RS

Rotary Flow Meter


Instruction Manual
MNV10151 09.10

Contents
1. Outline ··································································· 2
2. Type symbols ························································ 2
3. Installation procedure············································ 3
4. Functions & operating method ······························ 5
5. Maintenance & inspection ····································· 7
6. Disassembling procedure ····································· 8
7. Disassembly drawing ············································ 9

Thank you for purchasing a rotary flow meter of our make this time. This instruction manual explains
various cautions necessary for operation of this flow meter. The user is kindly requested to read
through this manual so that this flow meter may be used correctly and in safety for a long period of time
to his satisfaction.
For any inquiry about this flow meter or order of spare parts, please let us know the type and the serial
No. indicated on the nameplate without fail.
1.Outline
Rotary flow meter is a rotary piston type flow meter for liquid of simple construction. It uses ceramic as standard material for the
bearing in the liquid end has adopted a special resin with excellent chemical resistance, wear resistance, heat resistance and impact
resistance for the rotor. In addition, it also adopted a large register easy to read for the counting unit.

2.Type symbols
RS

Flange shape
Volume Symbol

Flange standard
Material symbol

Type of generator
Counter symbol

and pulse unit

specifications
Supplementary
Nominal size
symbol
Rotary flow meter

●: Standard; ○: Manufacturable; ×: Non-manufacturable

025 040 050 080 100


Type Specification code Specifications
B0 A0 B0 A0 B0 A0 B0 A0
RS Rotary flow meter ● ● ● ● ● ● ● ●

A0 Pointer and direct-reading type ● ● ● ● ● ● ● ●


Counter
symbol Z8 Digital zero-reset and direct-reading type ● ● ● ● ● ● ● ●

I0 With direct-reading instantaneous flow indicator ○ ○ ○ ○ ○ ○ ○ ○

025 Nominal size: 25A ●

040 Nominal size: 40A ● ●


Nominal For the max. flow rate, refer to "Flow Rate
size symbol 050 Nominal size: 50A Range Table". ● ●

080 Nominal size: 80A ● ●

100 Nominal size: 100A ●

A0 Volume small ● ● ● ●
Volume symbol
B0 Volume large ● ● ● ●

FB Main body: FC, Measuring chamber: CAC, Rotor: PPS, GC, AC ● ● ● ● ● ● ● ●

FF Main body: FC, Measuring chamber: FC, Rotor: PPS, GC, AC ○ ○ ○ ○ ○ ○ ○ ○

F2 Main body: FC, Measuring chamber: SCS14, Rotor: PPS, GC, AC ○ ○ ○ ○ ○ ○ ○ ○

DB Main body: FCD, Measuring chamber: CAC, Rotor: PPS, GC, AC ○ ○ ○ ○ ○ ○ ○ ○


Material symbol
DD Main body: FCD, Measuring chamber: FCD, Rotor: PPS, GC, AC ○ ○ ○ ○ ○ ○ ○ ○

D2 Main body: FCD, Measuring chamber: SCS14, Rotor: PPS, GC, AC ○ ○ ○ ○ ○ ○ ○ ○

S2 Main body: SCS14, Measuring chamber: SCS14, Rotor: PPS, GC, AC ○ ○ ○ ○ ○ ○ ○ ○

FC: Cast iron casting, CAC: Bronze casting, SCS14: Stainless steel casting; PPS: Special resin; GC: Carbon; AC: Corrosion-resistant aluminum
12 Without pulse output ● ● ● ● ● ● ● ●

R4 Reed switch (contact) pulse 1L/p ○ ○ ○ ○ × × × ×

R5 Reed switch (contact) pulse 10L/p ○ ○ ○ ○ ○ ○ ○ ○

R6 Reed switch (contact) pulse 100L/p × × (○) (○) ○ ○ ○ ○

Type of generator and pulse unit R7 Reed switch (contact) pulse 1m3/p × × × × (○) (○) (○) (○)

