Piping Material Specification 1SD1B01
Class 150, 316/316L Stainless Steel, 0.063" C.A.
Process
PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES
This Practice is subject to revision at any time by the responsible Function Team
and will be reviewed every 5 years. This Practice will be revised, reaffirmed, or
withdrawn. Information on whether this Practice has been revised may be found
at http://www.pipdocs.org.
48 T
42 J T
36 J H T
30 J H G T
24 J H G F T
20 P P G F K T
18 P P G F K K T
16 P P P F K K K T
14 P P P P K K K P T
BRANCH SIZE
12 P P P P K K K P P T
10 P P P P P K K P P P T
8 P P P P P P P P P P P T
6 P P P P P P P P P P P P T
4 P P P P P P P P P P P P P T
3 P P P P P P P P P P P P P P T
2 W W W W W W W W W W W W W W W T
1-1/2 W W W W W W W W W W W W W W W E T
1 W W W W W W W W W W W W W W W E E T
3/4 W W W W W W W W W W W W W W W E E E T
1/2 W W W W W W W W W W W W W W W E E E E T
48 42 36 30 24 20 18 16 14 12 10 8 6 4 3 2 1-1/2 1 3/4 1/2
HEADER SIZE
E Reducing Tee
F 0.300" (Note 59)
G 0.360" (Note 59)
H 0.420" (Note 59)
J 0.480" (Note 59)
K Full Encirclement Reinforcement (Length equals twice branch pip OD.)
P Branch Weld w/ Reinforcing Pad (Pad thickness equals run pipe thickness. Pad width equals 1/2 branch OD.)
T Tee
W BW Pipet (Note 81)
NOTES:
01 Where pipe schedule is shown under “SCH/RAT,” it is adequate for the full flange rating. Where “Calc” is shown, the pressure limit may be lower
than flange rating.
02 All buttwelded component thicknesses shall match pipe thickness.
07 These valves have no flanges, but are installed between line flanges with extra length bolts.
08 Full port valves shall be used when indicated on P&ID.
09 Pressure and temperature rating may be limited by certain components permitted by this specification. Refer to manufacturer’s recommended
pressure-temperature restrictions.
12 To be used only to match Class 300 rated flange connections at control valves and special equipment.
22 Use stub ends with lap joint backup flanges for temperature up to 500F (260C). For higher temperatures, use weld neck flanges.
26 To be used only when indicated on the P&ID.
59 Use branch weld with reinforcement pad when the minimum header wall thickness (specified or measured) at the branch location exceeds xxx, where
xxx equals the wall thickness value for the letter symbol shown in the legend. Use full encirclement reinforcement (length equals twice branch pipe
OD) when the wall is less than or equal to xxx.
62 Install in horizontal position with cover up or in vertical position with upward flow.
63 Install in horizontal position with hinge pin vertical or in vertical position with upward flow.
81 Integrally reinforced branch connections are permitted outside the sizes shown in the branch connection tables.
REFERENCES:
Process Industry Practices (PIP)
PIP PNF0200 - Vents, Drains, and Instrument Connection Details
PIP PNSMV023 - Stainless Steel Gate Valve Descriptions
PIP PNSMV024 - Stainless Steel Globe Valve Descriptions
PIP PNSMV025 - Stainless Steel Check Valve Descriptions
PIP PNSMV026 - Stainless Steel Ball Valve Descriptions
PIP PNSMV027 - Stainless Steel Butterfly Valve Descriptions
PIP PNSMV028 - Stainless Steel Plug Valve Descriptions