Professional Documents
Culture Documents
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○ ACDX-B / AUDX-B
Screw Compressor
Air Cooled Packages
48 Through 208 Tons
Installation, Operation & Maintenance Instructions
○ ○○ ○○ ○○ ○○ ○○ ○○ ○○ ○○ ○○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Form No. 6122B
TABLE OF CONTENTS ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Page
1.0 General Information
1.1 Introduction ................................................................................................................................ 5
1.2 Physical Specifications - English I.P. Units ............................................................................. 6 - 8
1.3 Physical Specifications - Metric S. I. Units ........................................................................... 9 - 11
2.0 Installation
2.1 General Installation Instructions .............................................................................................. 12
2.2 Inspection ................................................................................................................................. 12
2.3 Handling, Storage and Rigging ................................................................................................ 12
2.3.1 General Handling Instructions .......................................................................................................... 12
2.3.2 Storage ............................................................................................................................................
12
2.3.3 Rigging and Moving .........................................................................................................................
12
2.3.3.1 Rigging Instruction Drawing ........................................................................................... 12
2.4 Space and Clearance Requirements ......................................................................................... 13
2.4.1 General Space and Clearance Requirements .................................................................................... 13
2.4.2 Service Clearance Requirements ....................................................................................................... 13
2.4.3 Location and Installation Clearance ................................................................................................. 14
2.4.4 ACDX-B and AUDX-B Dimensional Data ....................................................................................... 15-24
2.5 Point Loading and Vibration Isolation ..................................................................................... 25
2.5.1 Foundation and Mounting Structure ................................................................................................ 25
2.5.2 Vibration Isolation ACDX-B / AUDX-B ................................................................................................ 25
2.5.3 ACDX-B Unit Wts. and Point Loading I.P. English Units ..................................................................... 26
2.5.4 ACDX-B Unit Wts. and Point Loading S.I. Metric Units ...................................................................... 27
2.5.5 AUDX-B Unit Wts. and Point Loading I.P. English Units ..................................................................... 28
2.5.6 AUDX-B Unit Wts. and Point Loading S.I. Metric Units ..................................................................... 29
2.6 Vibration Isolation Requirements ............................................................................................ 30
2.6.1 ACDX-B RIS Vibration Isolator - Alum. Fin Condenser ....................................................................... 30
2.6.2 ACDX-B Spring Vibration Isolator - Alum. Fin Condenser .................................................................. 31
2.6.3 ACDX-B RIS Vibration Isolator - Copper Fin Condenser ..................................................................... 32
2.6.4 ACDX-B Spring Vibration Isolator - Copper Fin Condenser ............................................................... 33
2.6.5 AUDX-B RIS Vibration Isolator - Alum. Fin Condenser ....................................................................... 34
2.6.6 AUDX-B Spring Vibration Isolator - Alum. Fin Condenser ................................................................. 35
2.6.7 AUDX-B RIS Vibration Isolator - Copper Fin Condenser ..................................................................... 36
2.6.8 AUDX-B Spring Vibration Isolator - Copper Fin Condenser ............................................................... 37
2.7 Piping Connections: ACDX-B / AUDX-B .................................................................................... 38
2.7.1 ACDX-B Chilled Water Piping ............................................................................................................ 38
2.7A Typical Chilled Water Piping -Three Way Bypass .............................................................. 40
2.7B Typical Chilled Water Piping -Two Way Bypass ................................................................ 40
2.7.2 Multiple Chiller Water Piping ........................................................................................................... 38
2.7.2.1 Parallel Multiple Chiller Water Piping .............................................................................. 38
2.7C Typical Parallel Chiller Chilled Water Piping ..................................................................... 40
2.7.2.2 Series Multiple Chiller Water Piping ................................................................................ 39
2.7D Typical Series Chiller Chilled Water Piping ....................................................................... 40
2.7.3 ACDX-B Chilled Water Quality .......................................................................................................... 39
2.7.4 AUDX-B Condensing Unit Connections ............................................................................................. 39
2.7.4.1 General Condensing Unit Connections Applications ....................................................... 39
2.7E Condensing Unit Typical Hot Gas Bypass Piping .............................................................. 40
2.8 Electrical Connections: ACDX-B / AUDX-B ................................................................................ 41
2.8.1 Field Control Wiring ......................................................................................................................... 41
2.8.2 General Electrical Notes ................................................................................................................... 41
2.8.3 Electrical Data: Units and Compressors ...................................................................................... 42-46
2.8.4 Compressor Crankcase & Cooler Heaters .......................................................................................... 47
2.8.5 Field Connection Terminal Blocks and Fan Data ............................................................................... 48
2.9 Refrigerant Charging Procedure .............................................................................................. 49
2.9.1 General Refrigerant Charging Procedures ........................................................................................ 49
2.9A Refrigerant Line Capacities .............................................................................................................. 49
2.9.2 AUDX-B Refrigerant Charge Calculation ........................................................................................... 49
2.9.3 AUDX-B Refrigerant Charging Procedure ......................................................................................... 49
2
TABLE OF CONTENTS ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Page
3
TABLE OF CONTENTS ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Page
4.4 ACDX-B / AUDX-B Package Control ........................................................................................... 66
4.4.1 Capacity Control for Screw Compressors .........................................................................................
66
4.4.1.1 Automatic Control ........................................................................................................
66
4.4.1.2 Manual Control .............................................................................................................
67
4.4.2 Staging of Compressors ..................................................................................................................
67
4.4.3 Compressor Current Limiting ..........................................................................................................
67
4.4.4 Ramp Control ..................................................................................................................................
67
4.4.5 Manual Lead/Lag Selection ..............................................................................................................
68
4.4.6 Compressor Start Delay ...................................................................................................................
68
4.4.7 Power Loss Reset ............................................................................................................................
68
4.4.8 Anti-Recycle Timing .........................................................................................................................
68
4.4.9 Low Pressure Safety ........................................................................................................................
68
4.4.10 High Pressure Safety ........................................................................................................................
68
4.4.11 Freeze Safety ...................................................................................................................................
68
4.4.12 Alarm Output ..................................................................................................................................
68
4.4.13 Ran Control .....................................................................................................................................
68
4.4.14 Chilled Water Reset (Optional) and Customer Control Interlock ......................................................
68
4.4.15 Hot Gas Bypass Control (Optional) ..................................................................................................
68
4.4.16 Compressor Power Control (No-Stop Alarm) and Unit Schedule ......................................................
68
4.4.17 Sensor Alarm Shutdown ..................................................................................................................
69
4.4.18 External Shutdown Indication (No-Run Alarm) ................................................................................
69
4.4.19 Fast Unload Solenoid Control ..........................................................................................................
69
4.4.20 High Motor Temperature Safety ......................................................................................................
69
4.4.21 Low Chiller Flow Alarm ...................................................................................................................
69
4.4.22 High Discharge Pressure Unload ......................................................................................................
69
4.4.23 Low Suction Pressure ......................................................................................................................
69
4.4.24 Low Oil Level Alarm .........................................................................................................................
69
4.5 Typical Power Wiring (Single Compressor Model) ................................................................... 70
4.6 Typical Control Wiring (Single Compressor Model) ............................................................ 71, 72
4.7 Typical Power Wiring (Three Compressor Model) ............................................................... 73, 74
4.8 Typical Control Wiring (Three Compressor Model) ............................................................. 75, 78
5.0 Maintenance
5.1 General Maintenance ............................................................................................................... 79
5.2 Periodic Inspection ................................................................................................................... 79
5.3 Monthly Inspection .................................................................................................................. 79
5.4 Vessel Maintenance .................................................................................................................. 79
5.4.1
General Unit Efficiency and Performance ........................................................................................ 79
5.4.2
Cooler Cleaning ............................................................................................................................... 79
5.5 Air Cooled Condenser Cleaning ............................................................................................... 79
5.6 Electrical Malfunction ............................................................................................................... 79
5.7 Troubleshooting ....................................................................................................................... 80
5.8 Start-Up and Maintenance Log Sheet ................................................................................. 81-82
5.9 Start-Up Check List ................................................................................................................... 83
5.10 Temperature and Pressure Table ............................................................................................... 84
5.11 Notes ....................................................................................................................................................... 85
4
1.0 GENERAL INFORMATION ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
1.1 Introduction
This manual is designed to provide all necessary To assure satisfactory operation and to avoid damage
information for installation, operation and to the unit, the installation should be made by a
maintenance of the latest generation of Dunham-Bush qualified refrigeration mechanic. It is assumed that
screw compressor package units. These packages the reader of his manual and those who install, operate
include air cooled water chiller machines, and air cooled and maintain this equipment have a basic
condensing units. understanding of the principles of air conditioning,
refrigeration and electrical controls. These instructions
To use this manual effectively, you must first determine
are general in nature and are for standard catalog units.
your unit model number from the unit nameplate.
Non-standard units may vary in some respects from
Since this manual is comprehensive for a wide variety
these instructions.
of units, you should be careful to use only those
sections which apply to your model. Note that each Your Dunham-Bush package has been manufactured
section is clearly marked as to the applicable models. under a careful quality control system and has been
factory run tested as a final verification of reliability. If
The AUDX-B is a condensing unit without a mounted
it is installed, operated and maintained with care and
evaporator. It is designed for remote DX water chiller
attention to these instructions, it will give many years
or air cooling coil applications. Due to the evaporator
of satisfactory service.
being remotely mounted, the AUDX-B machine is given
a factory electrical test only.
Air Cooled Packaged Chiller Models and Condensing Units for Use with
DX Coil Banks or Remote Coolers for Split-System Chillers
WARNING
NOTES: (1) Low Ambient option utilizes two (2) variable speed fan motors in place of standard motors.
(2) Extra Quiet Models utilize 855 RPM fan motors rated at 1.0 HP and .61 kW.
(3) Min. Starting/Operating Ambient assumes a 5 MPH max. wind and a 50% min. chiller load.
(4) Same as note (3) except the use of an Electronic Expansion Valve is required.
(5) Not available for compact models in this size. (Consult Factory)
6 (6) EXD16112J11DVRO used on compact unit; water volume = 43 gallons, min. flow = 175 GPM, max flow = 519 GPM
1.0 GENERAL INFORMATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
NOTES: (1) Low Ambient option utilizes two (2) variable speed fan motors in place of standard motors.
(2) Extra Quiet Models utilize 855 RPM fan motors rated at 1.0 HP and .61 kW.
(3) Min. Starting/Operating Ambient assumes a 5 MPH max. wind and a 50% min. chiller load.
(4) Same as note (3) except the use of an Electronic Expansion Valve is required.