M2 High frequency (no-contact) pulse 0.01L/p ○ ○ × × × × × ×


Note) The pulse units available for
output are restricted M3 High frequency (no-contact) pulse 0.1L/p ○ ○ ○ ○ × × × ×
depending on: M4 High frequency (no-contact) pulse 1L/p ○ ○ ○ ○ ○ ○ ○ ○
(1) pointer specifications, and
(2) type of generator. Refer M5 High frequency (no-contact) pulse 10L/p × × (○) (○) ○ ○ ○ ○
to "Output Pulse Unit Table". M6 High frequency (no-contact) pulse 100L/p × × × × (○) (○) (○) (○)

MD High frequency (no-contact) pulse DA conversion pulse ○ ○ ○ ○ ○ ○ ○ ○

K1 Photoelectric (no-contact) pulse 0.001L/p ○ ○ × × × × × ×

K2 Photoelectric (no-contact) pulse 0.01L/p × × ○ ○ × × × ×

K3 Photoelectric (no-contact) pulse 0.1L/p × × × × ○ ○ ○ ○

345 Non-explosion proof & without radiating fins ● ● ● ● ● ● ● ●

X00 Pressure-resistant explosion proof type ○ ○ ○ ○ ○ ○ ○ ○

X01 Pressure-resistant explosion proof type + Single-stage cooling fin ○ ○ ○ ○ ○ ○ ○ ○

X02 Pressure-resistant explosion proof type + Double-stage cooling fins ○ ○ ○ ○ ○ ○ ○ ○

Y00 Intrinsically safe explosion proof type ○ ○ ○ ○ ○ ○ ○ ○

Y01 Intrinsically safe explosion proof type + Single-stage cooling fin ○ ○ ○ ○ ○ ○ ○ ○


Supplementary specifications
Y02 Intrinsically safe explosion proof type + Double-stage cooling fins ○ ○ ○ ○ ○ ○ ○ ○

001 Single-stage cooling fin ○ ○ ○ ○ ○ ○ ○ ○

002 Double-stage cooling fins ○ ○ ○ ○ ○ ○ ○ ○

00J With jacket ○ ○ ○ ○ ○ ○ ○ ○

00W With jacket + Cooling fin ○ ○ ○ ○ ○ ○ ○ ○


Single-stage fin in the case where the liquid temperature exceeds 130°C, and double-stage fins in the case where the liquid temperature exceeds 180°C.
005 JIS 5K ○ ○ ○ ○ ○ ○ ○ ○

010 JIS 10K ● ● ● ● ● ● ● ●

Flange standard 020 JIS 20K ○ ○ ○ ○ ○ ○ ○ ○

AS1 ANSI class 150 ○ ○ ○ ○ ○ ○ ○ ○

AS3 ANSI class 300 ○ ○ ○ ○ ○ ○ ○ ○

F FF flange ● ○ ○ ○ ○ ○ ○ ○
Flange shape
R RF flange ○ ● ● ● ● ● ● ●
Note) No explosion proof type is available in the photoelectric pulse generator type.

-2-
3. Installation procedure
1.Precautions on place of installation
Select a place satisfying the following conditions for installing this flow meter:
(1)Place subject to little vibrations.
(2)Place protected against rain and dew.
(3)Place with little dust.
(4)Place with little moisture.
(5)Place with little corrosive gas.
(6)Place not subject to any violent fluid pulsations.
(7)Place with little electromagnetic noise.
(8)Place easy to inspect.
(9)Place protected against direct sunshine.
(10)Batch pumps such as plunger type, diaphragm type, etc. are liable to produce pulsations in the fluid,
eventually leading to damage to rotor or instrumental error. Install an air chamber or accumulator to
eliminate pulsations completely.

2.Precautions to take before installation


Flushing: Before installing the flow meter, completely remove dust, welding refuse, etc. produced with piping
work.

3.Precautions to take at start of operation


At the start of operation, the air in the piping is discharged at high speed. Open the valve slowly to avoid
damage due to high-speed operation to the rotor inside.

