Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: Robust analysis for decentralized load frequency control (LFC) for multi-area power systems is studied in
Received 30 June 2010 this paper. It is observed that such an analysis can be decomposed into two steps considering the inher-
Received in revised form 26 May 2012 ent structure of a multi-area power system: robustness analysis against the parametric variations in
Accepted 29 May 2012
local-area power systems and robustness analysis against the structure and/or magnitude variations in
Available online 15 July 2012
the tie-line power flow network. A detailed structured singular value method is proposed for local-area
robustness analysis, and an eigenvalue method is derived for tie-line robustness analysis. The proposed
Keywords:
method is then applied to a four-area power system and the results show that the method is convenient
Load frequency control
Robustness
and useful for decentralized load frequency control of multi-area power systems.
Decentralized control Ó 2012 Elsevier Ltd. All rights reserved.
Multi-area power systems
Structured singular value
0142-0615/$ - see front matter Ó 2012 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.ijepes.2012.05.063
W. Tan, H. Zhou / Electrical Power and Energy Systems 43 (2012) 996–1005 997
Nomenclature
Dfi frequency deviation of Area #i (Hz) DPti generator output in Area #i (p.u. MW)
Bi frequency bias setting of Area #i (p.u. MW/Hz) Ggi(s) transfer function of the governor in Area #i
Tij synchronizing coefficients between Area #i and Area #j Gti(s) transfer function of the turbine in Area #i
(p.u. MW/Hz) Gpi(s) transfer function of the rotor inertia and load in Area #i
DPdi load disturbance in Area #i (p.u. MW) Ri speed regulation of Area #i (Hz/p.u. MW)
DPtiei tie-line power between Area #i and other areas (p.u.
MW)
analysis is based on recent method ([11]) proposed to analyze the ACEi ¼ DPtiei þ Bi Dfi ð1Þ
stability of a multi-area power system under a decentralized LFC.
and the feedback control for Area #i takes the form
The method takes the inherent structure of the multi-area power
system into consideration, and makes it possible to check the im- ui ¼ K i ðsÞACEi ð2Þ
pacts of parametric variations in the local-area power systems
where Ki(s) is the local LFC controller.
and the structure and/or magnitude variations in the tie-line
According to [12,13], a decentralized controller can be designed
power flow network sequentially. Robustness analysis against the
assuming that there are no tie-line power flows, i.e.,
two groups of uncertainties will then be discussed. Finally, the pro-
DPtiei = 0(i = 1, . . . , n). In this case the local feedback control will be
posed method will be applied to analyze the decentralized LFC for a
four-area power system. It is shown that the method is convenient ui ¼ K i ðsÞBi Dfi ð3Þ
and useful for decentralized load frequency control of multi-area Denote the transfer functions of the governor, the turbine, and
power systems. the rotor inertia and load for Area #i by Ggi(s), Gti(s), and Gpi(s),
respectively, then the transfer function from ui to Dfi can be easily
2. Stability analysis of decentralized LFC found as
3. Robustness analysis of decentralized LFC where the perturbations take the form
DA ¼ E DF a ; DB ¼ E DF b ð16Þ
Due to changes of operation points, the parameters of the power
systems are not fixed, so it is crucial for a designed LFC control to Here D is a set of unknown but bounded parameters, E, Fa and Fb are
achieve robust performance. According to Fig. 3, uncertainties for known constant matrices with compatible dimensions. Then the
multi-area power systems can be divided into two groups: uncer- closed-loop system remains stable for all D such that kDk1 6 1 if
tainties in local-area power systems and uncertainties in the tie- and only if
line power flow network. A detailed robustness analysis can be lD ðMÞ < 1 ð17Þ
done using structured singular value (SSV) method, however, since where lD(M) is the structured singular value with respect to struc-
there are correlations between the local-area power systems and ture D defined in [14] and
the tie-line network, it is very complicated to perform such a de-
tailed analysis. Instead, we can analyze system robustness for the M :¼ P11 P12 KðI þ P22 KÞ1 P 21 ð18Þ
two groups of uncertainties sequentially, i.e., we will first make with
sure that the designed local LFC is robust for local-area power sys-
tems, and then make sure the whole controller is robust for tie-line P11 ¼ F a ðsI AÞ1 E; P 12 ¼ F a ðsI AÞ1 B þ F b
ð19Þ
operation. P21 ¼ CðsI AÞ1 E; P 22 ¼ CðsI AÞ1 B
and C ¼ ½ 1 0 0 0 . e c=s
hðsÞ ¼ detðI þ NT=sÞ ¼ 1 þ NðsÞ ð29Þ
Suppose the uncertain parameters are
where
m1 :¼ 1=T P ; m2 :¼ K P =T P ; m3 :¼ 1=T T ;
ð22Þ e N1 ðsÞ 0 1
m4 :¼ 1=RT G ; m5 :¼ 1=T G ; m6 :¼ 1=T r : NðsÞ ¼ ½ 1 1 ¼ N1 ðsÞ þ N2 ðsÞ ð30Þ
0 N2 ðsÞ 1
and that each parameter is varied within a bound, i.e.