7
1.0 GENERAL INFORMATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
NOTES: (1) Low Ambient option utilizes two (2) variable speed fan motors in place of standard motors.
(2) Extra Quiet Models utilize 855 RPM fan motors rated at 1.0 HP and .61 kW.
(3) Min. Starting/Operating Ambient assumes a 5 MPH max. wind and a 50% min. chiller load.
(4) Same as note (3) except the use of an Electronic Expansion Valve is required.
8
1.0 GENERAL INFORMATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
NOTES: (1) Low Ambient option utilizes two (2) variable speed fan motors in place of standard motors.
(2) Extra Quiet Models utilize 855 RPM fan motors rated at .746 kWo and .61 kWi.
(3) Min. Starting/Operating Ambient assumes a 5 MPH max. wind and a 50% min. chiller load.
(4) Same as note (3) except the use of an Electronic Expansion Valve is required.
(5) Not available for compact models in this size. (Consult Factory)
(6) EXD16112J11DVRO used on compact unit; water volume = 162.8 Liters, min. flow = 11.0 Liters/Sec.,
max flow = 32.7 Liters/Sec.
9
1.0 GENERAL INFORMATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
NOTES: (1) Low Ambient option utilizes two (2) variable speed fan motors in place of standard motors.
(2) Extra Quiet Models utilize 855 RPM fan motors rated at .746 kWo and .61 kWi.
(3) Min. Starting/Operating Ambient assumes a 5 MPH max. wind and a 50% min. chiller load.
(4) Same as note (3) except the use of an Electronic Expansion Valve is required.
10
1.0 GENERAL INFORMATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
NOTES: (1) Low Ambient option utilizes two (2) variable speed fan motors in place of standard motors.
(2) Extra Quiet Models utilize 855 RPM fan motors rated at .746 kWo and .61 kWi.
(3) Min. Starting/Operating Ambient assumes a 5 MPH max. wind and a 50% min. chiller load.
(4) Same as note (3) except the use of an Electronic Expansion Valve is required.
11
2.0 INSTALLATION ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Figure 2.3.3.1
SPREADER
BAR
MUST
CONTROL BOX CLEAR TOP
OF FAN
GRILLES
12
2.0 INSTALLATION ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ALLOW 60"
48.00 AIR FLOW [1524] FOR
[1219] SIDE & BOTTOM SERVICE
24.00
[610] ACCESS
88.00
[2235]
48.00
AIR FLOW
[1219]
SIDE & BOTTOM TOP VIEW
13
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
14
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ALLOW 60"
48.00 AIR FLOW [1524] FOR
[1219] SIDE & BOTTOM SERVICE
ACCESS
24.00
[610]
88.00
[2235]
48.00
AIR FLOW
[1219]
SIDE & BOTTOM TOP VIEW
POWER ENTRY
SEE NOTE 4
5.13
[130] 71.50
[1816]
64.50
[1638]
WATER OUT
(SEE TABLE) LIFTING & MOUNTING
WATER IN HOLE LOCATION
(SEE TABLE) D C LIFTING HOLE 2.88D
MOUNTING HOLES 0.688D AIR FLOW
129.00 [328]
86.61
LEFT SIDE VIEW CONTROL [2200]
BOX 83.36
NOTE:
[2117]
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS.
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER.
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL
END OF UNIT FOR SERVICE.
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO CONTROL
BOX TO ISOLATE UNIT. B
A MOUNTING
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD ON LOCATION
UNIT. 83.00 [2108]
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO
CHANGE WITHOUT NOTICE. 86.00 [2184]
CONTROL BOX END
15
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
88.00
[2235]
098C & 108C COMPACT UNITS ONLY: CLEARANCE, SERVICE AND ACCESS
REQUIREMENTS (NOT WALL OR WELL DIMENSIONS) FOR CHILLERS EXD14102 & EXD16112.
AIR FLOW - NO OBSTRUCTIONS
POWER ENTRY
SEE NOTE 4
5.13
[130] 71.50
[1816]
64.50
[1638]
16
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
88.00
[2235]
SEE NOTE #8
48.00
[1219] AIR FLOW
SIDE & BOTTOM
TOP VIEW
5.13
[130] 71.50
[1816]
64.50
[1638]
NOTE:
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS.
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER. 86.61
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL CONTROL [2200]
END OF UNIT FOR SERVICE. BOX 83.36
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO CONTROL
BOX TO ISOLATE UNIT. [2117]
B
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD ON
UNIT.
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO
CHANGE WITHOUT NOTICE.
7 - COMP #2 ON TWO COMP UNIT.
CHILLER POSITION A1 MOUNTING
COMP #1 ON SINGLE COMP UNIT.
WITH 1 COMP LOCATION
8 - COMP #1 ON TWO COMP UNIT.
CHILLER POSITION A2
WITH 2 COMP 83.00 [2108]
86.00 [2184]
CONTROL BOX END
17
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ALLOW 60"
48.00 AIR FLOW [1524] FOR
[1219] SIDE & BOTTOM SERVICE
24.00
[610] ACCESS
88.00
[2235]
48.00
AIR FLOW
[1219]
SIDE & BOTTOM TOP VIEW
POWER ENTRY
SEE NOTE 4
5.13
[130] 71.50
[1816]
64.50
[1638]
86.61
NOTE: [2200]
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS. CONTROL
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER. BOX 83.36
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL
[2117]
END OF UNIT FOR SERVICE.
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO CONTROL
BOX TO ISOLATE UNIT.
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD ON
UNIT.
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO B A
CHANGE WITHOUT NOTICE. MOUNTING
83.00 [2108] LOCATION
86.00 [2184]
18
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ALLOW 60"
48.00 AIR FLOW
[1524] FOR
[1219] SIDE & BOTTOM
24.00 SERVICE
[610] ACCESS
88.00
[2235]
CONTROL
BOX
POWER ENTRY
SEE NOTE 4
5.13
[130] 71.50
[1816]
64.50
[1638]
273.00 [6934]
AIR FLOW
LEFT SIDE VIEW POWER ENTRY
SEE NOTE 4
86.61
CONTROL [2200]
NOTE: BOX 83.36
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS. [2117]
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER.
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL
END OF UNIT FOR SERVICE.
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO CONTROL
BOX TO ISOLATE UNIT.
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD ON
UNIT.
B A
MOUNTING
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO
83.00 [2108] LOCATION
CHANGE WITHOUT NOTICE.
86.00 [2184]
19
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ACDX1B-138E EXD16122 6" VIC 30.00 [762] 17.17 [436] 101.89 [2588] 109.75 [2788]
EXD18122 8" VIC 28.00 [711] 18.17 [462] 104.00 [2642] 105.5 [2680]
EXD20122 10" VIC 27.12 [689] 19.17 [487] 105.32 [2675] 102.88 [2613]
ALLOW 60"
48.00 [1524] FOR
AIR FLOW
[1219] SIDE & BOTTOM SERVICE
24.00
[610] ACCESS
88.00
[2235]
48.00
[1219] AIR FLOW
SIDE & BOTTOM
TOP VIEW
POWER ENTRY
SEE NOTE 4
5.13
[130] 71.50
[1816]
64.50
[1638]
AIR FLOW
POWER ENTRY
SEE NOTE 4
LEFT SIDE VIEW
86.61
CONTROL [2200]
NOTE: BOX 83.36
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS. [2117]
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER.
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL
END OF UNIT FOR SERVICE.
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO CONTROL
BOX TO ISOLATE UNIT.
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD ON B
UNIT. A
MOUNTING
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO 83.00 [2108] LOCATION
CHANGE WITHOUT NOTICE.
86.00 [2184]
20
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ALLOW 60"
48.00 AIR FLOW [1524] FOR
[1219] SIDE & BOTTOM SERVICE
24.00
[610] ACCESS
#12 #10 #8 #6 #4 #2
88.00
[2235]
#11 #9 #7 #5 #3 #1
48.00
[1219] AIR FLOW
SIDE & BOTTOM
TOP VIEW
POWER ENTRY
SEE NOTE 4
5.13 69.86
[130] [1774]
62.86
[1597]
86.61
CONTROL [2200]
BOX 83.36
[2117]
NOTE:
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS.
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER.
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL
END OF UNIT FOR SERVICE.
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO B A
CONTROL BOX TO ISOLATE UNIT. MOUNTING
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD LOCATION
ON UNIT. 83.00 [2108]
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT
TO CHANGE WITHOUT NOTICE.
86.00 [2184]
21
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
14-FAN UNIT
CHILLER CONN A B C D
ACDX1B-198C
ACDX1B-208C EXT18122 8" VIC 29.12 [740] 18.17 [462] 106.44 [2704] 105.50 [2680]
ACDX1B-148S EXT20122 10" VIC 26.45 [672] 19.17 [487] 107.81 [2738] 102.88 [2613]
ACDX1B-158S
ACDX1B-178S
ACDX1B-188S
ALLOW 60"
48.00 AIR FLOW [1524] FOR
[1219] SIDE & BOTTOM SERVICE
24.00
[610] ACCESS
88.00
[2235]
#13 #11 #9 #7 #5 #3 #1
48.00
AIR FLOW
[1219]
SIDE & BOTTOM
TOP VIEW
POWER ENTRY
SEE NOTE 4
5.13 69.86
[130] [1774]
62.86
[1597]
POWER ENTRY
SEE NOTE 4
86.61
CONTROL [2200]
BOX 83.36
[2117]
NOTE:
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS.
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER.
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL
END OF UNIT FOR SERVICE.
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO B A
CONTROL BOX TO ISOLATE UNIT.
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD
MOUNTING
ON UNIT. 83.00 [2108] LOCATION
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT
TO CHANGE WITHOUT NOTICE.
86.00 [2184]
22
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
CHILLER CONN A B C D
16-FAN UNIT
ACDX1B-198S EXT18122 8" VIC 29.12 [740] 18.17 [462] 106.44 [2704] 105.50 [2680]
ACDX1B-208S EXT20122 10" VIC 26.45 [672] 19.17 [487] 107.81 [2738] 102.88 [2613]
ALLOW 60"
48.00 AIR FLOW [1524] FOR
[1219] SIDE & BOTTOM SERVICE
24.00
[610] ACCESS
88.00
[2235]
48.00
AIR FLOW
[1219]
SIDE & BOTTOM
TOP VIEW
POWER ENTRY
SEE NOTE 4
5.13 69.86
[130] [1774]
62.86
[1597]
86.61
CONTROL [2200]
BOX 83.36
[2117]
NOTE:
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS. B
23
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ALLOW 60"
48.00 AIR FLOW [1524] FOR
[1219] SIDE & BOTTOM SERVICE
24.00
[610] ACCESS
88.00
[2235]
48.00
[1219] AIR FLOW
SIDE & BOTTOM
TOP VIEW
POWER ENTRY
SEE NOTE 4
5.13 69.86
[130] [1774]
62.86
[1597]
86.61
CONTROL [2200]
BOX 83.36
[2117]
NOTE:
1 - ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS.
