Professional Documents
Culture Documents
This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
Abstract—Growing penetration of converter-interfaced renew- a situation can be divided into different categories, which are
able energy sources with numerous control operations results in described in this section with their limitations.
non-homogeneous fault characteristics in the network. Distance 1) Decision with multiple settings: Distance relays with
relay Zone-1 operation with such non-homogeneous situation
may be vulnerable compromising both dependability and security fixed zone settings often underreach for high SIRs. Multiple
aspects. In this work, vulnerability analysis is carried out to iden- boundary settings may be available in a distance relay for
tify the factors influencing Zone-1 performance in a renewable different SIRs [14]–[17]. High penetration of CIRESs changes
integrated power network, and a method is proposed to ensure system dynamics rapidly. Instantaneous update in relay setting,
its correct operation. The method considers the homogeneity required for primary protection in dynamic system condition,
present in negative and zero sequence networks with converter-
based sources to obtain the faulted loop current angle using is difficult to achieve with such a scheme. Further, distance
local measurements and to derive correct decisions. The proposed relays with large fault resistance coverage are prone to load
method is tested for different renewable integrated systems, encroachment, especially in high SIR situations [17].
even with 100% converter-based sources and with variations in 2) Adaptive setting based approaches: Adaptive techniques
different vulnerable factors. Comparison with available distance are available in [9], [11] to set distance relays protecting lines
relaying techniques demonstrates the superior performance of
the proposed method. connecting wind plants. Information (like plant and weather
status) obtained through communication links are employed
Index Terms—Renewable integrated power network, power
in those methods, which may delay the protection decision.
network faults, distance relay, Zone-1 protection.
Adaptive Zone-1 setting techniques based on local data are
proposed in [18], [19] for stressed system conditions following
I. I NTRODUCTION structural and operational changes. The techniques requiring
A. Motivation source equivalent estimation are not evaluated with CIRESs.
3) Data Driven Approaches: Distance relays, set with data
P OWER grids are experiencing a rapid growth in converter-
interfaced renewable energy sources (CIRES) to meet the
ambitious decarbonization target [1]–[3]. Reliable power sys-
driven approaches, may compensate the effect of high fault
resistance [20], [21]. Converter control operation diversity
tem operation meeting the grid code requirements compels the and generation variability associated with renewable sources
control operations of the converters, interfacing such sources, compel such techniques to be under scrutiny. In addition, the
to adjust accordingly [4]. Grid-forming controls are now being requirement of a large number of training data sets in such
introduced in the converters to provide a stable grid operation approaches restrains their application in real power systems.
with high renewable penetration [5], [6]. Large renewable 4) Communication assisted schemes: Communication
plants connected to transmission networks are complied with based trip schemes are recommended in [22], [23] for lines
fault ride through capability [7], [8]. Thus, numerous control connecting CIRESs. Such schemes may also fail to ensure
actions associated with the converters influence the fault char- correct protection decision, when an internal fault is seen
acteristics in the network differently compared to the system outside the zone boundary for both end relays. In addition,
with only synchronous generators, which introduces non- the latency associated with trip-command-transfer delays the
homogeneity in the system with the modulation of equivalent decision obtained by such schemes.
impedances of the renewable plants. Generation variability and 5) Modification in Control schemes: Fault current char-
fault current limitation also influence the source-impedance- acteristic of a synchronous generator is imitated in [24] by
ratio (SIR) for the distance relay at renewable connected bus. suitable modification in CIRES control scheme. Diversity in
These factors impel to reevaluate distance relay performance control operation with different CIRESs creates difficulty in
for the networks with high penetration of renewable sources. generalizing such an approach.
6) Other Approaches: Fault resistance in the presence of
B. Literature Review infeed current from the remote end affects the distance relay
Converter control operations and the generation variability performance. Different adaptive techniques are available in
with CIRESs influence the performance of distance relay, [25]–[27] to compensate such an affect, which consider either
used commonly for network protection [9]–[13]. Techniques both end equivalent source impedances to be negligible and/or
proposed for distance relay performance improvement in such the system to be homogeneous. Both considerations are not
true for a CIRES integrated system. The adaptive distance re-
The work is supported in part by the Central Power Research Institute, laying technique proposed in [12] for lines connecting CIRESs
Bangalore, India, under Grant RSOP/2019/TR/07 and conducted at the De-
partment of Electrical Engineering, Indian Institute of Technology, Kharagpur, compensates the effect of fault resistance by estimating faulted
India (e-mail:paladhisubha91@gmail.com). path current angle using local data. The technique considers
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
pre pre
and generates balanced current even for asymmetrical faults
V1M − xZ1L I1M satisfying dynamic reactive current requirement imposed by
I1F = pf
(7)
Z1T + RF the applied grid code [4], [24]. The CIRESs follow the
pf
pf
(Z pf +xZ1L )((1−x)Z1L +Z1R ) NERC reliability standard guidelines for fault-ride-through and
where, Z1T = 1S Z pf +Z +Z pf . internal protection [33].
