Professional Documents
Culture Documents
1
Contents:
1) Introduction
2) Literature survey
3) Background of Automatic Generation Control
4) Load Frequency Control of a Single Area System
5) General Aspects of Two Area Automatic Generation
Control
6) Automatic Generation Control of Two Equal Area
Reheat Thermal System Considering Tie Line Power
Non-Linearity
7) Simulation and PSO Based Optimization of an AGC
System After Deregulation
8) Conclusion
2
9) References
1) Introduction
Advantages of Interconnected Power System
Decrease in the probability of black outs.
Increasing power exchange among different system
Use of old and peak load plants.
Reduces plant reserve capacity.
Increases diversity factor
This can be done by measuring a control error signal, called the area control
error (ACE), which represents the real power imbalance between generation
and load, and is a linear combination of net interchange and frequency
deviations.
4
Classical control approaches reveal that it will result in relatively large
overshoots and transient frequency deviation.
PI Controller:
Eliminate the steady state error resulting from P controller.
Mostly used in areas where speed of the system is not an issue.
P-I controller has no ability to eliminate the oscillations.
5
Optimum control dynamics including zero steady state error, fast
response (short rise time), no oscillations and higher stability.
Necessity of using a derivative gain component in addition to the PI
controller is to eliminate the overshoot and the oscillations occurring in
the output response of the system.
Main advantages of the P-I-D controller is that it can be used with
higher order processes.
6
2) Literature Survey
12
The speed and induced electro motive force (e.m.f) of ac motors may
vary because of the change of frequency of the power circuit.
If the frequency is below the normal value, the flux in the core
increases. As a result, the magnetizing current even exceeds the normal
full load current. The sustained under frequency operation of the power
transformer results not only in low efficiency, but it may even damage
the transformer winding due to overheating.
13
ΔP = .Cosδ.Δδ
Or, ΔP є Δδ
Secondary Control:
Secondary control is in large power systems which include two or more
areas of interconnected power system. Active power is controlled at the
tie line between neighboring areas of central and local load control
along with distribution center.
15
4).Load Frequency Control of a Single Area
System
Speed governing system:
It consists of the
following parts:
1) Speed governor:
Flyball type
Sense change in freq.
2) Linkage mechanism:
Provide movement to
the control valve
3) Hydraulic amplifier:
4) Speed changer:
Provide steady state
output setting
16
(a) Model of speed governing system:
1 K g
y E (s) PC (s) F (s)
R 1 Tg s
Kg
GH
1 Tg s
Where,
ΔyE = steam valve opening
R = speed regulation of governor
ΔPc = commanded reference power
ΔF = change in frequency
Kg = gain of speed governor
Tg = time constant of speed
governor
17
(b) Turbine model:
Where,
Tt = time constant of turbine (generally 0.25
sec or so)
ΔPm = Output of turbine
ΔyE = Steam valve opening (Output of
governer)
18
Linearized Model of a Reheat Turbine Controller
19
(d) Complete Modeling of Single Area Conventional System
Using Integral Controller:
20
Modeling of two area thermal power plant
(a) Tie line model:
21
(b) Implementation of Area Control Error in Model :
22
In two area system the control signals (for each area) are proportional to the
change in frequency as well as change in tie line power.
The area control errors for a two area system are given by:
ACE1 P12 B1 f
ACE2 P21 B2 f
The area control error ACEi of the ith area for m no. of tie line system is
m
A CEi Pij Bi f i
j 1
The tie line power data of all the lines are sampled continuously at sampling
intervals of about 1 second or so. These data are added in an energy control
centre and compared with desired interchange (decided earlier by mutual
agreements).
The total line power transfer error is added to frequency bias power transfer
to give the area control error.
The ACE command is communicated to the speed changers of all the
generators in the area.
23
5). General Aspects of Two-Area
Automatic Generation Control
The aim of the control is to regulate the frequency in both the areas and
also to regulate the power flow over the tie line as per the agreement
between the utilities of systems A and B.
The following assumptions are made in the analysis of the two area
system: -
1. The overall governing characteristic of the operating units in any area
can be represented by a linear curve of frequency versus generation.