2 - VENT & DRAIN CONNECTIONS PROVIDED ON COOLER.
3 - ALLOW 60 [1524] CLEARANCE AT CONTROL PANEL
END OF UNIT FOR SERVICE.
4 - USE MINIMUM 36 [914] FLEXIBLE CONDUIT TO B
CONTROL BOX TO ISOLATE UNIT.
A
5 - WATER PIPING TO BE SUPPORTED TO MINIMIZE LOAD
MOUNTING
ON UNIT. 83.00 [2108] LOCATION
6 - ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT
TO CHANGE WITHOUT NOTICE.
86.00 [2184]
24
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
25
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW
CNT
•
Pos •
Pos •
Pos •
Pos •
Pos
#1 #3 #5 #7 #9
BOX FIELD: INSTALL ISOLATORS AT THE
F
END Pos Pos Pos Pos Pos
CORRESPONDING LOAD POINTS.
#2 #4 #6 #8 #10
• • • • •
A B C D E
26
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW
CNT
•
Pos •
Pos •
Pos •
Pos •
Pos
#1 #3 #5 #7 #9
BOX FIELD: INSTALL ISOLATORS AT THE
F
END Pos Pos Pos Pos Pos
CORRESPONDING LOAD POINTS.
#2 #4 #6 #8 #10
• • • • •
A B C D E
27
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW
CNT
•
Pos •
Pos •
Pos •
Pos •
Pos
#1 #3 #5 #7 #9
BOX FIELD: INSTALL ISOLATORS AT THE
F
END Pos Pos Pos Pos Pos CORRESPONDING LOAD POINTS.
#2 #4 #6 #8 #10
• • • • •
A B C D E
28
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW
CNT
•
Pos •
Pos •
Pos •
Pos •
Pos
#1 #3 #5 #7 #9 FIELD: INSTALL ISOLATORS AT THE
BOX
F CORRESPONDING LOAD POINTS.
END Pos Pos Pos Pos Pos
#2 #4 #6 #8 #10
• • • • •
A B C D E
29
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW
• • • • •
2.38 FREE
TOP VIEW W
• • • • •
A
A B C D E B
L
T
FIELD: INSTALL ISOLATORS AT THE
CORRESPONDING LOAD POINTS. .50 MAX. DIA. RIBBED NEOPRENE PAD
ANCHOR BOLT
DIMENSIONAL CHART
NOTE: Isolator Weights over 1500 lbs. require DESC. RANGE A B L T W H (FREE HT.) H (OPER. HT.)
XL 100-1500 5.125 6.375 8 .625 2.75 5.875 5.25
double springs one inside the other.
XLW 1600-3000 6.875 8.50 10 .625 3.875 5.875 5.25
31
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW
• • • • •
2.38 FREE
32
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW W
A
CNT
•
Pos •
Pos •
Pos •
Pos •
Pos
#1 #3 #5 #7 #9
BOX .50 DIA. STUD
.625 PROJECTION
F
END Pos Pos Pos Pos Pos
#2 #4 #6 #8 #10
• • • • • H
A B C D E B
L
T
FIELD: INSTALL ISOLATORS AT THE
CORRESPONDING LOAD POINTS. .50 MAX. DIA. RIBBED NEOPRENE PAD
ANCHOR BOLT
DIMENSIONAL CHART
NOTE: Isolator Weights over 1500 lbs. require DESC. RANGE A B L T W H (FREE HT.) H (OPER. HT.)
XL 100-1500 5.125 6.375 8 .625 2.75 5.875 5.25
double springs one inside the other. XLW 1600-3000 6.875 8.50 10 .625 3.875 5.875 5.25
33
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW
• • • • •
2.38 FREE
34
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW W
A
CNT
•
Pos •
Pos •
Pos •
Pos •
Pos
#1 #3 #5 #7 #9
BOX .50 DIA. STUD
.625 PROJECTION
F
END Pos Pos Pos Pos Pos
#2 #4 #6 #8 #10
• • • • • H
A B C D E B
L
T
FIELD: INSTALL ISOLATORS AT THE
CORRESPONDING LOAD POINTS. .50 MAX. DIA. RIBBED NEOPRENE PAD
ANCHOR BOLT
DIMENSIONAL CHART
NOTE: Isolator Weights over 1500 lbs. require DESC. RANGE A B L T W H (FREE HT.) H (OPER. HT.)
XL 100-1500 5.125 6.375 8 .625 2.75 5.875 5.25
double springs one inside the other. XLW 1600-3000 6.875 8.50 10 .625 3.875 5.875 5.25
TOP VIEW
• • • • •
2.38 FREE
36
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TOP VIEW W
A
CNT
•
Pos •
Pos •
Pos •
Pos •
Pos
#1 #3 #5 #7 #9
BOX .50 DIA. STUD
.625 PROJECTION
F
END Pos Pos Pos Pos Pos
#2 #4 #6 #8 #10
• • • • • H
A B C D E B
L
T
FIELD: INSTALL ISOLATORS AT THE
CORRESPONDING LOAD POINTS. .50 MAX. DIA. RIBBED NEOPRENE PAD
ANCHOR BOLT
DIMENSIONAL CHART
NOTE: Isolator Weights over 1500 lbs. require DESC. RANGE A B L T W H (FREE HT.) H (OPER. HT.)
XL 100-1500 5.125 6.375 8 .625 2.75 5.875 5.25
double springs one inside the other. XLW 1600-3000 6.875 8.50 10 .625 3.875 5.875 5.25
38
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
39
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Figure 2.7B
SERIES FLOW
Figure 2.7D
40
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
2.8 Electrical Connections The chilled water pump contacts shown on the wiring
diagram should be used in the pump control circuit. These
ACDX-B/AUDX-B contacts stay closed whenever the unit is enabled (see
item 1) and the internal schedule of operation is set for
All units are wired as completely as possible at the factory the unit to operate. However, especially in cases of low
prior to delivery. The connections which must be made by ambient temperature, the contacts should not be the sole
the installer are to the main power source, control power means of controlling pump operation.
source, separate chiller heater power source and interlocking
5. Remote Evaporator - On AUDX units with remote chiller
the satellite equipment. In connecting power wiring to the
barrel or DX coil, field wiring is required for liquid line
unit, the following precautions should be taken:
solenoids, water or air temperature sensors and flow
• All field wiring is to be in accordance with the National switches. The 120VAC wiring should be run in a separate
Electrical Code and state and local codes. conduit from the sensor wiring. Also, shielded cable must
• All wiring is to be checked for damage and all terminal be used for the sensor wiring with the shield grounded
connections tested for tightness. Unit terminal blocks are only to the main unit sub-panel.
to be connected with copper conductors only, sized per 6. Crankcase heaters are wired in the control circuit. On
ampacity listed on unit data plate. units with field-supplied control circuit power, the 15 amp
• The power supply should match the unit nameplate in fused disconnect switch must be closed (on) at all times
volts, phase and Hertz. Voltage must be within ± 10% of for heater operation. On units ordered with the control
nameplate value and voltage imbalance between phases transformer option, the main unit power field fused dis-
must not exceed 2%. connect (and local safety switch if used) must be closed
(on) at all times for heater operation.
• For minimum circuit ampacity and maximum fuse size,
see Unit Nameplate. 7. The compressor crankcase heaters must be energized for
24 hours before the unit is initially started or after a pro-
• All electrical connections should be periodically tightened.
longed open disconnect.
Refer to the unit nameplate data for the minimum circuit
8. All field wiring must be in accordance with all applicable
ampacity and maximum allowable dual element fuse size.
local and national codes.
The factory supplied field power block is sized to accept wires
sized per NEC, 75C (3-in-conduit) up to 500MCM as required. 9. Minimum and maximum unit supply voltages are shown
When multiple wires per pole are required to stay at or below in the following tabulated data.
500MCM, the power block supplied will have multiple wire Supply Voltage
per pole capability. Nominal Minimum Maximum
200V 187V 220V
A separate 15 amp 115V field power supply is required to
power the main control circuit (which includes the compressor 230V 207V 253V
sump heaters) unless the control transformer option is 460V 414V 506V
included. 575V 518V 632V
41
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
47
2.0 INSTALLATION (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
49
3.0 OPERATION - MECHANICAL SYSTEMS ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3.1 Qualified Unit Start-up Report 3.2 Typical ACDX-B Refrigerant Piping
The unit should be started up only by a refrigeration ACDXB048 thru 068 are single compressor, single circuit
technician who is familiar with accepted operation units.
practices for refrigeration systems.
ACDXB098 thru 138 are two compressor, two circuit
Use screw unit start-up report, Form NS4001, to record units.
all temperature, pressure, electrical readings and control
ACDXB148 thru 208 are three compressor, three circuit
settings. A copy must be forwarded to Dunham-Bush,
units.
Inc., North American Service, Harrisonburg, Virginia
before the warranty will be honored. See Figure 3.2A for typical ACDX-B packaged chiller
refrigerant piping.
See Figure 3.2B for typical AUDX-B condensing unit
piping.
NOTE: When the unit is spring mounted, care should
be taken to insure that piping is not excessively rigid.
See Section 2.6.
50
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
DISCHARGE
CHECK VALVE
COMP
SUCT. DISCH.
VALVE VALVE
(OPTION) (OPTION)
FLANGE
SUCTION
O-RING, ETC.
SOLENOID C3
VALVE COMPRESSOR LIQUID
INJECTION FITTINGS
WATER STL
AND PORT KIT
OUT CHECK
VALVE
REGULATOR
HOT GAS ACCESS VALVE
SIGHT
GLASS
SOLENOID
VALVE
EXPANSION VALVE
TXV THERMAL (STD) RELIEF VALVE
ELECTRONIC (OPT) 400#
LIQUID
ACCESS VALVE
SUBCOOLER
SOLENOID SUBCOOLER
VALVE LIQUID OUT IN
COND.
LIQUID
VALVE
FILTER DRYER
AND CORES
CONDENSATE
COND.
IMPORTANT NOTE:
- TYPICAL PER CIRCUIT
51
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
DISCHARGE
CHECK VALVE
COMP
SUCT. DISCH.
VALVE VALVE
(OPTION)
FLANGE
SUCTION
FILTER
SUCTION
FROM SPECIAL INJECTION ORIFICE,
REMOTE O-RING, ETC.