1S 1L 1R
Using (5) and (7), ∆Z in (4) can be rewritten as, Results in Fig. 5(a) demonstrate the performance of the
RF relay at bus 25 for phase-B-to-phase-C-to-ground (BCG) faults
∆Z = pf
(8) created in line 25-2 at a distance of 50% from bus 25 for
Z1T +RF
pre pre + C1 different RF and solar plant generation at bus 37. The solar
(V1M /I1M )−xZ1L
plant generation is maintained at 50% of its total capacity
With similar approach ∆Z for other types of faults is derived
for the fault cases with different RF , whereas the RF is
in Appendix-I, which reveals ∆Z to be a function of several
kept fixed at 15 Ω for the cases with different solar plant
variables as in (9).
generation. It is observed that the faults created in Zone-
pre
∆Z = f V1M pre
, I1M pf
, Z(0,1,2)S pf
, Z(0,1,2)R , Z(0,1,2)L , x, RF (9) 1 may be seen in Zone-2 with variation in fault severity
and solar plant generation. Sometime the apparent impedance
Subscripts ‘0’ and ‘2’ indicate the zero and negative sequence calculated for Zone-1 fault is seen to remain outside the Zone-
components respectively. A noticeable variation is observed 2 boundary. On the other hand, results in Fig. 5(b) demonstrate
pre pre
for V1M and I1M in a high renewable penetrated system the performance of the relay at bus 2 for phase-A-to-ground
with change in generation status of CIRESs, especially at (AG) faults created in line 25-26 at a distance of 10% from
the buses connected to large renewable plants. Pure-fault bus 25, for similar variation in RF and solar plant generation,
impedances of converter-based sources vary significantly in as considered for earlier case. Apparent impedances calculated
accordance with their control operation depending on the for Zone-2 faults may be seen in Zone-1 or may remain outside
fault severity. Equivalent system impedance without CIRESs the Zone-2 depending on RF and system conditions. For both
also gets affected following any structural and operational the cases, all CIRESs in the system operate with power factor
changes in the system. Influence of such variations on distance between 0.95 lag to 0.95 lead even during fault, following the
relay performance is demonstrated for different fault cases North American Grid Code (NAGC) [33]. Thus the distance
created in a renewable integrated 39-bus system, as in Fig. 4. relays may become vulnerable with both dependability and
The renewable plants (solar and wind farms), connected at security aspects with high penetration of renewable sources in
the system.
PV
Type–IV Zapp with variation in PV plant generation at bus 37 Zapp with variation in RF
37 38 WF
26 28 50
29 P V10% 25Ω (with only SG)
25 Zone-2 20Ω 35Ω 40 act
Zzone−2
15Ω P V100%
RF = 0 Ω 5Ω P V50% 5Ω
24 act 15Ω Zone-2
Zzone−1 RF = 0 Ω
27 0 (25) P V100% 20Ω
30 17 Zone-1 20 P V20%
X(Ω)
X(Ω)
10
Such issues demand a source-independent protection solu-
8 tion to ensure correct distance relay decision in renewable
32
9 PV integrated power systems.
Fig. 4. 39-bus system integrating renewable sources.
III. P ROPOSED M ETHOD FOR R ELIABLE D ISTANCE
bus 11, 14, 33, 37 and 38, are of 300 MVA each (detailed P ROTECTION D ECISION
specifications of the plants are mentioned in Appendix-II). A new protection method is derived in this section using
Solar plants are interfaced to grid through DC/AC inverter. For local voltage and current data to obtain correct distance
type-III wind farm, stator is directly connected to the grid and relaying decision for Zone-1 faults in a renewable integrated
the rotor is connected through a back-to-back power electronic power system.
converter. Type-IV wind farm is connected to the grid through Apparent impedance calculated by a distance relay in (1) is
full-scale AC-DC-AC converter. Following such standard con- rewritten in (10) by expanding the variables with their complex
verter arrangement, each renewable plant is interfaced to the forms.
grid through a dYg type step-up transformer [30]–[32]. Grid-
f
following converters interfacing the CIRESs are controlled in
VrM |I |
j(α−β) = x|Z1L |ejθ1L + F ej(γ−β) RF
f e (10)
f
synchronous reference frame with feedforward compensation IrM IrM
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
α and β are the phase angles of VrM and IrM . θ1L and γ dYg type connection in the main transformers connecting
represent the line impedance angle and the faulted path current CIRESs to the grid isolates the zero sequence network from the
phase respectively. (10) is rewritten in (11) by multiplying both CIRES control dynamics and maintain homogeneity as with
sides of (10) by ej(β−γ) . conventional sources. Thus γ in (18) can be calculated using
f
local zero sequence current as in (19).
VrM |I |
j(α−γ) = x|Z1L |ej(θ1L −γ+β) + F RF
f e (11) f
f γ = arg(3I0F ) = arg(I0M ) (19)
IrM IrM
Thus the phase angles required for protection decision using Thus γ in such a situation can be obtained as in (26).
(13) are derived as in (18). f
!
V2M
f f
f
γ = arg(−I2F ) = arg (26)
α = arg(VAM ), β = arg IAM +K0 I0M , γ = arg(3I0F ) (18) Z2L
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
I1RN1
I1RN2
Z1RN1
Z1RN2
Z1S1
I1RN1
I1RN2
I1M
Z1S2
F
Z1RN1
Z1RN2
Z1S1
I1M
Z1S2
Z1Tr1 M I1F N Z1Tr2 V1M
V1M xZ1L (1-x)Z1L E1S1 Rph
E1S2
E1S1
I1RN1
I1RN2
E1S2 F
Z1RN1
Z1RN2
Z1S1
I1M
Z1S2
3RF Z2Tr1 I2F Z2Tr2 Rph
Z2Tr1 I2F Z2Tr2 xZ2L (1-x)Z2L
xZ2L (1-x)Z2L V1M
I2RN1
I2RN2
E1S1
Z2RN1
Z2RN2
I2RN1
I2RN2
E1S2 I2M
Z2S1
Z2RN1
Z2RN2
I2M
Z2S2
Z2S1
Z2S2
2Rph V2M
V2M
Z2Tr1 I2F Z2Tr2
I0F Z0Tr2 xZ2L (1-x)Z2L
Z0Tr1 Z0Tr1 I0F Z0Tr2 3RF+Rph
(1-x)Z0L
I2RN1
I2RN2
xZ0L xZ0L (1-x)Z0L
Z2RN1
Z2RN2
I2M
Z2S1
Z2S2
I0M I0M
Z0S1
Z0S1
Z0S2
V2M
Z0S2
V0M V0M
Fig. 6. Sequence networks of the system in Fig. 1 for (a) AG, (b) BC and (c) BCG faults.
