Profibus DP Bus parameters

Profibus DP

Bus parameters

Slide 1
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Contents
 Bit time (TBIT)
 Standard bus parameters
 Slot Time (TSL)
 Largest Station Delay Responder (min TSDR)
 Smallest Station Delay Responder (min TSDR)
 Quiet Time (TQUI)
 Setup Time (TSET)
 Target Rotation Time (TTR)
 Bus timing diagram
 Highest Station Address (HSA)
 Maximum Retries
 Siemens S7 Parameter Configuration
Slide 2
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Bit Time (TBIT)


 Bus timing parameters are given in bit time 1
values. T 
bit

Baudrate

 Using 1500 kbit/s baud rate the value of one “1”


bit time is:
1
T   6,67  10 s
7

TBIT
bit
bit

1500000bit / s

Slide 3
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Standard bus parameters


 Standard bus parameters have to be set at every
master (automatically or by the user).

PARAMETER DESCRIPTION VALUE RANGE DEFAULT


VALUE (S7)
TS This Station Address 0 … 126
Baud rate Baud rate 9,6 kbit/s … 12 Mbit/s 1,5 Mbit/s
TSL Slot Time 52 … (216-1) bit times 300 bit times
min TSDR Smallest Station Delay 20 … (216-1) bit times 11 bit times
CHANGING
Responder
DEFAULT
max TSDR Largest Station Delay Responder 20 … (216-1) bit times 150 bit times VALUES
TQUI Quiet Time 0 … (28-1) bit times 0 bit times INCREASES
TSET Setup Time 20 … (28-1) bit times 1 bit times STABILITY!
TTR Target Rotation Time 20 … (224-1) bit times
G GAP Update Factor 1 … 100 10
HSA Highest Station Address 2 … 126
Retry Limit Maximum Retry Limit 0…8 1
Slide 4
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Slot Time (Tsl)


 The maximum time a master waits for the complete reception of the
first octet (11 bits) of a response from a slave.
– If no response is received in the Slot Time the master will attempt a retry
or continue with other actions.

TSL
COMMAND

REPLY REPLY WITHIN


SLOT TIME

Slide 5
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Largest Station Delay Responder (max TSDR)


 The maximum time a slave could need to send the first bit of a
response back to the master.

COMMAND

max TSDR

REPLY

Slide 6
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Smallest Station Delay Responder (min TSDR)


 The time a slave has to wait before sending a response back to the
master (to calm the bus).
 Masters sends this parameter to the slaves  has to be set in the
master.
 Standard value 11 bit times

min TSDR

COMMAND

max TSDR

REPLY

Slide 7
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Quiet Time (TQUI)


 The time after which the bus electronics or software are set from
sending to receiving mode.
– During the sending mode reflections will not be received and disturb the
bus electronics.
 RULE: TQUI < min TSDR
 It is good to set the quiet time to 9 (standard value 0).

TQUI
min TSDR

Send COMMAND
mode
DURING TQUI
max TSDR
REFLECTIONS
ARE NOT
Receive RECEIVED
mode
Slide 8
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Setup Time (TSET)


 An extra time the master waits before sending a new message to a
new/another slave
 Setup time is usually used when many media transitions (repeaters,
FO couplers) are used and some delay is caused by these
transitions.
 In cranes the number of transitions is small and this parameters
does not need to be changed.
 Standard value: 1

SIGNAL DELAYED

RS 485

FIBER
OPTICS Slide 9
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Target Rotation Time (TTR)


 The maximum time provided for a token to pass round all bus
masters.
– Normally not the real rotation time  cannot be used to determine the
reaction time of the bus system.

TOKEN

Slide 10
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Bus Timing Diagram


TIME

REQUEST
TQUI
min TSDR

RESPONSE max TSDR


TSL

Slide 11
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Highest Station Address (HSA)


 In S7 configuration this parameter is called Highest PROFIBUS
Address.
 The highest bus address the existing master will look for a new
master (in multi-master networks).
– In Profibus networks with only one master this parameter should not be
changed.
 Standard value: 126
 A master with bus address higher that the HSA will not be able to
access the bus.
 In S7 configuration this parameter is called Highest PROFIBUS
Address.

Slide 12
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Maximum Retry Limit


 Maximum number of repeated messages that a master sends if no
response is received from a slave station.
 Standard value: 1
 It is good to set the Maximum retry limit to 3.

1) COMMAND

2) NO RESPONSE
3) 1.RETRY: COMMAND MAX RETRIES = 1
 FAULT
4) NO RESPONSE
Slide 13
Profibus DP Bus parameters.ppt
www.konecranes.com Ismo Ylenius Sep 18, 2022
Profibus DP Bus parameters

Siemens S7 Parameter Configuration

INCREASE
TO TQUI=9

INCREASE TO
Retry limit=3

Slide 14
Profibus DP Bus parameters.ppt