So the maximum c such that the power system remains stable
mi ¼ mi0 ð1 þ wi di Þ ð23Þ e
is the largest gain which destabilizes NðsÞ=s. It can be checked by
e
using the root locus of NðsÞ=s.
where mi0 is the nominal value of the ith parameter, wi is the rela-
For interconnected power systems with more than two areas,
tive variation ratio of mi, and di is an uncertain parameter normal-
the tie-lie power flow network ‘T’ is much more complicated. For
ized as [1, 1].
instance, for a three-area power system several cases might be ta-
Define the set of uncertain parameters as
ken into consideration: operations with three tie-lines, with two
2 3
d1 tie-lines, and with one tie-line (the case without tie-line operation
6 d2 7 is trivial). Each case has its tie-line network matrix, so for a three-
6 7
6 7 area power system seven different matrices need to be considered
6 d3 7
D :¼ 6
6
7
7 ð24Þ for T. The number of combination increases with the number of
6 d4 7
6 7 areas. Moreover, the magnitude of each tie-line power flow is dif-
4 d5 5 ferent. So it is complicated to determine if the decentralized LFC is
d6 robust enough for structural uncertainties in tie-line operations.
However, once a the tie-lien topology is determined, the stability
It is noted that D has been normalized such that kDk1 < 1.
of the whole power system can be checked with Theorem 1. The
With the parameters of the local area power system varied as
complexity lies in enumerating the combination of tie-line opera-
(23), then the variations on state-space matrices A and B can be
tions, not the method in verifying the stability.
described as in (16) with
In summary, the stability of the whole power system relies on
2 3
m10 w1 m20 w2 0 0 0 0 the structure of the tie-line network, the magnitude of each tie-line
6 0 0 m30 w3 0 0 7 flow, and the local load frequency controllers. Checking the roots of
6 7
E¼6 7 ð25Þ h(s) under different tie-line network structure and magnitude can
4 0 0 0 m40 w4 m50 w5 0 5
verify the performance of the designed decentralized LFC.
0 0 0 0 0 m60 w6
2 3 2 3 4. Control area with different generation units
1 0 0 0 0
6 0 1 0 0 7 607
6 7 6 7 The model in Fig. 2 assumes that the individual control loops
6 7 6 7
6 0 1 c 1 7 607 and turbine-generators have the same regulation parameters and
F a :¼ 6
6 1 0
7; F b :¼ 6 7 ð26Þ
6 0 0 7
7
607
6 7 response characteristics. In practical power utilities, there are
6 7 6 7 many generators in each control area with different turbine-gover-
4 0 0 1 0 5 415
nor parameters and generation types. Furthermore, generators
0 0 1c 1 0
may or may not participate in the LFC task and participation rates
By Theorem 2, we can check the robust stability of a local-area are not the same for all participant generators [16]. In order to con-
power system using (17). sider the variety of generation dynamics and their sharing rate in
1000 W. Tan, H. Zhou / Electrical Power and Energy Systems 43 (2012) 996–1005
Fig. 5. Block diagram of control area i with different generation units and participating factors.
Bode Diagram
50
0
Magnitude (dB)
−50
−100
−150
0
Phase (deg)
−90
−180
−270
−1 0 1 2 3
10 10 10 10 10
Frequency (rad/sec)
Fig. 6. Bode diagrams of the dynamics of a multi-unit control area and its equivalence (solid: multi-unit area; dashed: lumped area).
−3
x 10
0.01 5
0.005
0 0
Δ f1 (Hz)
Δ f2 (Hz)
−0.005
−0.01 −5
−0.015
−0.02 −10
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3
x 10
5 0.01
0 0.005
Δ f3 (Hz)
Δ f4 (Hz)
−5 0
−10 −0.005
−15 −0.01
−20 −0.015
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3 −3
x 10 x 10
4 3
2
2
(p.u.MW)
(p.u.MW)
0
1
−2
tie−2
tie−1
0
−4
ΔP
ΔP
−1
−6
−8 −2
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3 −3
x 10 x 10
4 3
2 2
Δ Ptie−3 (p.u.MW)
(p.u.MW)
0 1
tie−4
−2 0
ΔP
−4 −1
−6 −2
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
Fig. 8. Responses of the four-area power system (solid: Tij = 0.0707; dashed: Tij = 0.444; dotted: Tij = 0.73).
