operating conditions have been carried out with multiple operating points: A multimodel LMI approach,” Proc.
to examine the robustness of the controller. Numerical results Inst. Elect. Eng., Gener. Transm. Distrib., vol. 153, pp. 375–382, 2006.
showed that the proposed controllers could effectively damp out [16] S. Kanev and C. Scherer, “Robust output-feedback controller de-
sign via local BMI optimization,” Automatica, vol. 40, no. 7, pp.
the inter-area oscillations under different operating conditions. 1115–1127, 2004.
[17] M. Noroozian, L. Angquist, M. Gandhari, and G. Andersson, “Im-
APPENDIX A proving power system dynamics by series-connected FACTS devices,”
IEEE Trans. Power Del., vol. 12, no. 4, pp. 1635–1641, Oct. 1997.
Robust TCSC damping controller for two-area system [18] B. C. Pal and B. Chaudhuri, Robust Control in Power Systems. New
York, NY, USA: Springer, 2005.
[19] J. H. Chow and J. J. Sanchez-Gasca, “Power system damping controller
(A) design using multiple input signals,” IEEE Magn. Control Syst., vol.
20, no. 4, pp. 82–90, 2000.
[20] G. Rogers, Power System Oscillations. Norwell, MA, USA: Kluwer,
Robust TCSC damping controller for 68 bus system is shown in 2000.
(B) at the top of the page. [21] P. Forsyth, T. Maguire, and R. Kuffel, “Real time digital simulation
for control and protection system testing,” in Proc. IEEE 35th Annu.
Power Electronics Specialists Conf., 2004, vol. 1.
REFERENCES
[1] J. Paserba, “Analysis and control of power system oscillation,” Tech. Jingchao Deng received the B.Eng. degree in electrical engineering and its au-
Brochure 111, 1996, in CIGRE Special Publication 38.01.07. tomation from Huazhong University of Science and Technology, China, in 2009
[2] P. Kundur, Power System Stability and Control. New York, NY, and the M.Sc. degree in control systems from Imperial College London, U.K.,
USA: McGraw-Hill, 1994. in 2010. He is currently pursuing the Ph.D. degree in electrical engineering at
[3] E. V. Larsen and D. A. Swann, “Applying power system stabilizers: the University of Birmingham, U.K.
Part I-III,” IEEE Trans. Power App. Syst., vol. PAS-100, no. 6, pp. His major research interests are power system stability analysis with FACTS
3017–3046, 1981. and HVDC.
[4] P. Kundur, M. Klein, G. J. Rogers, and M. S. Zywno, “Application of
power system stabilizers for enhancement of overall system stability,”
IEEE Trans. Power Syst., vol. 4, no. 2, pp. 614–624, May 1989.
[5] E. V. Larsen, J. J. Sanchez-Gasca, and J. H. Chow, “Concepts for de- Xiao-Ping Zhang (M’95–SM’06) received the B.Eng, M.Sc., and Ph.D. de-
sign of FACTS controllers to damp power swings,” IEEE Trans. Power grees in electrical engineering from Southeast University, China, in 1988, 1990,
Syst., vol. 10, no. 2, pp. 948–956, May 1995. and 1993, respectively.
[6] P. Pourbeik and M. J. Gibbard, “Damping and synchronizing torques He is currently a Professor in electrical power systems at the University of
induced on generators by FACTS stabilizers in multimachine power Birmingham, U.K., and he is also Director of the University Institute for Energy
systems,” IEEE Trans. Power Syst., vol. 11, no. 4, pp. 1920–1925, Nov. Research and Policy. Before joining the University of Birmingham, he was an
1996. Associate Professor in the School of Engineering at the University of Warwick,
[7] J. Ferraz, N. Martins, and G. Taranto, “Coordinated stabilizer tuning U.K. From 1998 to 1999, he was visiting UMIST, U.K. From 1999 to 2000, he
in large power systems considering multiple operating conditions,” in was an Alexander-von-Humboldt Research Fellow with the University of Dort-
Proc. IEEE Power Engineering Society General Meeting, 2007, pp. mund, Germany. He worked at China State Grid EPRI on EMS/DMS advanced
1–8. application software research and development between 1993 and 1998. He is
[8] P. S. Rao and I. Sen, “Robust pole placement stabilizer design using co-author of the monograph Flexible AC Transmission Systems: Modeling and
linear matrix inequalities,” IEEE Trans. Power Syst., vol. 15, no. 1, pp. Control (New York, NY, USA: Springer, 2006 and 2012).
313–319, Feb. 2000. Prof. Zhang is an Editor of the IEEE TRANSACTIONS ON POWER SYSTEMS.
Authorized licensed use limited to: Indian Institute Of Technology (Banaras Hindu University) Varanasi. Downloaded on July 24,2022 at 14:17:39 UTC from IEEE Xplore. Restrictions apply.