24
Types of Automatic Load Frequency Control For
Interconnected Power Systems:
25
(a) Load Increment in area B-no Controller
(b) Load Increment in area B and Frequency Controller in area B
26
27
Response between Frequency and Time for Smaller System
28
Response between Tie Line Power and Time
29
2. Flat Tie Line and Flat Frequency Control:
30
Response of Frequency Controller in Area A and Tie-Line
Controller in Area B for Two Interconnected Stations
31
Response between Frequency and Time for Bigger System
32
Response between Frequency and Time for Smaller System
33
Response Between Tie Line Power and Time
34
Load increment in area A-sequence of operation B-A-B for Two
Interconnected Stations
t1-t2 – Governor response
t3-t4 – Tie-line controller acts – frequency decreases w.r.t t2
t5 – Frequency Controller in A acts and restores frequency – Tie line
schedule become upset now.
Note – Stable operating conditions cannot be attained
35
Response between Frequency and Time for Bigger System
36
37
Response between Tie Line Power and Time
38
3. Tie-Line Bias Control:
Here the regulator does not act to hold a constant tie-line interchange regardless
of system frequency, but instead allows the tie line schedule to deviate from the
normal in adjustable proportion to frequency deviations from the normal rated
value.
39
Load increment in area B-sequence of operation A-B-A (controller in A
initiates first) for Two Interconnected Stations
41
Response between Frequency and Time for Smaller System
42
Response between Tie Line Power and Time
43
4. Complete Tie-Line Bias Control:
With tie-line bias controllers located in both the areas the control action is
complete in all the cases.
44
Controller Action in A for Local Load Changes for Two Interconnected
Stations
45
Response between Frequency and Time for Bigger System
46
Effect of biasing:
47
Response between Tie Line Power and Time
48
6). AUTOMATIC GENERATION CONTROL OF A TWO
EQUAL AREA REHEAT THERMAL SYSTEM
CONSIDERING TIE LINE POWER NONLINEARITY
ΔPD1(s)
+ +
Kp1/(1+sTp1)
+ + +
B1 1/R1 -
FHP FIP FLP
+r
+ - + 1/
-KT1/s 1/TG1 1/s 1/(1+sTr1) 1/(1+sTc1)
+ (1+sTt1)
-r
+ + +
- Pt(s) 2π/s
- - -
Ptie δ12
a12
+r
+ -
-K12/s + 1/TG2 1/s 1/(1+sTt2) 1/(1+sTr2) 1/(1+sTc2) a12
+ + -
-r
B2 1/R2
FHP FIP FLP
+ + -
+ +
Kp2/(1+sTp2)
+
ΔPD2
49
Response between Frequency and Time for Bigger System
50
Response between Frequency and Time for Smaller System
51
Response between Tie Line Power and Time
52
7). SIMULATION AND PSO BASED OPTIMIZATION
IN AN AGC SYSTEM AFTER DEREGULATION
In a traditional power system structure, the generation, transmission and distribution is
owned by a single entity called vertically integrated utility.
DISCO can contract individually with a GENCO through TRANSCOs for power and
these transactions are done under the supervision of the Independent System Operator
(ISO).
DISCO may or may not have contracts with GENCOs in their own area.
DPM is a matrix with the no. of rows equal to the no. of GENCOs and the
no. of columns equal to the no. of DISCOs in the system.
54
DISCO1 DISCO2 GENCO3 GENCO4
Off diagonal blocks correspond to the demands of the DISCOs in one area
to the GENCOs in another area.
55
Suppose DISCO3 demands 0.1 pu MW power,
cpf13 = , cpf23 =
cpf33 = , cpf43 =
56
Block Diagram Formulation
ACE participation factors (apfs): Coefficients that distribute ACE to several
GENCOs.
As there are many GENCOs, ACE signal has to be distributed among them in
proportion to their participation in the AGC.
Error signal is used to generate the respective ACE signals as in the traditional
scenario,
ACE1 = B1Δf1 + ΔPtie1-2, error
ACE2 = B2Δf2 + ΔPtie2-1, error
Where,
ΔPtie2-1, error = - (Pr1/Pr2)ΔPtie1-2, error
59
Flow Diagram Illustrating the Particle Swarm Optimization Algorithm
60
The algorithm keeps track of three global variables:
Stopping value indicating when the algorithm should stop if the target
isn't found.