C. For BCG fault In (32), | sin (γ − β) | ≤ 1 and RF for ABC fault is also small
Applying KVL in the faulted loop of Fig. 6(c) (consisting of (< 1Ω) [27]. Thus, the value of |II f1F | becomes insignificant
| 1M |
negative and zero sequence network), a relation can be derived when multiplied by sin (γ − β) RF and (32) can be simplified,
as in (27). as in (33).
f f f 0 f f
V2M –V0M = xZ2L I2M –K0L I0M –I0F (1–m) Rph +3RF (27) V1M
f sin (α − β) = x|Z1L | sin θ1L (33)
where, K0L 0
= Z I2F
Z1L and m = I0F . Apparent impedance
0L I1M
relation for BCG fault can be derived from (27) and expressed Thus the indices D1 and D2 in (14) for such fault types are
as in (28). derived as in (34).
f f
V2M –V0M I0F f
f f
= xZ1L – f f
((1–m) Rph +3RF ) (28) V1M
I2M –K00 I0M I2M 0
–K0L I0M D1 = sin (α − β) , D2 = 0.8|Z1L | sin θ1L (34)
f
I1M
Rph being the arcing resistance associated with phases is
considered to be very small. It is negligible compared to RF
E. Proposed relaying algorithm
for high resistance faults. On the other hand, m becomes
a real term for faults with low RF , due to homogeneity in Steps to be followed in the proposed protection approach
the equivalent negative and zero sequence networks. Thus by are provided in Fig. 7. The scheme is initiated with fault
comparing (28) with (1), the relations for BCG faults are detection. An undervoltage check is provided in addition to the
obtained as follows. usual overcurrent check for fault detection. Negative sequence
component based checking is also applied in parallel to
f
VrM f
= V2M f
–V0M f
, IrM f
= I2M –K00 I0M
f
, IF = –I0F (29) enhance the sensitivity for faults with high RF [36]. Following
the detection of a fault, it is classified using available local
Thus the phase angles required for protection decision using
voltage measurements, as in [37]. Based on the fault type,
(13) for such a fault type can be obtained as in (30).
relay calculates
the indices D1 and D2 using (14) and (34).
f
α = arg V2M f
− V0M f
, β = arg I2M − K00 I0M
f
, When D D2
1
is obtained in the range of (0, 1] satisfying both
(30)
f
γ = arg(−I0F ) = arg(I0M )−π the conditions in (13), the relay identifies the fault to be in
Zone-1 and issues a trip decision.
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
D1 /D2
Zone-2 30%
70%
70% 50% 0.5 50%
20 50% Zone-1
30% 30% 70%
10% 10% Zone-2 fault
0 (25) 0
A. For faults at different locations Reverse fault
-20 Reverse fault on -0.5
line 25-26
Severity of a fault varies with its location from the relay bus 5 5.02 5.04
0 50 100
and it influences the control operation of the renewable plants Time (s)
R(Ω)
accordingly. Distance relay performance is affected signifi- (a) (b)
cantly by the CIRESs, close to the faulted line. Performance of Fig. 8. Performance of distance relay for faults at different locations using
(a) conventional and (b) proposed approaches.
the relay at bus 25 is tested for BCG faults created at different
locations in line 25-2, 25-26 and 2-3 with RF = 15 Ω. Results 40
35Ω
Zone-2 20Ω 2 D1
(D ) for zone-1 faults
in Fig. 8(a) demonstrate large differences between the apparent 20RF = 0Ω
25Ω Z conv for zone-1 faults 2
X(Ω)
app
(D
D2 ) for zone-2 faults
1
10Ω 15Ω
act
Zzone−1
impedances calculated by the conventional distance relay and 0
(25) Zone-1 1.5
the actual faulted line section impedances. It is observed that -20 D1 /D2
0 R(Ω)50 100
1
the relay may find Zone-1 faults in Zone-2 and malfunction
40 RF = 0Ω
at times. The proposed method calculates two indices using 10Ω
15Ω Zone-2
25Ω
conv
Zapp for zone-2 faults 0.5
X(Ω)
20
act
(14) and checks the
conditions, as in (13). Results in Fig. 8(b) Zzone−2
0
20Ω
Zone-1
35Ω
Zone-1 fault region
(2)
0
demonstrate that D D2
1
calculated by the relay for all the faults -20
0 50 100 0 5 10 15 20 25 30 35
created in line 25-26 is withinthe range (0,1], which confirm R(Ω) RF (Ω)
(a) (b)
the faults to be in Zone-1. D D2
1
is obtained as negative
Fig. 9. Performance of distance relay for faults with different RF using (a)
for the fault created in line 25-26 (in the reverse direction), conventional and (b) proposed approaches.
whereas it is calculated as greater than 1 for the Zone-2
fault created in line 2-3. Thus the proposed method ensures The proposed method is also tested at bus 25 for all types
correct Zone-1 performance for faults at different locations. of created at different locations with variation in RF .