4.Piping procedure
(1)Install the piping in a way not to apply any piping pressure to the flow meter.
(2)Install on the outlet side of the pump.
(3)Be sure to provide a strainer for this flow meter. The strainer shall be installed on the upstream side of the
flow meter as close to the flow meter as possible.
Clean the strainer element (net) regularly. If there is a lot of dust in the fluid, provide a supplementary
strainer of coarse mesh on the upstream side.
(4)Fit the arrow mark given on the lateral face of the flow meter to the direction of inflow of the fluid.
(5)When using the flow meter at a tank head, give a head larger than the pressure loss of the flow meter.
(6)When using a liquid packing, etc., take care to prevent the liquid packing, etc. from protruding into the pipe.
(7)Install in the specified posture.
(8)Do not wind any insulating material around the cooling fin of the flow meter equipped with cooling fins.
(9)Change of direction of dial plate
(a)loosen the dial case tightening nut or bolt.
(b)Turn the dial case by a desired angle (by 90°each time).
(c)Tighten the nut or bolt.

Dial case

Nut or Bolt
Size :M8

-3-
5.Wiring procedure
A flow meter with pulse generator shall be connected according to the instructions given on the following table:

Type of generator Reed switch High-frequency pulse Photoelectric pulse

White Brown
Red Black Black Blue
Terminal
layout
drawing
Receiver SIG +V 0V SIG +12V 0V

6.Example of installation

Vertical piping
Horizontal piping Horizontal piping
(Horizontal installation) (Vertical installation)

The mark ※ indicates a space necessary for disassembling and inspection. Install the piping in a way to secure
a dimension no small than the figures indicated on the table below.

unit:mm
025B0 040B0 050B0 080B0
Type・Size
040A0 050A0 080A0 100A0
※Dimensions 192 246 312 444

-4-
4.Functions & operating method
1. Indicating function

RSA0 type・・・・・The pointer turns clockwise according to the measured flow rate, to count the
(Pointer type) integrated value.

Symbol of Dial plate Total counter


nominal Symbol of
capacity Minimum One Number of Minimum Maximum
size unit revolution figures unit capacity
025 B0 999,999
0.1L 10L 6 10L ×10L
A0
040
B0 999,999
0.1L 10L 6 10L
A0 ×10L
050
B0 999,999
1L 100L 6 100L
A0 ×100L
080
B0 999,999
1L 100L 6 100L
100 A0 ×100L

RSZ8 type・・・ The indication of the zero-reset counter and the total counter increase according to the
(Digital zero-reset type) measured flow rate.
・To reset the zero-reset counter to “0000”, turn the knob on the right side of the
counter anti-clockwize.
Note) The counter turns only in the direction of larger figures. Take care to avoid
any excessive turning.
Counter equipped with resetting
Symbol of Continuous total counter
Symbol of device
nominal Number of Minimum Maximum Number of Minimum Maximum
capacity
size figures unit capacity figures unit capacity
025 B0
4 0.1L 9,999L 7 1L 9,999,999L
A0
040
B0
4 0.1L 9,999L 7 1L 9,999,999L
A0
050
B0 9,999,999
4 1L 9,999×10L 7 10L
A0 ×10L
080
B0 9,999,999
4 1L 9,999×10L 7 10L
100 A0 ×10L

RSI0 type・・・ The measured instant flow rate can be read from the indication of the pointer.
(Instant flow rate indicator type) The indication of the total counter increase according to the measured flow rate.
Symbol of Full scale and division Total counter
nominal Symbol of
capacity Standard full Unit of Minimum Maximum
size scale division unit capacity
025 B0
5,000L/h 200L/h 0.02L 9,999,999×0.1L
A0
040
B0
12,000L/h 500L/h 0.2L 9,999,999L
A0
050
B0
24,000L/h 1,000L/h 0.2L 9,999,999L
A0
080
B0
50,000L/h 2,000L/h 2L 9,999,999×10L
100 A0
Note)230°for full-scale angle.

-5-
2.Output functions
●Reed switch pulse generator(Symbol:R)
Outputs no-voltage contact signals proportional to the flow rate.

Contact Max. generated


Variation Output signal Max. voltage Max. flow rate Switch capacity
resistance pulse
No-voltage
DRR-5 AC・DC200V 1A 25W 0.06Ω 5P/sec
contact pulse
No-voltage
MR506 DC50V 250mA 15w 0.1Ω 5P/sec
contact pulse

Note) In case of shortage of contact capacity, use a relay box (of optional specifications).

●High-frequency pulse generator(Symbol:M)


●Pulse generator for DA conversion(Symbol:MD)
Outputs voltage no-contact signals proportional to the flow rate.