EVAPORATOR C3
COMPRESSOR LIQUID
INJECTION FITTINGS
STL
AND PORT KIT
CHECK
SOLENOID VALVE
VALVE
ACCESS VALVE
SIGHT
GLASS
SOLENOID
REGULATOR VALVE
HOT GAS
RELIEF VALVE
400#
FILTER DRIER
SHUT OFF
VALVE
LIQUID
SUBCOOLER
SUBCOOLER
LIQUID LIQUID OUT IN
COND.
LIQUID
TO REMOTE
EVAPORATOR
CONDENSATE
COND.
IMPORTANT NOTE:
- TYPICAL PER CIRCUIT
52
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3.3 Pre-Start-Up Procedure for NOTE: Sump oil heaters should be energized a
minimum of 24 hours and the oil sump temperature
ACDX-B Packaged Chillers & must be at a minimum of 100°F (38°C) prior to arrival
AUDX-B Split Systems of start-up representative. This will ensure that the
oil is warm enough to vaporize any dissolved
The unit is ready for start-up when the following refrigerant and that the oil is within the normal
procedures have been completed. operating temperature range.
1. Water piping for the cooler is installed and tested. 2. Before starting the compressor(s), check all three
phases of supply voltage, of all legs of the motor.
2. Electrical connections are made and properly fused. They must be within ± 10% of the nameplate voltage.
3. Unit has been leak tested, leaks corrected, and charge 3. Start compressor(s), check the gages and note if the
completed. pressures are within the prescribed limits.
4. Compressor crankcase heater(s) has been energized 4. Check the refrigerant sight glass at the TX Valve to
for a minimum of 24 hours. be sure it is free of bubbles. If not, charge as specified
5. Calibrated refrigerant gages have been connected per section 4.8 Charging.
to the suction and discharge pressure ports. 5. Shut the compressor down and check the compressor
6. Turn on the chilled water pump, check direction of crankcase sight glass for oil level. Oil level must be
rotation and adjust the water flow through the cooler maintained at or below the sight glass prior to
to the specified flow rate. Bleed off all entrained air. package start-up. Due to refrigerant solubility in oil,
the level may rise over the sight glass prior to package
7.Manually energize the fan starters and check the fan start-up. This means the oil may be in the internal
rotation. Fans should pull air through the condenser cavities of the compressor causing unacceptable high
coil and discharge vertically upwards. Rotation can hydraulic loads or “liquid stress”. Oil may have to be
be changed on 3-phase motors by interchanging only drained out. Refer to page 56, section 3.6.1.
two wires on the main terminal block.
6. Restart the compressor. After an hour of operation
8. Check all refrigerant valves to be sure they are open. the expansion valve superheat setting should be
9. Proceed to System Start-up. checked, it should be between 9° and 12°F at full
load design conditions. In some instances, it will be
necessary to lower the superheat setting to ensure
3.4 System Start-Up & Reporting proper distribution. Turn the TX valve adjustment
for ACDX-B Packaged Chillers stem clockwise to increase the superheat setting and
counterclockwise to decrease the setting. Be sure
& AUDX-B Split-Systems and allow ample time between each adjustment for
the system to rebalance.
1. Request for Start-Up Representative ACDXB/AUDXB 7. The electrical control settings should be checked and,
Start-up service is an option for these units and is if necessary, reset to those settings indicated on the
requested when the unit is ordered. If you purchased wiring diagram. Safety controls are factory set and
start-up service, then after the installation has been must be maintained at settings indicated on the
completed and checked, Form 9180 must be filled wiring diagram.
out and sent to the local Dunham-Bush 8. The temperatures of the chilled water both in and
representative who sold the unit. Following receipt out, should be checked to insure the unit is operating
of this signed form, a representative will be sent to within the desired temperatures.
the customer. The purchaser should have competent
service and operating personnel in attendance to
assist in the work involved, and also to be trained in
the operation and maintenance of this unit.
The representative will inspect the installation to
determine whether it meets Dunham-Bush, Inc.
requirements, perform the initial start-up of the
installation, determine whether it is in satisfactory
operating condition, and instruct specified customer
personnel in its operation and maintenance for the
length of time specified in the purchase contract.
53
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3.5 System Flow Rate ACDX-B
The quantity of chilled water being circulated can be An alternate method of determining GPM is to measure
estimated by determining the water pressure drop pressure difference from pump inlet to outlet and read
through the cooler and reading GPM from the GPM from pump curve.
appropriate pressure drop curve, Table 3.5A.
Water flow rate must not vary more than ± 10% from
design flow rate.
Table 3.5A
NOTES:
1. A constant water flow rate is required with a
minimum of 3 gallons per ton (3.25 L/kW) water loop
volume increasing up to 10 gallons per ton (10.8 L/
kW) for process, low load applications with small
temperature ranges and/or vastly fluctuating load
conditions.
2. AUDX-B split system chillers use the same coolers as
the ACDX-B packaged chillers.
3. AUDX-B split-system remote cooler modules are
supplied insulated with the refrigeration specialty
parts all piped and wired.
54
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Figure 3.5B Water Side Pressure Drop
FEET
OF
KPa WATER 1 2 3 4 5 6 7 8 9 10
150 50
120 40
90 30
60 20
45 15
30 10
24 8
18 6
15 5
12 4
9 3
GPM 80 100 150 200 300 400 600 800 1000
L/S 3.8 6.3 9.5 12.6 18.9 25.2 37.8 50.5 63.1
WATER FLOW RATE
55
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3.6 Compressor Lubrication 3.6.5 Compressor Repairs (Internal)
Contact factory or an Authorized DB Service Agency if a
compressor malfunction is suspected.
3.6.1 Oil Level
The oil level in the compressor(s) should be checked 3.6.6. Compressor Repairs (External)
periodically, with the compressor stopped and the oil sump Proper operation of unloaded start, loading, and unloading
temperature at least 20°F above refrigerant saturated is controlled by solenoid valves. Any of these solenoid valves
discharge temperature. Stage the unit down until all may be repaired or replaced in the field, as required. Also
compressors are off and check the compressor crankcase sight the compressor crankcase heater may be replaced.
glass for oil level. The level should be just at the sight glass
or slightly below. It should never read over 1/2 of the sight
glass.
3.7 Hydraulic Capacity Control
Oil Sight Glass Interpretation - Oil level reading over 1/2 of
the sight glass on the compressor MUST BE AVOIDED. During System
the off cycle, depending on the amount, the oil will fill the
rotor lobes, discharge manifold and motor cavities subjecting Each compressor has a hydraulic control system to position
the compressor to unacceptably high hydraulic loads during the capacity control slide valve, thereby regulating compressor
start-up which can damage the compressor. If the oil is above capacity. It is composed of a normally closed solenoid valve
the sight glass, drain it to the bottom of the sight glass before (A), a normally open solenoid valve (B), an internal pressure
starting the compressor. If the oil level is above the sight regulating valve, a loading rate control valve (C), and an
glass during operation, drain oil from the compressor down unloading rate control valve (D).
to the bottom of the sight glass. With valves A and B both energized (A open, B closed) during
The compressor is protected against oil failure by means of normal compressor operation, high pressure oil is directed
an internal float switch. Therefore, operation of the to the slide valve. This pressure acts on the surface of the
compressor with oil levels below the sight glass is perfectly slide valve piston creating a force which is sufficient to
acceptable and in some cases, desirable. If there is no trip overcome the opposing spring force and to move the valve
on oil failure, do not be concerned and do not add any oil to in the direction of increasing capacity. When the compressor
compressor. is given a "hold" command, valve A is de-energized (closed)
and slide valve movement is halted. The internal pressure
If the oil sight glass level is 1/3 or less, you can assume that regulating valve allows oil to bleed from the slide valve
the level is actually below the sight glass. With the level chamber during the hold condition. If valve B is then de-
below the sight glass, a small amount of oil will sit in the energized (open), the high pressure oil acting on the slide
back of the glass, hence giving a false indication. valve will be vented to suction, and the pressure in the slide
valve chamber will be reduced. The slide valve spring will
3.6.2 Recommended Oil now move the piston back toward the minimum capacity
The unit is factory-charged with Dunham-Bush Karlube #2 position.
oil for R-22 refrigerant applications. It is suggested that a
gallon or more of Karlube #2 oil be obtained and kept on The rates of loading and unloading are regulated by load
hand at the job site. Consult factory for oil selection when rate needle valves C4 and C5 respectively. The proper time
refrigerants other than R-22 are used in the ACDX/AUDX for total slide valve travel (loading or unloading) is 40 + 10
machine. seconds. Load and unload rates will be slower when the
compressor is cool and at low head than when hot and at
3.6.3 Oil Analysis high head. To adjust load or unload rate, remove the socket
It is recommended that an oil sample be taken from each head O ring plugs to reach the needle valves. To decrease
compressor and submitted for laboratory analysis. Dunham- rate, turn needle valve clockwise.
Bush offers this service in its Oil Kare Program. This analysis See table for a summary of solenoid valve operation vs. slide
should be done at the beginning and end of each operating valve operation.
season, or every six months if the unit is used year round. Oil
should be changed if analysis indicates acids, moisture, SLIDE VALVE POSITION
contaminants or metals exceeding normal levels. UNLOADING UNLOADING HOLD
SOLENOID VALVE
3.6.4 Procedure For Adding/Changing Oil A
CLOSED OPEN CLOSED
(DE-ENERGIZED) (ENERGIZED) (DE-ENERGIZED)
Adding oil should not be necessary unless due to loss of oil (NORMALLY CLOSED)
thru system leaks or unless oil is lost during service procedures. CLOSED CLOSED CLOSED
SOLENOID VALVE
Oil is added thru the oil drain/fill valve near the bottom of B (DE-ENERGIZED) (ENERGIZED) (ENERGIZED)
the compressor housing using an appropriate pump and hose (NORMALLY OPEN)
following EPA guide lines. Keep in mind that the oil sump is
at discharge pressure and this pressure must be overcome to
add oil.
When changing compressor oil, follow EPA procedures,
initially add only as much oil as was removed until system
operation is checked.
56
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3.7 Hydraulic Capacity Control 3.7.2 Adjusting Rate of Slide Valve
System (cont.) Travel
The proper rate of slide valve travel, from fully loaded to
fully unloaded, or vice versa is 40 seconds, plus or minus 20
SUCTION
TERMINAL BO
seconds, and is controlled by independent needle valves near
DISCHARGE each solenoid valve respectively.
