10DDD-1
10DDD
Type PRS
Programmable Resettable Sectionalizer
Single-Phase
NOTE: Hubbell has a policy of continuous product improvement. We reserve the right to change design and specifications without notice.
©
Copyright 2011 Hubbell Incorporated • 210 North Allen Street • Centralia, MO 65240-1395 USA
H U B B E LL ® CHANCE – CENTRALIA, MISSOURI
Power Systems Printed in USA MAY 2011
10DDD-2
RECLOSER RECLOSER
➔
SLOW CURVE SLOW CURVE
RECLOSER RECLOSER
MINIMUM MINIMUM
TIME
TIME
TRIP TRIP
TIME
TIME
RECLOSER RECLOSER
FAST FAST
CURVE CURVE
MAXIMUM
COORDINATION
POINT
COORDINATION
RANGE COORDINATION
RANGE
100 800 100
CURRENT
CURRENT CURRENT
CURRENT
Figure 1. Addition of the CRS eliminates the fuse curve and extends the coordination range.
Application
The Type PRS electronic
sectionalizer is best suited for
use in the following applications:
• Locations where fuse
coordination is difficult to
achieve
• Remote locations prone to Drop-open operation is the same for both types of the PRS
electronic sectionalizer: Standard (left) and Loadbreak
transient faults caused by fauna (right, with Arc Chute interrupter). See following pages for
specifications and ordering information.
and/or flora
H U B B E LL ® CHANCE – CENTRALIA, MISSOURI
Power Systems MAY 2011
10DDD-4
Number of Counts:
The sectionalizer should be set to operate in at least
one less count than the backup recloser. Example: a
4-shot recloser would require a maximum of a 3-count
sectionalizer downstream (Figure 2, line A).
In case of a 2-fast/2-slow reclose setting, a 2-count Where sectionalizers are used in series, the downstream
sectionalizer may be used to reduce the number of sectionalizer should have one less count than the
recloser operations (Figure 2, line B). upstream sectionalizer (Figure 3).
PRS
PRS
PRS
PRS
PRS
PRS
PRS
Figure 2. Typical distribution system with Type PRS Figure 3. Coordination of sectionalizers
two- and three-count electronic resettable sectionalizers. in series.
H U B B E LL ® CHANCE – CENTRALIA, MISSOURI
Power Systems MAY 2011
10DDD-6
Event Log
The programmable sectionalizer contains onboard memory
storage that will record the last 8 events the unit has
seen. Users will be able to download the event log via the
USB port and have access to the measured fault current,
number of counts, and deadline current.
Electronics
Hookstick
ring
USB port
Nickel plated
copper tube
Position 9:
Position 3: Cutout Terminal Connectors
Cutout Type P = Parallel-groove USB Cable
E = Small eyebolt Cat. No. PSC7400177
4 = Non-Loadbreak
L = Large eyebolt (must order separately)
5 = Loadbreak T = Electronic Module Only
CP7 4 00 1 PP L B
Position 6: Universal Cutout Tool
Ideal for use with Standard Electronic
Cutout Insulation Level Position 10: Sectionalizer to easily lift out, place, *open
Cutout Bracket and close. Inverted, secure method also
1 = 15kV, 110kV BIL
Z = No bracket fits 100 amp fuse holders of ABB, Chance,
2 = 27kV, 125kV BIL B = NEMA B bracket S&C cutouts.
(Non-loadbreak only) D = D bracket
15/27kV, 125kV BIL X = Extended bracket
(Loadbreak only) Blank = Electronic Module Only
H U B B E LL ® CHANCE – CENTRALIA, MISSOURI
Power Systems MAY 2011
10DDD-8
Electronics
Hookstick
ring
USB port
Nickel plated
copper tube
Position 9:
Position 3: Cutout Terminal Connectors
Cutout Type P = Parallel-groove USB Cable
E = Small eyebolt Cat. No. PSC7400177
4 = Non-Loadbreak
L = Large eyebolt (must order separately)
T = Electronic Module Only
5 = Loadbreak
C7 4 00 1 PP L B
Position 6: Position 10: Universal Cutout Tool
Ideal for use with Standard Electronic
Cutout Insulation Level Cutout Bracket Sectionalizer to easily lift out, place, *open
1 = 15kV, 110kV BIL Z = No bracket and close. Inverted, secure method also
B = NEMA B bracket fits 100 amp fuse holders of ABB, Chance,
2 = 27kV, 125kV BIL (Non-loadbreak only) S&C cutouts.
D = D bracket
15/27kV, 125kV BIL (Loadbreak only) X = Extended bracket
3 = 38kV, 150kV BIL (Non-loadbreak only) Blank = Electronic Module
6 = 38kV, 170kV BIL (Non-loadbreak only) Only