Output signal: Voltage no-contact pulse


Approximate rectangular wave Output circuit
+V
H: 17V or over (10kΩ load)
(+ V = DC24V) 2.21kΩ
H: 8V or over (10kΩ load)
(+ V = DC12V) 215Ω
SIG
L: 0.5V or under (10kΩ load)

Output impedance: Approx. 2.4kΩ


0V

Max. generated pulse: 140P/sec


Power source: DC6~26.4V
Current consumption: 23mA or under (+V=DC24V)
17mA or under (+V=DC12V)

●Photoelectric type pulse generator output(Symbol:K)


Outputs voltage no-contact signals proportional to the flow rate.

Output signal: 12V no-contact pulse


Approximate rectangular wave
Output circuit
H: Approx. 12V (At no-load) +12V

2.2kΩ
L: 0.5V or under (At no-load)
SIG

Output resistance: Approx. 2.2kΩ


0V

Maximum generated pulse: 1,400P/sec


Power source: DC12V 50mA

-6-
5.Maintenance & inspection

Symptom Cause Remedy


No rise of inflow side pressure.
Check the piping system.
Opened bypass valve.
Clean the strainer element.
Clogged strainer.
Disassemble and inspect the measuring unit
No rotation of rotor due to dust, scale, etc. in
according to the disassembling procedure of
the measuring unit.
flow meter.
The liquid passes but Disengagement of gears in the counter unit.
neither pointer nor Loose set screw of gears in the counter unit.
totalizing counter move. Galling of shaft and bearing in the counter
Clean, lubricate or replace parts.
unit.
Breaking of transmitting mechanism parts in
the counter unit.
Excessive liquid temperature, pressure, etc. Use within the range indicated on the
beyond allowable range. nameplate.

Mixing of air in the liquid. Eliminate air by installing an air separator, etc.
Excessively large
totalized volume of flow
Take protective measures against penetration
meter against actual Empty piping before and after the flow meter.
of air into the piping.
liquid volume.
(Accuracy on plus side) High viscosity of operating liquid
Correct instrumental error by replacing the
(temperature, viscosity, etc. different from
correction gears.
specifications).

Small flow rate. Use in the flow rate range of specifications.

Excessively small
Low viscosity of operating liquid (temperature, Correct instrumental error by replacing the
totalized volume of flow
viscosity, etc. different from specifications). correction gears.
meter against actual
liquid volume. Wear or breaking of measuring unit parts. Disassemble and inspect the measuring unit
(Accuracy on minus Adhesion of dust, scale, etc. to the measuring according to the disassembling procedure of
side) unit. flow meter. Clean or replace parts.

Heavy rotation of counter unit. Clean, lubricate or replace parts.

Disagreement between Defective engagement or damage of


totalized value of flow Clean, lubricate or replace parts.
transmission gears and clutch.
rate in the counter unit
and value of output Defective wire connection with flow rate
Repair defective parts of the wiring.
pulse in the generator indicator, converter, etc.
unit.
Unusual waveform of Defective pulse generator. Replace pulse generator.
output signals.

Flow meter needs periodic maintenance and inspection to maintain measuring accuracy. Interval of inspection is basically
every year but this interval is changed depending on the frequency of use and the working environment.
It is recommended to make inspection of flow meter at our factory at least every three years.

-7-
6.Disassembling procedure

Body bolts Measuring

chamber cover
Lower magnet
Body

Measuring

chamber

Remove all body bolts。 Lift the lower magnet vertically and Remove the measuring chamber cover
Tool、Size separate the measuring chamber by lifting it vertically.
025B0、040A0 : Hex-head spanner(10mm)
from the main body while taking
040B0、050A0 : Spanner(24mm)
050B0、080A0 : Spanner(24mm) care not to damage the lower
080B0、100A0 : Spanner(30mm)
magnet.

Measuring chamber Rotor shaft


Rotor
Rotor
Eccentric
Partition
bearing
wall

Hole

Check if the rotor turns smoothly. Clean well the rotor and the Set the rotor shaft correctly in
measuring chamber sufficiently the hole for rotor shaft in the
with gasoline or water, etc. If eccentric bearing.
there is a contact between the
rotor and the partition wall when
you replaced the rotor, grind the
contact part gently with a fine
file.

