TABLE 1 SUMMARY OF VOLTAGE DROP CALCULATION

CONDUCTOR Z(Ω) (PEC/Book) Z(Ω) (Actual)


FROM NODE TO NODE No. of
Size R(Ω) X(Ω) R(Ω)
Sets
Transformer Sec. Dist. Line 1 # 2/0 ACSR 0.162 Ω/kft 0.112 Ω/kft 0.015941
Sec. Dist. Line Service Point 1 #6 AWG 0.75 Ω/kft 0.139 Ω/kft 0.009840
Service Point PB 1 22mm2 THHN 0.31 Ω/305m 0.052 Ω/305m 0.013213
PB Circuit 1 1 2.0mm2 THHN 3.1 Ω/305m 0.058 Ω/305m 0.508197
PB Circuit 2 1 2.0mm2 THHN 3.1 Ω/305m 0.058 Ω/305m 0.406557
PB Circuit 3 1 3.5mm2 THHN 2.0 Ω/305m 0.054 Ω/305m 0.295082
PB Circuit 4 1 3.5mm2 THHN 2.0 Ω/305m 0.054 Ω/305m 0.360656
PB Circuit 5 1 5.5mm2 THHN 1.2 Ω/305m 0.050 Ω/305m 0.039344
PB Circuit 6 1 5.5mm2 THHN 1.2 Ω/305m 0.050 Ω/305m 0.059016
PB Circuit 7 1 3.5mm2 THHN 2.0 Ω/305m 0.054 Ω/305m 0.078689
Z(Ω) (Actual) VOLTAGE DROP
LENGTH CURRENT Voltage at
PERCENT REMARKS
X(Ω) (m) (A) Per Segement At circuit end receiving end

0.011021 30 45.32 1.7566 1.7566 228.24 0.76 Passed


0.001824 4 45.32 0.9071 2.6636 227.34 1.16 Passed
0.002216 13 45.32 1.2144 3.8780 226.12 1.69 Passed
0.009508 50 2.82 2.8667 6.7447 223.26 2.93 Passed
0.007607 40 1.95 1.5859 5.4639 224.54 2.38 Passed
0.007967 45 9.39 5.5437 9.4217 220.58 4.10 Passed
0.009738 55 7.82 5.6427 9.5207 220.48 4.14 Passed
0.001639 10 10 0.7876 4.6656 225.33 2.03 Passed
0.002459 15 8 0.9451 4.8231 225.18 2.10 Passed
0.002125 12 2.17 0.3416 4.2197 225.78 1.83 Passed
Fault Point : MDP

IMPEDANCE APEC : Fault Impedance :


R: 0.00032 R: 0.048819
X: 0.0011 X: 0.076891

Voltage Level : 230


Transformer :
R: 0.024858
X: 0.061399 Fault Current : 2635.05 Amps

Secondary
Distribution Line :
R: 0.015941
X: 0.011021

Service Drop:
R: 0.002585
X: 0.001496

Service Entrance:
R: 0.005115
X: 0.001875