The document summarizes the characteristics of current sensors for VIP400 and VIP410 meters. It provides parameters such as rated primary current, rated secondary current, transformation ratios, knee point voltages, magnetizing currents, winding resistances, and power consumption for the metering and power supply windings of the CUa and CUb sensors. The metering winding provides signals for metering and protection functions and has an accuracy limit factor of 5P50 for CUa and 5P30 for CUb according to class P standards.
The document summarizes the characteristics of current sensors for VIP400 and VIP410 meters. It provides parameters such as rated primary current, rated secondary current, transformation ratios, knee point voltages, magnetizing currents, winding resistances, and power consumption for the metering and power supply windings of the CUa and CUb sensors. The metering winding provides signals for metering and protection functions and has an accuracy limit factor of 5P50 for CUa and 5P30 for CUb according to class P standards.
The document summarizes the characteristics of current sensors for VIP400 and VIP410 meters. It provides parameters such as rated primary current, rated secondary current, transformation ratios, knee point voltages, magnetizing currents, winding resistances, and power consumption for the metering and power supply windings of the CUa and CUb sensors. The metering winding provides signals for metering and protection functions and has an accuracy limit factor of 5P50 for CUa and 5P30 for CUb according to class P standards.
The metering winding is a magnetic core winding hard-wired onto a built-in resistor (LPCT type) that provides the signals needed by the VIP metering and protection functions. Characterized in accordance with class P, the accuracy limit factor is equivalent to 5P50 for the CUa sensor and 5P30 for the CUb sensor.
Parameters CUa CUb
Ipn rated primary current 200 A 630 A Isn rated secondary current 0.0833 A 0.15 A Rated transformation ratio 1/2400 1/4200 Rated kneepoint voltage Ek (50 Hz) 72 V 200 V Maximum magnetizing current Ie to Ek 4 mA 2 mA
Maximum resistance of the secondary winding at 75 C o 18.8 Ohm 50.4 Ohm
Metering resistance integrated in the sensor 1.8 Ohm 1 Ohm
Voltage at the terminal of the metering resistance integrated 150 mV/ln 150 mV/ln in the sensor (Usr rated secondary voltage)
The power supply winding is a magnetic core winding that provides the VIP power supply.
Parameters CUa CUb
Ipn rated primary current 200 A 630 A Isn rated secondary current 0.377 A 0.485 A Rated transformation ratio 1/530 1/1300 Rated kneepoint voltage Ek (50 Hz) 32.9 V 20.1 V Maximum magnetizing current Ie to Ek 13.5 mA 8 mA
Maximum resistance of the secondary winding at 75 C o 12.4 Ohm 9.2 Ohm
Consumption at the rated load current 75 mW 150 mW