Ditch

Clutch

Partition

Rotor Entrance
wall

shaft

Put the measuring chamber cover Assemble the measuring chamber by


correctly by fitting the rotor fitting the inlet of the measuring

shaft to the position of hole in chamber to the inlet of the main

the clutch and the partition wall body.

to the groove in the measuring


chamber cover.

-8-
7.Disassembly drawing
Counter unit(Type A0) 23A Counter unit(Type Z8) 23B
(including (including
20A,21A,22A) 20B,22B)

22A 22B

21A

20A 20B

※Note1 ※Note1
25
25

Counter unit(Type I0) Note1


When counter units is type
23C
(including A0 , Z8 and direct totalizing
20C,21B,22C) type (without pulse generator /
cooling fin), installation of dial
22C
case is made by fastening nut
into stud bolts fixed to dial
case as shown below.
21B

20C

25
(Intermediate gear)

Note) Set screws are not included.


Please instruct separately if necessary.
Generator unit and cooling fins or Measuring unit
-9-
Generator unit
From counter unit
(Non explosion-proof type and
Equipped with generator
intrinsic safety type)
Equipped with
pressure-resistant 17
explosion-proof
generator 16 Shape of pulse unit
25 is slightly differed
19 according to kind of
(including 16~18) pulse (R,M,K).
Pulse unit
18
(Pressure-resistant
explosionproof type )

Without
generator

31 (including 27,30)

27 (including 26)

25 26

Shape of pulse unit


is slightly differed
30 (including 28,29) according to kind of
pulse (R,M).
28

Equipped with cooling fins


29

Without Cooling fins


32
cooling fins

25

※ In case of two stage cooling fins


construction, same cooling fin is added.

Note) Set screws are not included.


To measuring unit Please instruct separately if necessary.
-10-
Note) Set screws are not included.
From Measuring unit or Generator unit and cooling fins Please instruct separately if necessary.

15
10(including 7~10)

9 (Split pin included.)


14 (including 13)
13 (including 12)
12
Symbol of nominal size 8 (including bushing,
and capacity suppression board)
025B0 , 040A0
Symbol of nominal
size and capacity
( Equipped with over 040B0
cooling fins)
7

5
24
4

11 1

-11-
№ Parts name Q’ty № Parts name Q’ty № Parts name Q’ty
1 Measuring chamber set 1 14 Main body set (including 13) 1 22C Glass set – Type I0 1
Counter unit set – Type A0
2 Measuring chamber 1 15 Dial flange set 1 23A 1
(including 20A,21A,22A)
Non explosion-proof Counter unit set – Type Z8
3 Center axis 1 16 1 23B 1
reduction gear unit (including 20B,22B)
Non explosion-proof Counter unit set – Type I0
4 Partition wall 1 17 1 23C 1
generator case set (including 20C,21C,22C)
5 Eccentric bearing 1 18 Non explosion-proof pulse unit 1 24 Bolts for main body 8(6)
Non explosion-proof generator
6 Rotor set 1 19 1 25 Bolts for dial unit 4
set(including 16~18)
Explosion-proof reduction gear
7 Clutch 1 20A Dial set - Type A0 1 26 1
unit
Measuring chamber cover
Explosion-proof reduction gear
8 (including bushing , 1 20B Dial set – Type Z8 1 27 1
set (including 26)
suppression board)
Lower magnet set
9 1 20C Dial set – Type I0 1 28 Explosion-proof pulse unit 1
(including split pin)
Measuring chamber cover set Scale plate (including pointer) Pressure-resistant packing
10 1 21A 1 29 1
(including 7~9) Type A0 type metal fixture
Explosion-proof pulse set
11 Packing for body 1 21B Scale plate – Type I0 1 30 1
(including 28,29)
Explosion-proof generator set
12 Upper magnet set 1 22A Glass set – Type A0 1 31 1
(including 27,30)
Pressure cover set
13 1 22B Glass set – Type Z8 1 32 Cooling fins set 1
(including 12)

-12-
NITTO SEIKO CO., LTD.
Control System Division
30 Nobu-cho, Ayabe, Kyoto
623-0041 Japan
Phone: (0773) 42-3151
Fax: (0773) 42-3155
URL: http://www.nittoseiko.co.jp/