Professional Documents
Culture Documents
SHGC
Where,
C = thermal coefficient of roof
U = The U-factor for the envelope component
A = The area of a specific envelope component
FACTORS AFFECTING EPF:
Material
Orientation
Surface Area
WINDOW WALL RATIO
WINDOW WALL RATIO: It is the measure of the percentage area determined by dividing the
building's total glazed area by its exterior envelope wall area.
EFFECTIVE APERTURE: A measure of the amount of daylight that enters a space through
horizontal fenestration
Given by formula, Visible Light Transmittance x window-to-wall Ratio. (EA = VLT x WWR)
VLT
VISUAL LIGHT TRANSMISSION OR VLT, IS THE AMOUNT OF VISIBLE LIGHT THAT PASSES
THROUGH A GLASS
FOR GLASS WITH A VLT OF 12%, IT ALLOWS 12% OF LIGHT TO SHINE THROUGH AND
BLOCKS 88% OF IT.
PROJECTION FACTOR
Equivalent SHGC: SHGC for a fenestration with a permanent external shading projection
Shading Equivalent Factor (SEF) It is the coefficient for calculating effective SHGC of
fenestrations shaded by overhangs or side fins.
PROJECTION FACTOR, SIDE FIN: It is the ratio of the horizontal depth of the external
shading projection to the distance from the window jamb to the farthest point of the external
shading projection,
DAYLIGHT FACTOR
Daylight factor (DF) - It is the ratio of the light level inside a structure to the light level outside
the structure
DF = (Ei / Eo) x 100%
LLF (Light Loss Factor) is the depreciating light output at certain point in time in the future
compared to initial light output
Lighting Power Density (LPD): It is the maximum lighting power per unit area of a space
Given by watts of lighting per square foot of room floor area
ILLUMINATION
Illumination can be calculated as
I = Ll Cu LLF / Al
where
I = illumination (lux, lumen/m2)
Ll = luminance per lamp (lumen referred as amount of light emitted per second)
Cu = coefficient of utilization
LLF = light loss factor
Al = total area (m2)
Example - Illumination
10 CFL lights of 40 W (1500 lumens per lamp) are used in an area of 50 m2. With Cu =
0.6 and LLF = 0.8 illumination can be calculated as
I = 10 (1500 lumens) (0.6) (0.8) / (50 m2)
I = 144 lux
DEFINITIONS
Energy Efficiency Ratio (EER) It is the ratio of net cooling capacity of an equipment to the
total electrical input in watts under designated conditions.
Example, a cooling capacity of air condition system of 12000 Btu (1 ton unit) requires 800
watts of electrical input, then EER is 15
Cooling capacity (HVAC) - It is the measure of a cooling system's ability to remove heat.
DEFINITIONS
Coefficient of Performance COP (cooling): It is the ratio of the rate of heat removal to the rate
of energy input.
Coefficient of Performance (COP) heating: It is the ratio of the rate of heat delivered to the
rate of energy input.
Calculated by dividing sensible cooling capacity in watt to total energy input.
It is considered as the simplest and most relevant indicator for qualifying a building
as energy efficient or not.