A personal best (pBest) value indicating the closest the particle's data has
ever come to the target.
61
Advantages:
PSO is based on the intelligence. It can be applied into both scientific research
and engineering use.
The calculation in PSO is very simple. Compared with the other developing
calculations, it occupies the bigger optimization ability and it can be completed
easily.
PSO adopts the real number code, and it is decided directly by the solution. The
number of the dimension is equal to the constant of the solution.
Disadvantages:
The method easily suffers from the partial optimism, which causes the less exact
at the regulation of its speed and the direction.
The method cannot work out the problems of scattering and optimization.
The method cannot work out the problems of non-coordinate system, such as
the solution to the energy field and the moving rules of the particles in the
energy field. 62
Simulation Results of Two Area System Based on Conventional and
PSO in the Deregulated Environment
Thus the load is demanded only by DISCO1 and DISCO2. Let the value of this
load demand be 0.1 pu MW for each of them.
65
Dynamic Response of Frequency Deviation in Area – 2
Dynamic Response of Power Deviation in Tie Line
66
Dynamic Response of Turbine Power Gen 1 in Area – 1 (MW)
Dynamic Response of Turbine Power Gen 2 in Area – 1 (MW)
67
Dynamic Response of Turbine Power Gen 3 in Area – 2 (MW)
Dynamic Response of Turbine Power Gen 4 in Area – 2 (MW)
Case 2:
Now DISCOs contract with the GENCOs for power as per the following DPM,
Assume that the total load of each DISCO is changed by 0.1 pu and each GENCO
participates in AGC as defined by the following apfs:
apf1=0.75, apf2=1-apf1=0.25; apf3=0.5, apf4=1-apf3=0.5 68
Dynamic Response of Frequency Deviation in Area - 1
69
Dynamic Response of Frequency Deviation in Area - 2
Dynamic Response of Power Deviation in Tie Line
70
Dynamic Response of Turbine Power Gen 1 in Area – 1 (MW)
Dynamic Response of Turbine Power Gen 2 in Area – 1 (MW)
71
Dynamic Response of Turbine Power Gen 3 in Area – 2 (MW)
Dynamic Response of Turbine Power Gen 4 in Area – 2 (MW)
Consider case 2 again with a modification that DISCO1 demands 0.1 pu MW of excess
power.
The total load in area 1 (ΔPL1, LOC ) = Load of DISCO1+ load of DISCO2
= (0.1 + 0.1) + 0.1 pu MW = 0.3 pu MW
Similarly,
The total local load in area 2 (ΔPL2, LOC)
= Load of DISCO3 + load of DISCO4
72
= 0.2 pu MW (no uncontracted load)
Dynamic Response of Frequency Deviation in Area - 1
73
Dynamic Response of Frequency Deviation in Area - 2
Dynamic Response of Power Deviation in Tie Line
74
Dynamic Response of Turbine Power Gen 1 in Area – 1 (MW)
Dynamic Response of Turbine Power Gen 2 in Area – 1 (MW)
75
Dynamic Response of Turbine Power Gen 3 in Area – 2 (MW)
Dynamic Response of Turbine Power Gen 4 in Area – 2 (MW)
76
7).Conclusions
The subnormal frequency results in malfunctioning of ac motors, transformers and may
result in complete shutdown of plants.
For large interconnected power systems, it is necessary to control frequency and tie line
power simultaneously for better operation of system.
For a load frequency control of a single area system, secondary controllers are used. The
best controller used for this purpose is integral controller. The proper integral gain setting
can reduce the frequency deviation to zero.
An individual flat frequency control or tie line control method is not able to operate the
interconnected power system satisfactorily, so it is necessary to match the speed governor
characteristic and the tie-line bias control characteristic for satisfactory control of an
interconnected power system.
77
Continued…..
Mismatch between actual and contracted demands will result in frequency deviation that
will drive AGC to re-dispatch GENCOs according to area control error participation
factors (apfs).