faults
D1
Results in Fig. 8(b) demonstrate that the proposed method can D2 for some of those cases are provided in Table I. The
take correct decision within 1 cycle following fault inception, Zone-1 faults are created in the middle of line 25-26, faults
which satisfies the requirement of Zone-1 protection. in Zone-2 are created in line 2-3 at a distance of 20% from
bus 2 and faults in reverse direction are created in line 25-26
B. For faults with different fault resistances
at a distance of 10% from bus 25. Results provided in Table
Increase in fault resistance magnifies the effect of infeed I demonstrates that D D1
is obtained within (0,1] for Zone-
2
current on conventional distance relay performance and de- 1 faults, it is > 1 for Zone-2 faults and < 0 for faults in
viates the apparent impedance significantly from the actual reverse direction. Thus, the proposed method derives correct
faulted section impedance in R-X plane. The nature of this protection decision for all types of faults with variation in RF .
deviation depends on the both end current angles, which is
modulated by the control operation of the connected renewable C. For faults with change in renewable plant generation
plants. Results for two cases are presented in Fig. 9 demon- Generation variability in the renewable plants near the relay
strating the influence of RF on conventional and proposed bus affects the pre-fault voltage and current significantly and
methods. In the first case, performance of the distance relay influences distance relay performance accordingly. In addition,
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
TABLE I 1.5
D1 for Zone-2 faults
P ERFORMANCE E VALUATION FOR D IFFERENT TYPES OF FAULTS 30
For Zone-2 faults
D1 and D2 (Ω)
1
Fault RF Zone-1 fault Zone-2 fault Reverse fault
D1 /D2
20
Type (Ω) in line 25-2 in line 2-3 in line 25-26 D2 for Zone-2 faults
0.5
AG 0.1 0.63 1.38 -0.12 D2 for Zone-1 faults For Zone-1 faults
10
Zone-1 fault detection region
BG 10 0.63 1.40 -0.13 0
D1 for Zone-1 faults
CG 100 0.64 1.45 -0.13 0
0 10 30 50 70 100 with with
only SG 0 10 30 50 70 100
only SG
BC 0.1 0.63 1.50 -0.11 PV plant generation (%) PV plant generation (%)
CA 1 0.62 1.45 -0.12 (a) (b)
AB 5 0.61 1.38 -0.14
Fig. 11. Performance of the proposed method with change in solar plant
BCG 0.1 0.63 1.43 -0.13 generation: (a) D1 and D2 , (b) (D1 /D2 ).
ABG 10 0.62 1.38 -0.12
CAG 100 0.57 1.31 -0.11
0.1 0.62 1.47 -0.12 generation variations on adjacent line protection, BCG faults
ABC 1 0.62 1.34 -0.13 (with RF = 15 Ω) are created in line 14-4 and line 29-26
5 0.58 1.21 -0.13 at a distance of 50% from bus 14 and 29 respectively, where
the protection methods are tested. Generations at type-III and
type-IV wind farms connected at bus 14 and 38 are varied for
change in renewable plant generation modifies the equivalent this study. Results provided in Fig. 11 demonstrate that the
impedance of the plant and also modulates the pure-fault apparent impedance calculated by conventional distance relay
impedance based on the control operation in the present varies significantly with change in generation of the adjacent
generation status. Two cases are presented to demonstrate the wind farm and the relays fail to identify Zone-1 faults correctly
performance of distance relay in such a scenario. In the first in such
situations. The relays with proposed method calculate
case, BCG faults are created in line 25-2 at a distance of 50% D1
D2 for all the cases, which are provided in Table II. All the
from bus 25 with RF = 15 Ω and performance of relay at bus values satisfy both the conditions in (13) implying the faults
25 is tested with variation in solar plant generation at bus 37. In to be in Zone-1. This demonstrates the proposed method to
the second case, AG faults with RF = 20 Ω are created in line be independent of renewable plant generation adjacent to the
25-26 at a distance of 10% from bus 25 and the performance protected line.
of relay at bus 2 is tested for similar generation variation in
the solar plant at bus 37. Performance of conventional distance 40 40
Zone-2
relays are provided in Fig. 10. Relays are observed to perform act
Zone-2
10% Zzone−1 10%
correctly when only synchronous generator is connected at 20 50% 20 50%
X(Ω)
bus 37, but both relays maloperate at times with solar plant act
Zzone−1 100% X(Ω) 100%
30%
0 70% 0 30%
integration. Dependability for Zone-1 faults and security for (14)
Zone-1
(29) Zone-1 70%
act P V10%
Zzone−1 P V70%
0 P V100% 0 D. With change in grid code compliance of the adjacent
X(Ω)
(25) (2)
Zone-1 Zone-1
renewable plant
-20 -20
Ratio between active and reactive fault current from a
0 50 100 0 50 100
R(Ω) R(Ω) renewable plant changes with the grid code to satisfy the fault
(a) (b) ride through requirements. Thus the fault current angle from
Fig. 10. Performance of distance relay with change in solar plant generation a renewable plant is modulated with the change in grid code
for(a) Zone-1 and (b) Zone-2 faults. compliance. Such modulation influences conventional distance
relay performance significantly. Two cases are presented here
remotely connected do not influence much on the protection to demonstrated the performance of distance relays at bus 25
of line 25-2. In order to verify the influence of wind farm and 2, when the solar plant connected at bus 37 is complied
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
with two different grid codes, one at a time. With the first one, replaced by a type-III and a type-IV wind farm, one at a
the solar plant operates close to unity power factor (similar time. All the CIRESs are controlled with balanced current
to NAGC). On the other hand, the solar plant interfacing controller and inject only positive sequence current even for
converter prioritizes reactive current injection while complied asymmetrical faults. In addition, the methods are tested by
with the second one (as followed in European Union grid incorporating negative sequence current injection capability
code (EU-GC)) [4], [24]. Results in Fig. 13(a) demonstrate in the solar plant. Results shown in Fig. 15(a) demonstrate
the performance of distance relay at bus 25 for BCG faults that the apparent impedance calculated by distance relay varies
created in line 25-2 at a distance of 50% from bus 25 with significantly with change in control operation associated with
RF = 15 Ω. On the other hand, performance of distance relay the CIRES connected at the relay bus and results in relay
at bus 2 is presented in Fig. 13(b) for AG faults, created in line maloperation. On the other hand, D 1
D2 calculated for all
25-26 at a distance of 10% from bus 25 with RF = 20 Ω. It is those cases (as shown in Fig. 15(b)) are found to satisfy
observed that the apparent impedance calculated by a distance both the conditions in (13) ensuring correct Zone-1 protection
relay varies significantly with change in grid
code compliance decisions. This demonstrates the correct performance of the
and may results in maloperation at times. D D2
1
calculated by proposed method when the fault current at relay bus is only
the proposed method for all the cases are shown in Fig. 14. fed from CIRES and it is independent of control operation
Results demonstrate that both the conditions mentioned in the associated with the CIRES.