SOLENOID External Adjustment
B Needle Valve (C5)
Normally Open Controls Unload Rate
A A
SUCTION
NORMALLY CLOSED
SOLENOID
LOADING SOLENOID `A A
External Adjustment
Normally Closed
Needle Valve (C4)
Controls Load Rate
LOADING RATE
CONTROL VALVE `C4
NOTES:
1. Make adjustments at design conditions only.
2. To reach the needle valves, remove the plugs (C4, C5).
This information describes the operation, adjustment
and troubleshooting steps for compressors 3. The needle valves are sealed internally so as to minimize
leakage.
manufactured with the pad mounted unloader.
Familiarize yourself with all of the data contained in 4. A safety stop prevents removal of the needle valves.
this section as it details some things that should not be
done. 3.7.3 Field Checks
3.7.1 Operation of the Unloader The Schrader valve pressure tap on the pad unloader can be
A. Loading: solenoids A & B are energized. High pressure used to read various pressures:
oil from internal strainer flows to load piston. Loading A. Suction pressure (downstream of suction filter). Set the
rate controlled by load rate needle valve (C4). controller in the “manual” mode. The suction pressure at
B. Unloading: solenoids A & B are de-energized. Oil flows this point should never be more than 5-7 PSIG (34.5 -
from load piston to suction. Unloading rate controlled 48.3 kPa), below the suction pressure read at the suction
by unload rate needle valve (C5). service valve. A greater pressure difference can indicate a
C. Hold: solenoid A de-energized, solenoid B energized. Oil dirty suction filter.
is captured in load cylinder at a pressure approximately B. Load cylinder pressure. With the controller in the “manual”
40 to 90 PSI (279.5 - 620.7 kPa), above suction pressure. mode, close the C5 needle valve and then disconnect a
wire to solenoid B. At a part or full load condition, the
Vertical Screw Compressor
pressure should equalize to approximately 40-90 PSIG
Suction Filter
(275.9 - 620.7 kPa) above suction pressure. At a fully
Suction
Gas Ext. Adj. Needle Valve
unloaded condition, this pressure can be equal to suction
Filter Controls Unload Rate (C5) pressure. To watch the effect of relief valve performance,
C5 Solenoid ‘B’
switch controller to “manual-load” briefly, and back to
Connection Normally Open “manual-hold”. Pressure should rise and then fall back to
B (Unload) approximately 40-90 PSIG (275.9 - 620.7 kPa) above suc-
Relief Valve
3-Way tion. Reconnect wire to solenoid B.
Load and Strainer
Solenoid Valve
Unload C2 Connection
Schrader Valve
Load Piston A
Solenoid ‘A’
Normally Closed
(load)
C4 Connection
Ext. Adj. Needle Valve
Controls Unload Rate (C4)
Oil Strainer
57
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3.7.4 Troubleshoting
Symptom
Top of Enclosure
58
3.0 OPERATION - MECHANICAL SYSTEMS (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3.8 Low Ambient Operation ambient, providing wind velocity is less than 5 MPH, and the
unit capacity requirements are a minimum of 50%. Electronic
expanion valve(s) may also be provided with this option, and
3.8.1 Condenser Head Pressure Control
are required if the ambient temperature may reach as low as
Outdoor air-cooled units required by application to start and
-20°F.
run at ambients below normal summer conditions require
some means to keep the condensing pressure high enough 3.8.4 Cooler Freeze Protection - Low Ambient
to insure adequate expansion valve feed to the cooler to Cooler freeze protection is a serious concern with outdoor
prevent low side pressure trips, particularly during cold starts. packaged chillers and the responsibility for the proper
Two types of condenser fan control are available to allow the implementation, monitoring and maintenance of both factory
units to operate at the ambients and loads indicated. and field installed protective devices and procedures lies solely
with the customer. The ACDX coolers are heat tape wrapped
3.8.2 Standard Factory Installed Fan Cycling
which utilize built-in 38°F (3.33°C) thermostats and are
This commonly applied scheme cycles condenser fans “on”
insulated for protection down to about -20°F (-28.9°C).
and “off” in response to head pressure to maintain the head
However, this protection disappears if power fails, power to
pressure within an acceptable range for proper system
the heater circuit is switched off or left off by mistake, or the
operation. This methods will permit starting and sustained
heater tapes burn out. In this regard, it is advisable to read
running 20°F (-6.66°C) ambient.
and log the heater circuit amp draw at the first low ambient
The minimum ambient shown above reflect the performance shut-down opportunity for future service and monitoring
of the condenser surface exposed to the operational fan(s) reference. In light of all the above, the following should be
as well as that portion of the surface rejecting heat by natural considered:
convection with related fans “off”. To further assist low
1. Drain the cooler and water piping thoroughly for long
ambient starts, all fans are held “off” until the head pressure
term shut-down at ambients below 32°F (0°C). Drain fit-
reaches 190 psig (310 kPa). This alone cannot insure sustained
tings are provided on the cooler for this purpose.
operation if the system load is not high enough to produce
the minimal pressures required. 2. Add ethylene glycol to the chilled water system at a per-
cent concentration suitable for a freeze point at least 10°F
3.8.3 Optional Variable Speed Fan Control (5°C) below the minimum expected ambient.
This scheme utilizes fan cycling but also adds speed control 3. The field installed cooler heater disconnect switch must
to the lead fan or fans. This feature not only serves to stabilize be permanently tagged “DO NOT OPEN THIS SWITCH”.
the head pressure between normal fan staging but also allows
4. Make absolutely sure that responsible people know ex-
for virtually “no fan” operation down to 0°F (-17.77°C)
actly how to react to general power failures.
NOTE: Refer to the unit wiring diagram for fan cycling pressure settings.
CWP Chilled Water Pump Interlock M Contactor (Compressor and Fan Motor)
For ACDX-B/AUDX-B units, it is recommended that The contactor, operated by the control circuit,
an interlock between the chilled water pump and provides power individually to the compressor and
the package be provided to prevent the unit from fan motors. Two contactors are used for double-
operating with the chilled water pump off. Connect delta start of the compressors. These devices are
the interlock to the terminals shown on the diagram. amp rated to handle both rated load amps and
60 locked rotor amps.
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
61
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
4.2 Typical Control Sequence of • System voltage above undervoltage relay (UVR) setting
• chilled water pump running
Operation: • chilled water flow switch made
Models ACDXB048-138 • compressor circuit breakers on
Refer to pages 71-79 for wiring diagrams. • customer unit control contact closed
• control switch and compressor switches on
The following sequence of operation for two compressor unit
• reset pressed on microcomputer keypad
is typical of all ACDX-B Models. Refer to the wiring diagram
furnished with the unit for specific information. • power has been on the microcomputer for 15 minutes
• all safety conditions satisfied
( ) Control Identification Symbol
• leaving chilled water temperature 2°F (1°C) or more above
( ) Circuit Line Number setpoint
Important Note! • schedule in micorcomputer set for unit operation
A compressor is started by first energizing 1M1 followed by
With all the control circuit switches (S1-S3) in the “off” 1M2 after 1 second if step start is activated. Otherwise, both
position, Terminals #1 and #2 must have 115 volts supplied contactors energize together. Anti-recycle time of 15 minutes
for a minimum of 24 hours to energize the compressor is initiated within the computer at start.
crankcase heaters (HTR).
The liquid line valve will open when the compressor starts.
Preliminary Sequence - Close the main power disconnect As condenser pressure rises, the microcomputer will stage
switch. Verify proper voltage. Check to see that the indicating on the fans according to the fan setpoints.
light on the under voltage relay (UVR) is lit. This light must
be on to indicate proper phase rotation for the Stage 1 Modulation
compressors. If the light is not on, disconnect the main
When the compressor starts, the microcomputer monitors
power and reverse any two phase legs at the Main Incoming
amperage by means of 1CT, leaving water temperature using
Power Terminal Block. (WARNING! DO NOT REVERSE THE
1TS, and condensing pressure. These inputs are used to
LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW
control the loading and staging of the compressor. The
THE COMPRESSORS TO RUN BACKWARDS, CAUSING SEVERE
compressor’s loading is controlled by pulsing signals to the
DAMAGE, & WILL VOID THE COMPRESSOR WARRANTY!)
load and unload solenoids.
Check phase sequence using a meter before compressor start.
Stages 2 and 3 Starting
The crankcase heater relay contacts (1M2-1) and (2M2-1) are
closed and are supplying power to the compressor crankcase If the safety conditions are satisfied for the #2 compressor,
heaters. Power must also be supplied to the chiller heaters at least 1 minute has elapsed since #1 compressor has
by the separate customer supplied 115 VAC supply. Terminal reached full load, and leaving water temperature remains
block 5TB. above the deadband; 2M1 and 2M2 will be activated by the
microcomputer, (2M2 will close after 1 second delay, if step
Control power is turned on by the Control Power Switch (S1).
start is desired). #2 compressor also has a 15 minute anti-
Start up the chilled water pump. The water flow is confirmed recycle timer built into the microcomputer. Loading of the
when the water flow switch completes the electrical circuit #2 compressor is controlled the same as compressor #1.
across Terminals #31 and #32 on three compressor or
For each compressor, the liquid line valve will open when the
terminal #11 and #12 on single compressor and when chilled
compressor starts.
water pump auxiliary (CWP) closes between #151 and #152
on three compressor or #8 and #11 on single compressor The fans will also be staged on to maintain proper condenser
machine. pressure.
Check to make sure unit control contacts between terminals 4.2.2 Shutdown Sequence
#10 and #33 on three compressor or terminal #8 and #13
on single compressor close when the unit needs to operate. Stages 2 and 3 Shutdown
Set the desired leaving water temperature (e.g. 44°F - 6.66°C)
When leaving water temperature falls below setpoint minus
in the microcomputer setpoint 1A. See micro-computer
deadband, the compressors begin to unload. When the
controller section.
operating compressor capacities fall below a pre-determined
Place the compressor control circuit switches (S2-S3-S4) in setpoint, the last compressor is shut down. The
the “On” position, thus energizing the balance of the control corresponding liquid line valve closes and the fans turn off.
circuit. All safety controls must be satisfied and the When a compressor turns off, the remaining compressors
microcomputer has been RESET. The system may be in a load up to maintain the leaving water temperature.
“Time-in” mode for up to fifteen minutes before the first
Stage 1 Shutdown
compressor will start.
If the leaving water temperature is still lower than the
4.2.1 Stage-Up Sequence setpoint, compressor 1 unloads fully and then turns off.
Circuit #1 liquid line valve turns off and the fans turn off.