If the generation units in a control area shown in Fig. 5 are of the and
same type, then the area can be simplified to a control area in Fig. 2. R1 ¼ 3; R2 ¼ 3; R3 ¼ 3:3 ð34Þ
For example, suppose a control area has three generation units with
non-reheated turbines, and the parameters of the units are The rated powers of the three units are
P1 ¼ 300 MW; P2 ¼ 200 MW; P3 ¼ 250 MW ð35Þ
1 1 1
Gg1 ¼ ; Gt1 ¼ ; Gp1 ¼ and suppose the participating factors for the three units are
0:08s þ 1 0:4s þ 1 0:1667s þ 0:015
1 1 1 a1 ¼ 0:4; a2 ¼ 0:4; a3 ¼ 0:2 ð36Þ
Gg2 ¼ ; Gt2 ¼ ; Gp2 ¼ ð33Þ
0:06s þ 1 0:36s þ 1 0:12s þ 0:014 The first step in simplifying is to find an equivalent generator
1 1 1 for all the units in the area. The inertia and damping of the equiv-
Gg3 ¼ ; Gt3 ¼ ; Gp3 ¼
0:07s þ 1 0:42s þ 1 0:2s þ 0:015 alent generator is the weighted sum of all the inertia and damping
1002 W. Tan, H. Zhou / Electrical Power and Energy Systems 43 (2012) 996–1005
−3 −3
x 10 x 10
5 4
2
0
0
Δ f (Hz)
Δ f (Hz)
−5 −2
2
−4
−10
−6
−15 −8
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3
x 10
5 0.01
0.005
0
0
Δ f (Hz)
Δ f (Hz)
−5 −0.005
4
3
−0.01
−10
−0.015
−15 −0.02
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3 −3
x 10 x 10
4 2.5
2
2
(p.u.MW)
(p.u.MW)
1.5
0 1
tie−1
tie−2
−2 0.5
ΔP
ΔP
0
−4
−0.5
−6 −1
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3 −3
x 10 x 10
4 3
2 2
(p.u.MW)
Δ Ptie−3 (p.u.MW)
1
0
0
tie−4
−2
−1
ΔP
−4
−2
−6 −3
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
Fig. 9. Responses of the four-area power system under structure variation in the tie-line network (solid: current; dashed: Case 1; dashdotted: Case 2).
of the generators in the area, where the weights accounts for the 1 1
Gg ðsÞ ¼ ; Gt ðsÞ ¼ ð38Þ
portion of each unit in the total rated power. So the dynamics of 0:07133s þ 1 0:396s þ 1
the equivalent generator is
1
Gp ðsÞ ¼ ð37Þ and the speed regulation is lumped as R = 3.0938. The Bode diagram
0:1653s þ 0:01473 of the original local-area dynamics and the reduced local-area
Now the dynamics of the turbines and governors are lumped dynamics are shown in Fig. 6. They are very close so there is no loss
using the same idea as for the equivalent generator. They are found of generality to use the control area shown in Fig. 2 in LFC analysis
as and design if all the units are of the same type.
W. Tan, H. Zhou / Electrical Power and Energy Systems 43 (2012) 996–1005 1003
A better approximation can be found by approximating the lo- decentralized LFC cannot guarantee the stability of the multi-area
cal-area dynamics (31) with a reduced-order transfer function in power system.
the frequency domain, especially when the number of generation To test the performance of the designed decentralized LFC
units in the control area is large. Moreover, even if the generation against tie-line network interaction, suppose a step load
units are not of the same type, the lumped area in Fig. 2 is still DPd1 = 0.01 is applied to Area #1 at t = 10 and a step load
applicable in analyzing the effects of the tie-line flow, with Gti(s)G- DPd3 = 0.01 is applied to Area #3 at t = 50. The system responses
gi(s) replaced by a single transfer function which is approximated are shown in Fig. 8 for the nominal tie-line network and the cases
in the frequency domain from the local-area dynamics (31). that Tij = 0.444 (increased by a factor of 2p) and Tij = 0.73 (near sta-
bility margin). From the simulation results, it is observed that the
5. Illustrative example decentralized LFC works very well for weak tie-line network, and
performance degrades for strong tie-line network, which com-
Consider a four-area power system discussed in [17,13]. A sim- pletely agrees with the analysis discussed above.
ple diagram of the four-area power system is shown in Fig. 7,
where Areas #1,#2,#3 are interconnected while Area #4 is only 5.2. Robustness against tie-line structure change
connected with Area #1.