proposed method are satisfied correctly even with change in
60
grid code compliance. Thus the performance of the proposed ZSolar
app
(with negative sequence current)
Solar (with balanced current controller)
Solar (with negative sequence current injection)
method remain unaffected when CIRESs connected in the 40 Zone-2 Type-III Wind farm
Type-IV Wind farm
system are complied with different grid codes. 20 Z act
zone−1
1.5
X(Ω)
Zone-1
0 1
(25) ZType-IV wind
D1 /D2
40 with EUGC 40 app
act
Zone-2 Zzone−2 -20 0.5
with NAGC Zone-2 ZType-III wind
app 0
20 20 -40
X(Ω)
ZSolar
X(Ω)
app
(with balanced current controller)
act
Zzone−1 with NAGC with EUGC
-0.5
0 50 100 5 5.01 5.02 5.03 5.04
0 0
(25) (2)
Zone-1
R(Ω) Time (s)
(a) (b)
-20 -20
0 50 100 0 50 100
R(Ω) Fig. 15. Performance of (a) distance relay and (b) the proposed method for
R(Ω)
(a) (b) lines connecting only CIRES at the local end with different control schemes.
Fig. 13. Performance of distance relay with change in grid-code compliance
in the adjacent renewable plant for (a) Zone-1 and (b) Zone-2 faults.
F. For a system with 100% converter-based sources and
Comparative assessment
Zone-1 With EUGC With NAGC
D1 /D2
0.5 0.5
to the grid through grid-following converter, whereas the solar
plants at bus 1 and 3 are integrated through grid-forming
0 0
converters. The grid-following converter operates with bal-
5 5.02 5.04 5.06 5 5.02 5.04 5.06 anced current controller, as used in the previous case studies.
Time (s) Time (s)
On the other hand, grid-forming converters with dual-current
(a) (b)
controller are designed to mimic synchronous generator neg-
ative sequence impedance angle to maintain homogeneity as
Fig. 14. Performance of the proposed method with change in grid-code with considered in Section-III.B. A BCG fault is created in line 7-8
the adjacent renewable plant for (a) Zone-1 and (b) Zone-2 faults.
at a distance of 50% from bus 7 with RF = 15 Ω and the
performance of the distance relay at bus 7 is tested.
Results in Fig. 17 provides a comparative assessment with
E. Performance evaluation for lines connecting only CIRES conventional distance relaying and the method available in
at the local end with different control schemes [12]. As demonstrated in Fig. 17(a), the distance relay with
Impact of converter-control operation becomes more promi- conventional approach fails to find the fault within Zone-
nent on protection decision when the relay bus is only 1 boundary due to the non-homogeneous fault response in
connected to CIRESs. Considering line 25-26 to be out-of- the system. The method available in [12] considers the grid
operation, performance of distance relay and the proposed connected at remote end of the protected line to be strong
method is tested for such situations at bus 25 for BCG faults with sufficient conventional synchronous generators, which
created in line 25-2 at a distance of 25% from bus 25 with is not true for a system, as considered here. Result in
RF = 25Ω. Impact of four different control operations is Fig. 17(b) shows a significant difference between the fault
demonstrated in this study. The solar plant at bus 37 is section impedance calculated using the method with the actual
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
∆
1
is proposed to ensure correct Zone-1 operation. The method
Grid-forming
16.5 kV derives distance relay decision by estimating the faulted path
200 MVA
current angle. Use of the homogeneity present in negative
Fig. 16. 9-bus system with 100% converter-based sources. and zero sequence networks for the estimation ensures the
accurate performance of the proposed method for any line in
a power network with or without the connection of converter-
and exposes its limited performance for converter-dominated based sources. The method does not require any additional
power systems. On the other hand, the proposed method meets information or measurement for its implementation. The im-
the criteria of (13), as shown in Fig. 17(c) and identifies the proved performance of the proposed method is demonstrated
fault in Zone-1 correctly. This confirms the proposed method for change in fault location, fault resistance, renewable plant
to be independent of system strength and sources with different generation, and grid code compliance of the CIRESs. Correct
control operations. It also reveals the necessity and advantages performance in a system with 100% converter-based sources
of the proposed method over conventional distance relaying validates the method to be independent of system strength
and the method available in [12]. and converter-control operation. Comparative assessment with
available distance relaying techniques demonstrates the ne-
Conventional Distance relaying With the method in [12] Using Proposed Method
cessity and superiority of the proposed method in the new
scenario of power grid operation.