Stage 1 Starting
In summary, the following conditions must be met to start a
compressor:
62
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
1 2 3
CONTROL ANALOG DIGITAL MENU
HELP
4 5 6
ALARMS SET AUTH
7 8 9
CLOCK CONFIG SYSTEM
LOWER PAGE
RESET ENTER
+/-
019318A1 Rev. 0
63
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
64
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
4.3.3.5 To Alter Setpoint Data 5. Press ENTER to continue. The last ENTER will store the
1. You must be authorized and in the PROG mode. See new date and time.
section 4.3.3.4. WARNING: Setting the clock will cause a system reset. The
2. Select SETPOINTS A & B on the main menu. Press ENTER. entire unit will shut down and start over again. If the change
3. Use the up or down arrow keys to select the setpoint to was started inadvertently, press MENU key before completing
be changed. Press ENTER. A cursor will flash over the the change.
setpoint A value. 4.3.3.8 To Display Data without Accessing Menu
4. a) If you want to change setpoint A, press in the desired 1. Press LOWER FUNCTION.
new value and press ENTER. If the new value is within 2. Press function desired (blue sub-script)
limits, it will be stored in memory. The cursor will then
3. Press item number to be displayed.
move to setpoint B.
4. Press ENTER.
b) If you do not want to change setpoint A, press ENTER.
EX: To display analog input #5, press LOWER FUNCTION,
5. Repeat Step 4 for Setpoint B.
ANALOG INPUT, 5, ENTER.
4.3.3.6 To Calibrate Temperature and Pressure 4.3.3.9 To Revise Unit Schedule of Operation
Sensors (Optional)
NOTE: Pressure calibration should only be done by a If a seven day time schedule of unit operation is desired, the
qualified refrigeration technician. Calibrate amps internal real time clock of the microcomputer can be used.
with potentiometer on filter board. When the SCHEDULE control point is ON, the unit is allowed
to operate. The following procedure is used to modify the
NOTE: For units with SI display option, the critical operating schedule.
temperature and pressure calibration values are 1. Perform the authorization procedure (See 3.4).
stored in the setpoints corresponding to the sensor
2. Press MENU key.
names or numbers.
3. Use Up and Down to select CONTROL POINTS.
1. You must be authorized and in the PROG mode. See 4. Press ENTER.
Section 4.3.3.4. 5. Use Up and Down to select SCHEDULE control point.
2. Display the analog sensor to be calibrated on the top 6. Use to display the first schedule. The standard display
line of the display. screen would show:
3. Press ENTER to show ZERO CALIBRATION value. CP 17 SCHEDULE GRP:1 SCH:1 0000 2400 DAYS: *** ALL
4. Use an accurate gauge to measure the analog value when DAYS ***
it is stable and near design conditions. This indicates that control point 17 named SCHEDULE is
5. Determine the revised zero calibration required as controlled by schedule group (GRP) #1. The first schedule
follows: Meter Reading - AI Display + Zero Calibration (SCH:1) turns on at 0000 hours and off at 2400 hours
= New Zero Calibration. The new zero calibration must (military time) every day of the week. Thus it is on all the
be rounded to the nearest whole number. time.
6. Press ENTER to place the cursor on the zero calibration 7. To change this schedule, press ENTER. The cursor will
value. flash over the turn-on time. To move to the next schedule,
7. Enter the new value from Step 5. Negative values are press the right arrow key.
entered by pressing LOWER FUNCTION +/- before the 8. Use the number keys (0-9) to enter the revised turn-on
number. time using military format.
8. Press ENTER to store the revised zero calibration. 9. Press ENTER. The cursor will move over to the turn-off
time.
For example, if a suction pressure gauge shows 58 psig
10. Use the number keys to enter the turn-off time in military
and the computer displays 60.3 psig with a zero
format.
calibration of -1, then new calibration would be 58 -
60.3 + (-1) = -3.3 (-3). So the zero calibration should be 11. Press ENTER. The cursor will move to DAYS during which
changed to -3. this schedule is active.
12. To change the days for this schedule, press one or more
4.3.3.7 To Set Date and Time of the following number keys:
1. You must be authorized. See Section 4.3.3.4. 0 - Clear all current days;
2. Select DATE & TIME SET on the main menu. Press ENTER 1 - Sunday(S); 2 - Monday(M);
to display current date and time. 3 - Tuesday(T); 4 - Wednesday(W);
3. Press ENTER key to move cursor to each date/time item. 5 - Thursday(R); 6 - Friday(F);
4. As each item flashes, use the number keys to enter revised 7 - Saturday(A); 8 - *** ALL DAYS***
data if necessary. The day of week, SUNday through 13. Press ENTER. The revised schedule number is now stored.
SATurday, is selected by number keys 1 through 7,
14. To add another schedule, press the right arrow key and
respectively.
repeat steps 7-13.
65
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
15. To delete a schedule, clear all of the days by pressing 0 18. Sensor alarm shutdown
at Step 12. 19. Compressor shutdown indication (No-run alarm)
The schedule group turns on when any of the individual 20. Fast Unload Solenoid Control (ACDX040-185B)
schedules turns on. The turn-on time does not have to
be earlier than the turn off time. Schedules turn on by 21. High Motor temperature safety
time and day, but turn off by time alone. For example, a 22. Low chiller flow alarm
schedule from 1900 to 0700 Saturdays would turn on at
7:00 PM Saturday (time and day) and turn off at 7:00 23. High discharge pressure unload
AM Sunday (time only). 24. Low suction pressure unload
Example: If a unit is to operate at all times except
between the hours of 1:00 AM and 6:00 AM, the 25. Low oil level alarm
following schedule would be entered: A description of each of the functions follows.
CP 17 SCHEDULE GRP:1 SCH:1 0600 0100 DAYS:
*** ALL DAYS ***
4.4.1 Capacity Control of Screw
Another example: A typical building may require cooling Compressors
from 6:00 AM to 7:00 PM Monday - Friday and from The capacity of a compressor can be controlled manually or
7:00 AM -3:00 PM on Saturdays. The schedules would automatically.
be entered as follows: The status of a compressor can be observed by displaying
CP 17 SCHEDULE GRP:1 SCH:1 0600 1900 DAYS: the compressor control point 1/CP or 4/CP.
MTWRF
One of the following messages will be displayed where # is
CP 17 SCHEDULE GRP:1 SCH:2 0700 1500 DAYS: A 1 or 4 for compressors 1 or 2:
CP# COMP LOAD COM Computer load
4.4 ACDX-B/AUDX-B Package CP# COMP CURRENT STATUS: LOAD Manual load
CP# COMP HOLD COM Computer hold
Control CP# COMP CURRENT STATUS: HOLD Manual hold
In order to start a unit, the following conditions must be CP# COMP UNLD COM Computer unload
met: CP# COMP CURRENT STATUS: UNLD Manual unload
• chilled water pump running CP# COMP OFF COM Off on a normal
• chilled water flow switch made control shutdown
• customer control contact closed CP# COMP COFF COM Off on timer (clock
off)
• control switch and compressor switch on
CP# COMP LOFF MAN Manual off or safety
• main unit power on
shutdown
• all safety conditions satisfied
4.4.1.1 Automatic Control
• reset pressed on microcomputer keypad
The computer calculates the operating percent capacity of a
• the compressor has not started within the last 15 compressor by measuring discharge pressure and amps. This
minutes operating percent capacity is then compared to a target
• leaving chilled water temperature 2°F or more above percent capacity. If the operating capacity is outside of a +
set point 3% deadband, the load or unload solenoids are pulsed to
The NC25 computer system performs the following functions match the operating and target percent capacities. Since all
on small screw compressor packages : compressors have the same target, their percent capacities
1. Capacity control of compressors are balanced.
2. Staging of compressors The target percent capacity is given a fixed value when a
3. Compressor current limiting compressor starts or stops. This value is then increased or
4. Ramp control decreased based on how far the leaving water temperature
(TLW) is from setpoint and also on how fast the TLW is
5. Manual lead/lag
approaching setpoint. The target percent capacity will not
6. Compressor start delay change if the temperature is within a temperature deadband
7. Power loss reset around the setpoint.
8. Anti-recycle timing
Some packages may have logic that prevents loading if the
9. Low pressure safety leaving water temperature is falling (negative derivative) at a
10. High pressure safety certain rate.
11. Freeze safety The desired leaving water temperature is typically stored in
12. High Oil Temp Safety setpoint 1A.
13. Alarm output
Calibrations of Amps Calculation at Full Load
14. Fan control
15. Chilled water reset and customer control interlock The amps calculation is calibrated at the factory and does
not normally need to be altered. If a compressor is replaced
16. Hot Gas Bypass option control
or improper operation is observed, the amps values can be
17. Compressor power control (No-stop alarm) calibrated as follows:
66
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
1. Check calibration of discharge pressure, and amps. NOTE: All compressors will revert back to automatic control
NOTE: Calibrate amps with potentiometer on filter board. if the computer is not given a load, unload or hold command
2. Manually load the compressor(s) to full load. This can at least once every 15 minutes. A command can be repeated
be done one compressor at a time if necessary. to meet the 15 minute requirement for manual control.
3. Locate the amps and full load amps (FLA) analog locations
4.4.2 Staging of Compressors
from the analog input menu for the compressor being
The staging of compressors is based on leaving water
calibrated.
temperature and the capacity calculations mentioned in
4. When the compressor(s) are at full load and conditions section 4.1. When the percent capacity target gets up to full
are close to design, record the amps and FLA analog load and temperature is above deadband, a time delay of
values. one or two minutes is initiated before starting the next
5. If the values do not match within 2-3 amps, do the compressor. When the capacity target falls below a stored
following calculation: AMPS - FLA setpoint and temperature is below the deadband, a
6. Locate the amps calculation A setpoint for the compressor is turned off.
compressor from the setpoint menu.
The percent capacity values that the computer is calculating
The setpoint is labeled FLA # CON, where # is 1 through can be displayed by addressing the analog input menu.
4 for each compressor number.
7. Add the value obtained in step 5 to the amps calculation 4.4.3 Compressor Current Limiting
A setpoint value from step 6. The amp limit B setpoint on the unit control data sheet is the
8. Change the amps calculation setpoint to the new value. amp value at which the compressor will be prevented from
loading. The amp limit A setpoint is the amp value at which
9. Verify that amps and FLA now match closely.
the compressor will be given an unload command until the
10. Manually unload the compressor all the way. current drops below the A setpoint.
11. Locate the percent full load capacity (%FLCP) for the
compressor from the analog input menu and record the If the values are changed, the difference between the hold
value. and unload points should not be de-creased below 10% of
compressor RLA so that oscillations will not occur.