It is assumed that Areas #1, #2, #3 are identical systems with Despite the possible magnitude change of the tie-line power
reheated turbines. The parameters are: flow network, its structure may also be changed. We consider
two circumstances under the current network structure with a
1 ci T ri s þ 1 1 K Pi
Ggi Gti Gpi ¼ ð39Þ strong interaction (Tij = 0.444):
T Gi s þ 1 T ri s þ 1 T Ti s þ 1 T Pi s þ 1
with Case 1. Area #4 is connected to Area #2 (T24 = T42 = 0.444).
Case 2. Area #2 is disconnected from Area #1 (T12 = T21 = 0).
T Gi ¼ 0:2; T Ti ¼ 0:3; T Pi ¼ 20; K Pi ¼ 120;
T ri ¼ 20; ci ¼ 0:333 ði ¼ 1; 2; 3Þ ð40Þ The system responses under the same load disturbances as be-
and Ri = 2.4. Area #4 is a power system with hydro turbine, with the fore are shown in Fig. 9. It is observed that the designed decentral-
open-loop plant model given by: ized LFC works well in Case 2, but performance degrades for Case 1.
In fact, the minimal damping ratio of h(s) is 0.0054 for Case 1 and
1 0:513s þ 1 1 s 80 0.1364 for Case 2. Compared with the nominal damping 0.0947, it
Gg Gt Gp ¼ ð41Þ
48:7s þ 1 10s þ 1 1=2s þ 1 13s þ 1 is observed that disconnecting one area from an existing power
network may increase the damping of the system, while connect-
and R = 2.4. The synchronizing constants are
ing more areas into an existing power network may decrease the
T 12 ¼ T 21 ¼ T 13 ¼ T 31 ¼ T 23 ¼ T 32 ¼ 0:0707 ð42Þ damping of the system. The large oscillation in Case 1 indicates
T 14 ¼ T 41 ¼ 0:0707; T 24 ¼ T 42 ¼ T 34 ¼ T 43 ¼ 0 ð43Þ that the decentralized LFC can only provide a very weak damping
to the multi-area power system, so for Case 1 it needs to be re-
and the frequency bias constants Bi(i = 1, 2, 3, 4) are 0.425 for each tuned to achieve good damping.
area.
In [13], the following PID controllers are tuned for Areas #1, #2
5.3. Robustness against local-area uncertainties
and #3,
1:5847 Another source of uncertainties in a multi-area power system
K i ðsÞ ¼ 2:4457 þ þ 1:5261s ði ¼ 1; 2; 3Þ ð44Þ
s lies in the parameters of the local area. We can utilize Theorem 2
to analyze the effects of parametric variations on the stability of
and the following modified PID controller is tuned for Area #4.
the system. Assume that there are 40% variations in all the param-
0:0216 3:8787s þ 1 eters in Areas #1, #2, #3, and 18% in Area #4, the SSV plots (lD(M))
K 4 ðsÞ ¼ 0:1456 þ þ 18:7715s ð45Þ
s 0:03919s þ 1
We would like to test the robust performance of this decentral- 1
ized LFC under different situations.
0.9
1, the minimum damping ratio for h(s) is 0.4219, so the nominal 0.5
−3
x 10
0.01 5
0.005
0
Δ f2 (Hz)
Δ f (Hz)
0
−5
1
−0.005
−10
−0.01
−0.015 −15
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3
x 10
5 0.01
0 0.005
Δ f4 (Hz)
Δ f3 (Hz)
−5 0
−10 −0.005
−15 −0.01
−20 −0.015
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3 −3
x 10 x 10
4 3
2
2
(p.u.MW)
Δ Ptie−2 (p.u.MW)
0
1
−2
tie−1
0
−4
ΔP
−6 −1
−8 −2
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
−3
x 10
−3 x 10
4 3
2 2
Δ Ptie−3 (p.u.MW)
Δ Ptie−4 (p.u.MW)
0 1
−2 0
−4 −1
−6 −2
0 20 40 60 80 100 0 20 40 60 80 100
Time (sec.) Time (sec.)
