You are on page 1of 2

Detailed Design Drawing

Template for Power Cabinet Foundation

Project Name BB installation for Country 1 and 2


Client Contractor
Designer Unit
Reviewer Scale
Title Cover Sheet
Supervisor Size A4
Approver Date 5/10/2021 Dwg. NO 1 Ver. 1
B FRONT C25 reinforced concrete, 500mm
C10 plain concrete, 100mm

270
Ø110 mm PVC Pipe Well compacted soil,150mm
No. 2

170
170
Natural soil
Ø110 mm PVC Pipe
Gravel

A A
Finish Level(+0.30m)

B
ø10@150 Both Way
Bottom

CABINET FOUNDATION LAYOUT B-B SECTION


C25 reinforced concrete, 500mm
C10 plain concrete, 100mm
No. 1 Well compacted soil,150mm
Natural soil Ø110 mm PVC Pipe
FOUNDATION DETAIL
Gravel
L(mm) W(mm) H(mm)
+0.60m
1600 1000 500
Finish Level(+0.30m)

UNIT TOTAL
No SIZE SHAPE LENGTH Quantity LENGTH

ø10@150 Both Way 1 Ø10 400 1500 400 2300 7 16100


Bottom

2 Ø10 400 900 400 1700 11 18700


A-A SECTION
C25 reinforced concrete, 500mm
C10 plain concrete, 100mm Note:
No. 1 Masonry
1. All dimension are in Millimeters(mm), and all level in Meter(m), unless otherwise noted.
Natural soil
Gravel 2. Steel grade shall no less than S-400Mpa,
3. Ø110 mm embeded PVC pipe shall be buired for cable connection

Finish Level(+0.30m)
4. Compaction strength of the plain concrete shall no less then 10Mpa(C10),
for reinforced concrete the strength shall no less than 25Mpa(C25).
5. The thickness of concrete cover for reinforcement is 50mm for foundation,
6. Soil under the foundation shall be solid, otherwise well compacted soil shall be provided.
7. If the foundation on backfilling soil or the natural soil is soft, masonry under the foundation is necessary.
ø10@150 Both Way
Bottom 8. Duirng Excavation give attention for cable damage

A-A SECTION WITH MASONRY Project Name BB installation for Country 1 and 2
Client Contractor
Designer Unit mm
Reviewer(RAN) Scale
Title Cabinet Foundation Design for Beijing Dynamic
Reviewer(P&E) Size A4
Approver Date 5/10/2021 Dwg. NO 2 Ver.

You might also like