12. If the value is 25% ±3%, no change is required. If the
value is less than 22% or greater than 28%, locate the 4.4.4 Ramp Control
%FLA # CON setpoint B. If the setpoint is equal to 25.0, Ramp control can be implemented with the microcomputer.
change it to the value observed in step 11 and proceed Whenever the unit starts with leaving water temperature
to step 13. If the setpoint is not equal to 25.0, change it greater than 5°F above setpoint, a ramp up is generated.
to 25.0 and repeat steps 11 and 12. The ramp start B setpoint specifies the percent capacity target
13. Repeat this procedure for each compressor. at which the ramp begins on the first compressor. This can
be set between 25 and 100 percent. The ramp rate A setpoint
specifies the maximum amount that can be added to the
4.4.1.2 Manual Control target each compressor control interval. Thus a ramp rate of
Screw compressors can be controlled manually with the 0.1 produces the longest ramp rate. Table 1 gives sample
keypad. A compressor can be turned on, off, or placed in ramp times for various ramp rate setpoints and start points
computer control. When a compressor is controlled manually, for a two-compressor machine.
it can be commanded to load, hold, or unload. If current
limit is active, it will not accept a load command. TABLE 1
Sample Ramp Times (Minutes) For a Two-Compressor Unit
To place a compressor in manual control, which turns it on, with a 2-Second Compressor Control Interval
the following procedure is used:
Ramp 25% 50% 75%
1. Log in for authorization. Rate Start Pt. Start Pt. Start Pt.
2. Address desired compressor (1, 4, 7, or 10 control point). Setpoint Setpoint Setpoint Setpoint
3. Press ENTER to modify status. .1 58 50 42
4. Use up or down arrow keys to select ON MAN. .2 29 25 21
5. Press ENTER. The compressor will start or continue to .3 19 17 14
run in hold state. .4 15 12 10
6. Press 0 to return to computer control, 1 to hold, 2 to
load, 3 to unload. Note: Compressors will not load past A formula for calculating ramp time in minutes is:
amp limits.
T = [(# compressors x 100) - start pt.] x Compressor Control
7. Use menu key or arrows to access other data. Interval/(Ramp rate x 60)]
If a safety condition is exceeded while operating manually,
the compressor will shutdown. To put all compressors back The compressor control interval can be determined by timing
into computer control from a locked off state, press RESET. the frequency of load/unload pulses given to a compressor.
It is typically 2 seconds.
CAUTION: Anti-recycle timer is bypassed by manual control.
DO NOT start a compressor more than once every 15 minutes.
67
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
68
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
69
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
L1 1L1
200/3/60 L2 1L2
230/3/60
400/3/50 L3 1L3
* 460/3/60 SEE NOTES 2, 3 & 4 SEE NOTE 6
UNIT 575/3/60
FUSING 1TB 6TB
L1 11FU 5L1 5L1
~ ~ ~
~ ~ ~
L2 12FU 5L2 5L2
L3 13FU 5L3 5L3
SEE NOTE 6
GND
LUG
1OL 400/3/50
460/3/60
575/3/60
1M1 1M2
1OL 200/3/60
11L1 11L3 230/3/60
~ 460V ~
(1L1)
~ ~ 1T1 1T2 1T3 1T4 1T5 1T6
(1L2)
1 2 3 7 8 9
1-MTR
COMPRESSOR MOTOR
SEE NOTE 5
(1L1)
(1L1)
(1L2) (1L2)
5L1
5L2
5L3
A B C
UVR
~
~
~
1CO
LEGEND 5L1
~ ~ ~
5L2
NOTES CB CIRCUIT BREAKER
1- FUSES SHALL BE TIME DELAY TYPE. C SHORTING CONTACTOR 5L3
2- ALL FIELD WIRING SHALL COMPLY WITH LOCAL, CO CONVENIENCE OUTLET
COMP COMPRESSOR
STATE, AND NATIONAL CODES. CPR CAPACITOR
3- USE COPPER CONDUCTORS ONLY. CONTROL CT CURRENT TRANSFORMER
WIRING 14AWG. FM FAN MOTOR
FU FUSE
4- BRANCH CIRCUIT PROTECTION SHALL BE PROVIDED GND GROUND
BY INSTALLER. DISCONNECT MEANS ALSO REQUIRED M CONTACTOR
MTR MOTOR
UNLESS CIRCUIT BREAKER OPTION IS FURNISHED.
OL OVERLOAD
5- IF POWER SUPPLY HAS BEEN INTERRUPTED FOR S SWITCH FAN MOTORS
A PROLONGED PERIOD, OIL SUMP HEATERS MUST SCR SPEED CONTROL
SOL SOLENOID
BE ENERGIZED FOR 24 HOURS MINIMUM BEFORE T TRANSFORMER 5L1
~ ~ ~
019322AB
FAN MOTORS
70
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
3
S1(CONTROL POWER)
4
5
7 8 1M1-2
6 J7 COMP 1 LIQ INJECTION
SOL.
7
1 2 5 6
8
12 7
9
10
RIBBON CABLE
DIGITAL J1
TO MICROCOMPUTER
11 I/O BOARD
12VAC (1DI/OB)
12
1M1-1 9 1M2-2 10
13 1DI COMP SWITCH AUXILIARY
1H 1N
14
26
27
28
33 4CP 30
4C 4NO 2CR
ALARM OUTPUT (60)
34 8
35 31
3CR CONTROL POWER/SCHEDULE
(24, 55)
36
FAN COMPACT STD EXT.
CONTROL
37 32 STAGE OPT. OPT.
2M
STAGE FAN FAN FAN
38 1 1&2 1&2 1&2
39 33
3M
STAGE FAN FAN FAN
40 2 3&4 3&4 3&4
41
34 4M
42 STAGE -- FAN FAN
3 5&6 5&6
43
44
45
46
47
48 35 5M
STAGE FAN
-- --
49 4 7&8
SEE NOTE 13
2
50 36
HOT GAS BYPASS
51 11
52 12VAC
53 12
54
55
56
57
SEE NOTE 10
58
59
60
019331AC
61
71
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
CONTROL
(-) 107 105 (-) POWER ALARM
7 2 30 2
1LT 2LT
SH SH W R
#1 MTR
OVERLOAD
16 19
R
36 5SOL 2
SET POINTS
NAME A B
1 LV WTR SP. TLW °F
2 LEAD 0.0
3 RAMP UP 0.2 30.0
4 AMP LIMIT (UNLOAD) (HOLD)
5 PWR LOSS
6 HI/LO PRESSURE 360 PSIG SEE TABLE
SEE TABLE GND
7 FREEZE
8 HOT GAS BYPASS
9 LO AMB
10 SUCTION LIMIT SEE TABLE SEE TABLE
11 DISCHARGE LIMIT 355 PSIG 345 PSIG
12 FAN STAGE 1 230 PSIG 100 PSIG
13 FAN STAGE 2 240 PSIG 140 PSIG
14 FAN STAGE 3 250 PSIG 160 PSIG
15 FAN STAGE 4 260 PSIG 170 PSIG
16 DMND LMT/CWR 0.0 0.0
10 2
4CR
NOTES
1- FUSES SHALL BE TIME DELAY TYPE.
2- ALL FIELD WIRING SHALL COMPLY WITH LOCAL, STATE
AND NATIONAL CODES.
3- USE COPPER CONDUCTORS ONLY. CONTROL WIRING 14AWG WITH MAX.
15A OVERCURRENT PROTECTION. USE TERMINALS 2 AND 102 FOR
NEUTRAL CONNECTIONS.
4- DISCONNECT MEANS AND BRANCH CIRCUIT PROTECTION
SHALL BE PROVIDED BY INSTALLER IF NOT SUPPLIED.
5- IF POWER SUPPLY HAS BEEN INTERRUPTED FOR A
PROLONGED PERIOD, OIL SUMP HEATERS MUST BE ENERGIZED
FOR 24 HOURS MINIMUM BEFORE STARTING COMPRESSORS.
6- TO RESET OVERLOAD TURN COMPRESSOR SWITCH OFF FOR 5 SECONDS.
7- CUSTOMER CONTROL CONTACTS MUST BE WIRED BETWEEN
TERMINALS 8&13.
8- IF 0-5 VDC CWR IS USED, SET SETPOINT 16B TO RESET DESIRED
AT +5VDC INPUT. CAUTION: DO NOT SUPPLY OVER 5.0VDC TO 6AI.
9- SHIELDED CABLE IS RECOMMENDED FOR CUSTOMER SUPPLIED
CONTACT WIRING. GROUND ON SUBPANEL.
10- CONTACT RATING IS 10A AT 125 VAC AND 5A AT 250 VAC (1/2 HP).
72
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
019352AB
73
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
19FU 20FU
FURNISHED 10A 10A
NOT FURNISHED 120 V
CONNECTION
11T
L1
L2
L3
AMMETER
TRANSFER SWITCH
VOLTMETER A B C
TRANSFER SWITCH
11 12 13 14
UVR
21 22 23 24
VM
7FU
9L1
~
L1
8FU
9L2
~
L2
9FU
~
9L3 REMOVE J9
L3
L2
1FU 2FU 4FU 5FU 16FU 17FU
11L1 11L2 12L1 12L2 7L1 7L2 10FU 11FU
.75A .75A
1T 3T 8T 8L1 8L2
L1
L2 9T
1B 94 101B
74
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
115VAC - CUSTOMER SUPPLIED AUDX-NOT SUPPLIED SEE POWER DIAGRAM FOR TRANSFORMER
5TB SEE POWER DIAGRAM FOR CHILLER HTR TRANSFORMER OPTION. OPTION. SEE NOTES 2, 3 AND 4.
102
GND SEE NOTES 2, 3, & 4
101
5 HTR CHILLER HTR 115VAC
1 NOTE: (3) HEATER TAPES GND 1 2 3TB
2
1
3
1M2-1 3
4 400W COMP 1 OIL SUMP HTR
2 HTR
2M2-1 4 400W
5 3 HTR COMP 2 OIL SUMP HTR
S1 3M2-1 5
6 400W COMP 3 OIL SUMP HTR
4 HTR
CONTROL
7 POWER
8
10 1M1-2 11 8TAS-1 12 1SOL
9 J9 COMP 1 LIQ INJECTION SOL
9
10 115VAC
2M1-2 13 8TAS-2 14 2SOL
1 2 5 6
COMP 2 LIQ INJECTION SOL
11 2T
7 12
12 12VAC 3M1-2 15 8TAS-3 16 3SOL
18 19 COMP 3 LIQ INJECTION SOL
13 12FU 4A 13FU
14
15 DIGITAL
I/O BOARD
12VAC (D I/O B) RIBBON CABLE
16
20 21 TO MCB
1M1-1 1M2-2 TO MICROCOMPUTER 25
22 1H 1N
17 1DI COMP 1CTR AUX.
2M1-1 2M2-2 26 2H 2N
23
18 2DI COMP 2CTR AUX.
3M1-1 3M2-2 27 3H 3N
24
3DI COMP 3CTR AUX.