Fig. 11. Responses of the four-area power system (solid: nominal; dashed: +40% parametric variations in Areas #1, #2, #3, and +18% in Area #4; dashdotted: 40% parametric
variations in Areas #1, #2, #3, and 18% in Area #4).
of each area are shown in Fig. 10. From the plot, if there are 40% To test the robust performance of the designed decentralized
parameter variations in Areas #1, #2, #3, the maximums of the LFC against uncertainties in local-area power systems, suppose a
SSV are just less than 1, so robustness is guaranteed by Theorem step load D Pd1 = 0.01 is applied to Area #1 at t = 10 and a step
2. It is the same with Area #4. If the variations are more than load DPd3 = 0.01 is applied to Area #3 at t = 50. The system
40% in Areas #1, #2, #3 (or 18% in Area #4), the SSV will be larger responses are shown in Fig. 11 when there are 40% simultaneous
than 1, and then robustness is not guaranteed. Since the open-loop variation in the models of Areas #1,#2 and #3 and 18% simulta-
model (5) of Area #4 is unstable, it is not easy to achieve similar neous variation in the model of Area #4, and the magnitude of
robustness in Area #4 without performance degradation as in the tie-line network is 0.444. They validate the statements
other areas, where the open-loop models are stable. above.
W. Tan, H. Zhou / Electrical Power and Energy Systems 43 (2012) 996–1005 1005
6. Conclusion [5] Yang TC, Ding ZT, Yu H. Decentralized power system load–frequency control
beyond the limit of diagonal dominance. Int J Eelctr Power Energy Syst
2002;24(3):173–84.
Robust analysis of decentralized load frequency controller for [6] Bevrani H, Mitani Y, Tsuji K. Sequential design of decentralized load frequency
multi-area power systems was discussed in this paper. Robust controllers using l synthesis and analysis. Energy Convers Manage
2004;45:865–81.
analysis for the whole system was decomposed into two steps:
[7] Alrifai MT, Hassan MF, Zribi M. Decentralized load frequency controller for a
robustness analysis for local-area power systems and that for tie- multi-area interconnected power system. Int J Electr Power Energy Syst
line operation. The method was shown to be useful for decentral- 2011;33(2):198–209.
[8] Farhangi R, Boroushaki M, Hosseini SH. Load–frequency control of
ized LFC tuning. Further research on efficient robustness tests
interconnected power system using emotional learning-based intelligent
against structure variations of tie-line power network for large controller. Int J Electr Power Energy Syst 2012;36(1):76–83.
power systems is under investigation. [9] Yazdizadeh A, Ramezani MH, Hamedrahmat E. Decentralized load frequency
control using a new robust optimal MISO PID controller. Int J Electr Power
Energy Syst 2012;35(1):57–65.
Acknowledgment [10] Khodabakhshian A, Pour ME, Hooshmand R. Design of a robust load frequency
control using sequential quadratic programming technique. Int J Electr Power
This work was supported by the National Natural Science Foun- Energy Syst 2012;40:1–8.
[11] Tan W. Decentralized load frequency controller analysis and tuning for multi-
dation of China under Grant 61174096, the Natural Science Foun- area power systems. Energy Convers Manage 2011;52(5):2015–23.
dation of Beijing under Grant 4122075, and the Natural Science [12] Tan W. Tuning of PID load frequency controller for power systems. Energy
Foundation of Hebei under Grant F2011502069. Convers Manage 2009;50(6):1465–72.
[13] Tan W. Unified tuning of PID load frequency controller for power systems via
IMC. IEEE Trans Power Syst 2010;25(1):341–50.
References [14] Doyle JC. Analysis of feedback systems with structured uncertainties. IEE Proc
Control Theory Appl 1982;129:242–50.
[1] Kundur P. Power system stability and control. McGraw-Hill; 1994. [15] Tan W, Xu Z. Robust analysis and design of load frequency controller for power
[2] Ibrabeem PK, Kothari DP. Recent philosophies of automatic generation control systems. Electric Power Syst Res 2009;79(5):846–53.
strategies in power systems. IEEE Trans Power Syst 2005;20(1):346–57. [16] Bevrani H, Mitani Y, Tsuji K. Robust decentralized load–frequency control
[3] Shayeghi H, Shayanfar HA, Jalili A. Load frequency control strategies: a state- using an iterative linear matrix inequalities algorithm. IEE Proc Gener Transm
of-the-art survey for the researcher. Energy Convers Manage 2009;50 Distrib 2004;151(3):347–54.
(2):344–53. [17] Chang CS, Fu WH. Area load frequency control using fuzzy gain scheduling of
[4] Lim KY, Wang Y, Zhou R. Robust decentralized load–frequency control of PI controllers. Electr Power Syst Res 1997;42(2):145–52.
multi-area power systems. IEE Proc Part C 1996;143:377–86.