Impedance Magnitude (Ω)
50 250 1.5
Fault inception
Zone-2 200
Zact
MF 1
F Zone-1
D1 /D2
150 A PPENDIX -I
X(Ω)
0 (7) Zone-1
100 Z act
0.5
MF
[12]
∆Z for different types of asymmetrical faults (AG, BC and
50 Z MF
Zconv
app 0 BCG) are derived in this section using the Sequence networks
-50 0
0 50 100 5 5.02 5.04 5 5.02 5.04 5.06 provided in Fig. 6.
R(Ω) Time (s) Time (s)
(a) (b) (c)
A. For AG fault
Fig. 17. Performances of (a) conventional distance relaying, (b) the method in
[12] and (c) the proposed method for fault in a system with 100% converter- The relay operating current for AG fault is expressed as,
based sources.
f f f pre f f
IrM = IAM +K0 I0M = I1M +∆I1M +I2M +(1 + K0 ) I0M . (35)
The proposed protection method is compared with a few Using the sequence network in Fig. 6 (a), the faulted loop
advanced distance relaying techniques proposed in recently current can be expressed as,
available literature [12], [13], [40]–[42]. The comparative as-
sessment is summarized in Table III. The table clearly depicts IF = I1F = I2F = I0F (36)
the advantages of the proposed method when compared to
Using (35) and (36), ∆Z in (1) can be expressed as,
the other available techniques for converter-dominated power
systems. 3RF
∆Z = pre f f
. (37)
I1M ∆I1M I2M I0M
I1F
+ I1F
+ I2F
+ (1 + K0 ) I0F
TABLE III
C OMPARATIVE A NALYSIS WITH R ECENT AVAILABLE M ETHODS I1F in Fig. 6 (a) can be obtained as,
Available Methods Proposed pre pre
Parameters V1M − xZ1L I1M
[40] [41] [42] [13] [12] Method I1F = pf
. (38)
Applicable for all types Z1T + Z2T + Z0T + 3RF
No Yes No Yes Yes Yes
of faults?
Applicable in weak grid where,
Yes No Yes No No Yes
condition? (Z2S1 + xZ2L ) ((1 − x)Z2L + Z2S2 )
Tested with high renewa-
No No No No No Yes
Z2T =
ble penetration in grid? Z2S1 + Z2L + Z2S2
Method independent of ((Z0T r1 ||Z0S1 ) + xZ0L ) ((1 − x)Z0L + (Z0T r2 ||Z0S2 ))
CIRES control scheme?
Yes No No Yes Yes Yes Z0T =
(Z0T r1 ||Z0S1 ) + Z0L + (Z0T r2 ||Z0S2 )
No requirement of remote
Yes Yes Yes No Yes Yes
end information? Thus, ∆Z for AG fault can be derived as,
Applicable to all buses
No No No No No Yes RF
in the system?
∆Z = pf
. (39)
Z1T +Z2T +Z0T +3RF
pre pre + C1 + C2 + (1 + K0 ) C0
(V1M /I1M )−xZ1L
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
where, TABLE IV
S IMULATION PARAMETERS OF CIRES S CONNECTED TO THE S YSTEM
(1 − x)Z2L + Z2S2
C2 =
Z2S1 + Z2L + Z2S2 Plant Specifications
(1 − x)Z0L + (Z0T r2 ||Z0S2 ) Unit Capacity: 1 MVA; Total number of units: 300
C0 = .
(Z0T r1 ||Z0S1 ) + Z0L + (Z0T r2 ||Z0S2 ) Current Controller: KP = 0.15 & Ti = 0.08 s
Solar
Rated DC bus voltage: 600 V
Plant
B. For BC fault DC Link capacitor: 7800 µF
Filter: Lf = 300µH, Cf = 200µF, Rf = 0.025Ω
The relay operating current for BC fault is expressed as, Unit capacity: 5 MVA; Total number of units: 60
f
IrM f
= I1M f
− I2M pre
= I1M f
+ ∆I1M − I2M . (40) Machine terminal voltage: 0.69 kV
Converter reactor: 134 mH
Type-III
Using the sequence network in Fig. 6 (b), the faulted loop Cf = 700µF, Cdamp = 300µF, Ldamp = 620 mH,
Wind
current can be expressed as, Rdamp = 1.33 Ω, DC crowbar on voltage: 2.2 kV
Farm
DC chopper activation voltage = 1.7 kV
IF = I1F − I2F = 2I1F . (41) DC chopper Off voltage = 1.5 kV
Using (40) and (41), ∆Z in (1) can be rewritten as, Shunt resistor: 1.2 Ω
Unit capacity: 5 MVA; Total number of units: 60
2I1F Rph Machine terminal voltage: 0.69 kV
∆Z = pre f
. (42)
I1M + ∆I1M − I2M Type-IV Converter reactor: 200 µH
I1F in Fig. 6 (b) can be obtained as, Wind VSC DC voltage set point = 1.45 kV
Farm Maximum reactive power = 0.3 pu
pre pre
V1M − xZ1L I1M Filter: Cf = 1000µF, Cdamp = 500µF,
I1F = pf
. (43)
Z1T + Z2T + 2Rph Ldamp = 1 mH, Rdamp = 1 Ω
Thus, ∆Z for BC fault is derived as,
2Rph A PPENDIX -II
∆Z = pf
. (44)
Z1T +Z2T +2Rph
pre pre + C1 − C2 R EFERENCES
(
V1M /I1M )−xZ1L
[1] “Renewables integration in india,” NITI Ayog, International
C. For BCG fault Energy Agency, Tech. Rep., April 2021, [Online]. Available:
https://iea.blob.core.windows.net/assets/7b6bf9e6-4d69-466c-8069-
The relay operating current for BCG fault is expressed as, bdd26b3e9ed1/RenewablesIntegrationinIndia2021.pdf.