For a two area system, the simulation and results of conventional based system is
compared with the particle swarm optimization (PSO) techniques. The result shows that
the PSO based system requires less time to reach steady.
78
Future Scopes
The work done in the dissertation may be extended in the following directions:
The parameters in this work have been taken constant throughout the whole
operation. But there may be parameter uncertainty due to wear and tear, temperature
variation, imperfection of component, aging effect, environment changes etc. So
during controller design the variation of parameter may be taken into consideration.
The load frequency control (LFC) of power system can be designed by proportional
integral derivative (PID) controller via different optimization technique.
Analysis of AGC considering more non linearities like load frequency constant etc.
The particle swarm optimization may also be integrated with fuzzy system approach
to improve the results.
79
8). References
Vasu k, Chandar G. B, “Automatic Generation Control of Multi area Thermal Systems by Using
Fractional Order Controllers”, WCECS, October 19-21, 2016.
Masrur H, Ferdoush A, “Automatic Generation Control of Two Area Power System with
Optimized Gain Parameters”, IEEE-ICEEICT, May 21-23, 2015.
Morsali J and Zare K, “Appropriate GRC Modeling Method for Reheat Thermal Units to Obtain
Optimal Load Frequency Controller”, IPGC, June 10-11, 2014.
Kumar A and Sirdeep S, “Automatic Generation Control Issues in Power System Operation after
Deregulation Review”, IJARCSSE, Vol. 4, Issue 5, pp 705-710, May 2014.
Mohinder Pal and Palvee, “To Control Load Frequency by using Integral Controller”, IJIRSET”,
Vol. 3, Issue 5, pp 12502-12506, May 2014.
80
Continued…..
Naresh K and Jha A. N, “Effect of GRC on Load Frequency Control of Multi Area
Interconnected Thermal Systems”, JEEER, Vol. 5(3), pp 44-49, September 2013.
Reena K and R. Avtar, “Automatic Generation Control of Multi Area Power System Using PID
Controller”, IJETT, Vol. 4, Issue 5, pp 1976-1980, May 2013.
Subbaraj P and Manickavasagam K, “Automatic Generation Control of Multi Area Power System
with GRC using Computational Intelligence Techniques”, IJAPE, Vol. 2, No. 1, pp 27-38, April
2013.
Rohilla V and Parmar P. S, “Optimization of AGC Parameters in the Restructured Power System
Environment using GA”, IJESET, Vol. 3, Issue 2, pp 30-40, Oct. 2012.
Hasan N and Ibraheem, “Real Time Simulation of Automatic Generation Control for
Interconnected Power System”, IJEEI, Vol. 4, pp 40-51, March 2012.
81
Continued….
Lambert G and Esmin A. A. A, “Fitting Fuzzy Membership Functions using Hybrid Particle
Swarm Optimization”, IEEE International Conference on Fuzzy Systems, pp 2112-2119, July 16-
21, 2006.
Gross G and Lee J. W, “Analysis of Load Frequency Control Performance Assessment Criteria”,
IEEE Transactions on Power Systems”, Vol. 16, No. 3, pp 520-525, August 2001.
Donde V, Pai M. A and Hiskens IA, “Simulation and Optimization in an AGC System After
Deregulation”, IEEE transactions on Power Systems”, Vol. 16, No. 3, pp 481- 489, August 2001.
82
Continued….
Sharma A and Kothari M. L, “Automatic Generation Control of a Two Area Reheat Thermal
System Considering Tie Power Non-Linearity and Generation Rate Constraints” pp 399-403,
NPSC, 1998.
Cheng J.W.M and Galiana F.D, “Studies of Bilateral Contracts with respect to Steady State
Security in a Deregulated Environment”, IEEE transactions on Power Systems, Vol. 13, No. 3, pp
1021-1025, August 1997.
Christie R and Bose A , “ Load Frequency Control Issues in Power System Operations After
Deregulation”, IEEE transactions on Power Systems, Vol.11, No. 3, pp 1191 - 1200, August 1996.
Kennedy J and Eberhart R. C, “Particle Swarm Optimization”, Proceeding of The 1995 IEEE
International Conference on Neural Networks, Vol. 4, pp 1942- 1948, 1995.
83
84