[2] H. Lund and B. V. Mathiesen, “Energy system analysis of 100%
f f f pre f
IrM = I1M − I2M = I1M + ∆I1M − I2M . (45) renewable energy systemsthe case of denmark in years 2030 and 2050,”
Energy, vol. 34, no. 5, pp. 524–531, 2009.
Using the sequence network in Fig. 6 (c), the faulted loop [3] “Green energy corridors-II: (Part-A),” Power Grid Cor-
poration of India Ltd., Tech. Rep., [Online]. Available:
current for BCG fault can be expressed as, https://www.powergrid.in/sites/default/files/footer/smartgrid/Green%20
Energy%20Corridor%202-Part%20A.pdf.
IF = I1F − I2F . (46) [4] IRENA, “Grid codes for renewable powered systems,” International
Renewable Energy Agency, Abu Dhabi, Tech. Rep., April 2022.
Applying current distribution property in Fig. 6 (c), I2F can [5] W. Du, F. K. Tuffner, K. P. Schneider, R. H. Lasseter, J. Xie, Z. Chen,
be expressed as, and B. Bhattarai, “Modeling of grid-forming and grid-following invert-
I2F = −D2 I1F . (47) ers for dynamic simulation of large-scale distribution systems,” IEEE
Transactions on Power Delivery, vol. 36, no. 4, pp. 2035–2045, 2021.
[6] ESIG, “Grid-forming technology in energy systems integration,” Energy
where, Systems Integration Group, Tech. Rep., March 2022.
Z0T + Rph + 3RF [7] H. M. Hasanien, “An adaptive control strategy for low voltage ride
D2 = .
Z2T + Z0T + 2Rph + 3RF through capability enhancement of grid-connected photovoltaic power
plants,” IEEE Trans. Power Syst., vol. 31, no. 4, pp. 3230–3237, July
Using (45) and (46), ∆Z in (1) can be rewritten as, 2016.
[8] Y. Wang and B. Ren, “Fault ride-through enhancement for grid-tied PV
(1 + D2 ) I1F Rph systems with robust control,” IEEE Trans. Ind. Electr., vol. 65, no. 3,
∆Z = pre f
. (48) pp. 2302–2312, March 2018.
I1M + ∆I1M − I2M
[9] A. K. Pradhan and G. Joos, “Adaptive distance relay setting for lines
I1F in Fig. 6 (c) can be obtained as, connecting wind farms,” IEEE Trans. Energy Conv., vol. 22, no. 1, pp.
206–213, March 2007.
pre pre [10] A. Hooshyar, M. A. Azzouz, and E. F. El-Saadany, “Distance protection
V1M − xZ1L I1M
I1F = pf (Z0T +Rph +3RF )(Z2T +Rph )
. (49) of lines emanating from full-scale converter-interfaced renewable energy
Z1T + Rph + Z2T +Z0T +2Rph +3RF
power plants; part I: Problem statement,” IEEE Trans. Power Del.,
vol. 30, no. 4, pp. 1770–1780, Aug 2015.
Thus, ∆Z for BCG fault can be derived as, [11] K. E. Arroudi and G. Joos, “Performance of interconnection protection
based on distance relaying for wind power distributed generation.” IEEE
(1 + D2 ) Rph Trans. Power Del., vol. PP, no. 99, pp. 1–1, 2017.
∆Z = . (50) [12] S. Paladhi and A. K. Pradhan, “Adaptive distance protection for lines
pf (
Z0T +Rph +3RF Z2T +Rph )( )
Z1T +Rph + Z2T +Z0T +2Rph +3RF connecting converter-interfaced renewable plants,” IEEE J. Emerg. and
pre pre + C1 − C2 Sel. Topics Power Electron., vol. 9, no. 6, pp. 7088–7098, 2021.
(
V1M /I1M −xZ1L )
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2022.3218615
[13] Y. Fang, K. Jia, Z. Yang, Y. Li, and T. Bi, “Impact of inverter-interfaced reliability services by a 300-MW solar photovoltaic power plant,”
renewable energy generators on distance protection and an improved National Renewable Energy Lab.(NREL), Golden, CO (United States),
scheme,” IEEE Trans. Ind. Electr., vol. 66, no. 9, pp. 7078–7088, Sep. Tech. Rep., 2017.
2019. [31] PSCAD, “Type 3 wind turbine model,” Tech. Rep., November 2018.
[14] M. Thompson and A. Somani, “A tutorial on calculating source [32] PSCAD, “Type 4 wind turbine model,” Tech. Rep., December 2018.
impedance ratios for determining line length,” in Proc. 68th Annual [33] NERC, “Reliability guideline: Improvements to interconnection
Conference for Protective Relay Engineers, March 2015, pp. 833–841. requirements for BPS-connected inverter-based resources,” Atlanta,
[15] G. E. Alexander, J. G. Andrichak, and W. Z. Tyska, “Relaying GA 30326, Tech. Rep., September 2018, [Online]. Available:
short lines,” GE Power Management, Tech. Rep., [Online]. Available: https://www.nerc.com/comm/OC Reliability Guidelines DL/Inverter-
http://store.gedigitalenergy.com/faq/documents/alps/ger-3735.pdf. Based Resource Performance Guideline.pdf.
[16] Siemens, “Distance protection relay for transmission lines,” Tech. Rep., [34] VDE-AR-N 4130, “Technical requirements for the connection and
1999, [Online]. Available: ftp://ftp.so-cdu.ru/RZA/Siemens/SIPROTEC operation of customer installations to the extra high voltage network
[17] Alstom, “Network protection and automation guide,” Tech. Rep. 978-0- (TCR extra high voltage),” Tech. Rep., November 2018.
9568678-0-3, May 2011. [35] M. Nagpal, M. Jensen, and M. Higginson, “Protection challenges and
[18] S. Paladhi and A. K. Pradhan, “Adaptive zone-1 setting following practices for interconnecting inverter based resources to utility transmis-
structural and operational changes in power system,” IEEE Trans. Power sion systems,” Working Group C32, Power System Relaying and Control
Del., vol. 33, no. 2, pp. 560–569, April 2018. Committee, Tech. Rep., 2020.
[19] S. Paladhi and A. Pradhan, “Resilient protection scheme preserving [36] S. Paladhi and A. K. Pradhan, “Adaptive fault type classification for
system integrity during stressed condition,” IET Gen., Trans. Distr, transmission network connecting converter-interfaced renewable plants,”
vol. 13, no. 14, pp. 3188–3194, 2019. IEEE Syst. J., vol. 15, no. 3, pp. 4025–4036, 2021.
[20] K. Li, L. Lai, and A. David, “Stand alone intelligent digital distance [38] A. Zitouni, “Power transformer differential relay reliability assessment
relay,” IEEE Trans. Power Systems, vol. 15, no. 1, pp. 137–142, Feb using false trip root cause analysis,” in International Conference on
2000. Electrical Engineering (ICEE), 2020, pp. 1–5.
[21] J. Upendar, C. Gupta, and G. Singh, “Comprehensive adaptive distance [39] R. W. Kenyon, A. Sajadi, A. Hoke, and B.-M. Hodge, “Open-source
relaying scheme for parallel transmission lines,” IEEE Trans. Power PSCAD grid-following and grid-forming inverters and a benchmark for
Del., vol. 26, no. 2, pp. 1039–1052, April 2011. zero-inertia power system simulations,” in IEEE Kansas Power and
[22] A. Hooshyar, M. A. Azzouz, and E. F. El-Saadany, “Distance protection Energy Conference (KPEC), 2021, pp. 1–6.
of lines connected to induction generator-based wind farms during [40] Y. Liang, W. Li, and Y. Huo, “Zone i distance relaying scheme of
balanced faults,” IEEE Trans. Sustainable Energy, vol. 5, no. 4, pp. lines connected to MMC-HVDC stations during asymmetrical faults:
1193–1203, Oct 2014. Problems, challenges, and solutions,” IEEE Trans. Power Del., vol. 36,
[23] A. Hooshyar, M. A. Azzouz, and E. F. El-Saadany, “Distance protection no. 5, pp. 2929–2941, 2021.
of lines emanating from full-scale converter-interfaced renewable energy [41] K. Ma, H. K. Hoidalen, Z. Chen, and C. L. Bak, “Improved zone 1 top-
power plants ; part II: Solution description and evaluation,” IEEE Trans. line tilting scheme for the polygonal distance protection in the outgoing
Power Del., vol. 30, no. 4, pp. 1781–1791, Aug 2015. line,” CSEE Journal of Power and Energy Systems.
[24] A. Banaiemoqadam, A. Hooshyar, and M. A. Azzouz, “A control-based [42] C. Chao, X. Zheng, Y. Weng, Y. Liu, P. Gao, and T. Nengling,
solution for distance protection of lines connected to converter-interfaced “Adaptive distance protection based on the analytical model of addi-
sources during asymmetrical faults,” IEEE Trans. Power Del., vol. 35, tional impedance for inverter-interfaced renewable power plants during
no. 3, pp. 1455–1466, 2020. asymmetrical faults,” IEEE Trans. Power Del., 2021, available in early
[25] Y. Liang, Z. Lu, W. Li, W. Zha, and Y. Huo, “A novel fault impedance access.
calculation method for distance protection against fault resistance,” IEEE
Trans. Power Del., vol. 35, no. 1, pp. 396–407, 2020.
[26] J. Ma, W. Ma, Y. Qiu, and J. Thorp, “An adaptive distance protection
scheme based on the voltage drop equation,” IEEE Trans. Power Del.,
vol. 30, no. 4, pp. 1931–1940, Aug 2015. Subhadeep Paladhi received PhD degree in Electrical Engineering
[27] V. Makwana and B. Bhalja, “A new digital distance relaying scheme from Indian Institute of Technology, Kharagpur, India in 2021. He
for compensation of high-resistance faults on transmission line,” IEEE is currently working as a Research Associate in the Department
Trans. Power Del., vol. 27, no. 4, pp. 2133–2140, Oct 2012. of Electronic and Electrical Engineering, University of Strathclyde,
[28] C. K. Alexander, Fundamentals of Electric Circuits. McGraw-Hill, Glasgow, U.K.
2009.
[29] G. Ziegler, Numerical Distance Protection: Principles and Applications. Jaisaikiran Reddy Kurre received M.Tech. degree in Electrical
John Wiley & Sons, 2011. Engineering from Indian Institute of Technology, Kharagpur, India.
[30] C. Loutan, P. Klauer, S. Chowdhury, S. Hall, M. Morjaria, V. Chadliev,
Ashok Kumar Pradhan is a Professor in the Department of
N. Milam, C. Milan, and V. Gevorgian, “Demonstration of essential
[37] A. Hooshyar, E. F. El-Saadany, and M. Sanaye-Pasand, “Fault type Electrical Engineering, Indian Institute of Technology, Kharagpur,
classification in microgrids including photovoltaic DGs,” IEEE Trans. India. Prof. Pradhan is a Fellow of Indian National Academy of
Smart Grid, vol. 7, no. 5, pp. 2218–2229, Sept 2016. Engineering and the National Academy of Sciences, India.
© 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSITY OF STRATHCLYDE. Downloaded on November 02,2022 at 06:17:40 UTC from IEEE Xplore. Restrictions apply.