19
20RES
20 1.5A BLK
1FS 28 4H 4N
WHT
31FU 4DI COMP 1 OIL FLOAT SWITCH
21 YEL
22
1.5A
WHT 2FS BLK 21RES 29 5H 5N
23
32FU 5DI COMP 2 OIL FLOAT SWITCH
YEL
22RES
24 1.5A BLK
WHT 3FS 30 6H 6N
33FU 6DI COMP 3 OIL FLOAT SWITCH
25 YEL
1CPR
26 10 CWP * 31 CWFS 32 7H 7N
7DI WATER FLOW SWITCH
2CPR
27 33 NOTES 7 & 8 8H 8N
* UNIT CONTROL
8DI
28 10
115VAC
29 14T
1SN
41 1C 1CP 1NO 42
30 3CR 24VAC 1M1 COMP 1 CTR 1ST WINDING
J42 (9,17)
39 40 COMP 1 43
31 35 OVERLOAD 1M2 COMP 1 CTR 2ND WINDING
1OL (4, 17)
S2 38 3 1
32 NOTE 6 10TR-1 4SOL COMP 1 LIQUID
LINE SOL.
COMP 1PB
51 AUDX-FIELD WIRED
33 #1
99
T2 M1 M2 B 2SN
TO 25 2C 2CP 2NO 48
34 2AIB 5SOL
T1 COMP 1 LOAD SOLENOID
G 105
35 S1 S2 S3 C 3SN
3C 3CP 3NO 49
44 6SOL
45 46 47 BLK COMP 1 UNLOAD SOLENOID
36
37
4SN
4C 4CP 4NO 54
38 2M1 COMP 2 CTR 1ST WINDING
MOTOR TEMP J54 55 (11,18)
39 53 2M2
SENSORS COMP 2 CTR 2ND WINDING
3 1 (5, 18)
40 10TR-2
COMP 2 7SOL COMP 2 LIQUID
41 OVERLOAD LINE SOL.
2OL AUDX-FIELD WIRED
S3 50 NOTE 6
42 5SN
COMP 2PB 26 5C 5CP 5NO 60
52 100 8SOL
#2 COMP 2 LOAD SOLENOID
43
T2 M1 M2 B
TO 6SN
2AIB 6C 6CP 6NO 61
44 T1 9SOL
COMP 2 UNLOAD SOLENOID
G 105
45 S1 S2 S3 C
56 57 58 59 BLK
46
47
MOTOR TEMP
SENSORS
019338C1
75
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
2
(DI/OB)
48 7SN
64 7C 7CP 7NO 65 3M1 COMP 3 CTR 1ST WINDING
49
J65 66 (12,19)
3M2
50 COMP 3 CTR 2ND WINDING
3 1 (5, 19)
51 COMP 3 10TR-3
10SOL COMP 3 LIQUID
OVERLOAD LINE SOL.
3OL AUDX-FIELD WIRED
52 S4 62 NOTE 6
8SN
53 COMP 3PB 27 8C 8CP 8NO 71
167 11SOL
#3 COMP 3 LOAD SOLENOID
63 T2 M1 M2 B
54 TO 9SN
2AIB 9C 9CP 9NO 72
T1 12SOL
COMP 3 UNLOAD SOLENOID
55 G 105
S1 S2 S3 C
67 68 69 70 BLK
56
57 10SN
10 10C 10CP 10NO 74 2CR
ALARM OUTPUT
58 (58)
MOTOR TEMP 11C 11CP 11NO 75 3CR
CONTROL POWER
59 SENSORS (30, 71)
11SN
60 4TB
+12VDC 90
61
GND 92
62
SH
63
12SN
64 12C 12CP 12NO
65
13SN
66 13C 13CP 13NO
67
14SN
68 14C 14CP 14NO
69
15SN
70 15C 15CP 15NO
71
16SN
72 151 3CR 152 16C 16CP 16NO
73 CHILLED
RIBBON
WATER CABLE
74 PUMP
CONTACTS DIGITAL
75 OUTPUT BOARD #2
(2D0B) 17SN
76 1C 17CP 1NO
77
18SN
153 2CR 154 18CP
78 2C 2NO
79 ALARM
CONTACT 19SN
80 3C 19CP 3NO
81
20SN
82 4C 20CP 4NO
83
21SN
84 5C 21CP 5NO
85
EXTENDED 22SN
86 FAN MOTOR OPTION 6C 22CP 6NO
ONLY
87 JUMPER ON GND
ADDRESS #3
019338C2
76
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
88 RIBBON CABLE
TO DIGITAL I/O BOARDS
89
90
RIBBON CABLE
91
111
112
RIBBON
CABLE
113
114 AI BOARD #2
(2AIB)
115
(+) 104
116 AI12 99
(#4) AI9
CHILLED (#1)
117 WATER 0-5 VDC TO 1OL
4ZD 105
RESET GND
(-) 105
118
GND
SEE NOTE 10
119 SH 100
AI10
120 (#2)
TO 2OL
105
121 GND
(+) 106
AI13
122 (#5)
DEMAND 167
LIMIT 0-5 VDC AI11
123 5ZD
(-) 105 (#3) TO 3OL
105
124 SEE NOTE 12 GND GND
SH
125
JUMPER ON
ADDRESS #2
019338C3
77
4.0 OPERATION - MICROCOMPUTER CONTROL (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
126
CB CIRCUIT BREAKER
COMP COMPRESSOR
153 CP CONTROL POINT
CPR CAPACITOR
6MTR CR CONTROL RELAY
154 CT CURRENT TRANSFORMER
4MTR 5MTR CTR CONTACTOR
CWFS CHILLED WATER FLOW SWITCH
155 COMP #3 CWP CHILLED WATER PUMP
TX VALVE CWR CHILLED WATER RESET
COMP #1 COMP #2 DI DIGITAL INPUT
156 TX VALVE TX VALVE FS FLOAT SWITCH
HOT GAS BYPASS OPTION FU FUSE
GF GROUND FAULT
157 (ALL CIRCUITS) TO MCB GND GROUND
H0T GAS BYPASS OPTION (J2) H-O-T HIGH OIL TEMP
FURNISHED HMT HIGH MOTOR TEMP
(1 CIRCUIT) RIBBON HTR HEATER
158 TO MCB NOT FURNISHED
FURNISHED CABLE I/O INPUT/OUTPUT
(J2) LS LEVEL SENSOR
NOT FURNISHED LT
159 RIBBON DIGITAL M
LIGHT
CONTACTOR
2
CABLE OUTPUT BOARD #3 MCS MOLDED CASE SWITCH
160 MOV METAL OXIDE VARISTOR
(3DOB) MTR MOTOR
23SN NC NORMALLY CLOSED
DIGITAL NO NORMALLY OPEN
161 OUTPUT BOARD #3
10 3C 25CP 3NO 148 13SOL OL OVERLOAD
CIRCUIT #1 PB PUSH BUTTON
(3DOB)
162 23SN
PT PRESSURE TRANSDUCER
RES RESISTOR
10 3C 25CP 3NO 148 13SOL 2 24SN RLY RELAY
163 4C 26CP 4NO 149 14SOL SC STARTS COUNTER
CIRCUIT #2 SH SHIELD
SN SNUBBER
164 SOL SOLENOID
TAS THERMOSTAT
25SN TB TERMINAL BLOCK
165 20 5C 27CP 5NO 150 15SOL TLW TEMP LEAVING WATER
12VAC CIRCUIT #3 TR TIMER
GND TS TEMP. SENSOR
166 21 UVR UNDERVOLTAGE RELAY
20 VI VAPOR INJECTION
12VAC VM VOLTMETER
167 GND ZD ZENOR DIODE
JUMPER ON
21 MANUAL RESET
ADDRESS #4
JUMPER ON FACTORY TERMINAL
168
ADDRESS #4 FIELD WIRING
* FIELD SUPPLIED
169
NOTES SET POINT TABLE
170 SET POINTS
1- FUSES TO BE TIME DELAY TYPE. A B % MIN. MIN. MIN. SUCTION
2- ALL FIELD WIRING SHALL COMPLY WITH LOCAL, STATE AND NATIONAL CODES. 1 LV. WTR. SP. TLW F ETHYLENE LOW P. TLW FREEZE LIMIT
171 3- USE COPPER CONDUCTORS ONLY. CONTROL WIRING 14AWG. WITH MAX. GLYCOL [8B] [1A] [9B] [18A] [18B]
2 LEAD 0.0
15A OVERCURRENT PROTECTION, USE TERMINALS 2 AND 102 FOR (PSIG) (°F) (°F) (PSIG) (PSIG)
3 RAMP UP 0.2 30 %
NEUTRAL CONNECTIONS.
172 4- DISCONNECT MEANS AND BRANCH CIRCUIT PROTECTION SHALL BE PROVIDED 4 AMP LIMIT 1 (UNLOAD) (HOLD) 0 58 42 38 60 62
BY INSTALLER 5 AMP LIMIT 2 (UNLOAD) (HOLD) 10 52 37 24 54 56
5- I F POWER SUPPLY HAS BEEN INTERRUPTED FOR A PROLONGED PERIOD, 6 AMP LIMIT 3 (UNLOAD) (HOLD) 20 41 28 24 43 45
173 OIL SUMP HEATERS MUST BE ENERGIZED 24 HOURS MINIMUM BEFORE 7 PWR LOSS 0.0 30-60 30 20 9 32 34
STARTING COMPRESSORS. 8 HI/LO PRESS 360PSIG SEE TABLE
6- TO RESET OVERLOAD, PRESS CORRESPONDING PUSH BUTTON. 9 FREEZE SEE TABLE % MIN. MIN. MIN. SUCTION
174 10 FAN STAGE 1 230PSIG 100 PSIG PROPYLENE LOW P. TLW FREEZE LIMIT
7 CUSTOMER CONTROL CONTACTS MUST BE WIRED
11 FAN STAGE 2 240PSIG 140 PSIG GLYCOL [8B] [1A] [9B] [18A] [18B]
BETWEEN TERMINALS 10 AND 33.
12 FAN STAGE 3 250PSIG 160 PSIG (PSIG) (°F) (°F) (PSIG) (PSIG)
175 8- SHIELDED CABLE IS RECOMMENDED FOR FLOW SWITCH AND CUSTOMER CONTROL 13 FAN STAGE 4 260PSIG 170 PSIG 0 58 42 38 60 62
FIELD WIRING. 14 H G BYPASS 80% 45%
9- CONTACT RATING IS 10A AT 125VAC AND 5A AT 250VAC (1/2HP). 10 51 37 32 53 55
176 15 DISCHARGE LIMIT 355PSIG 345PSIG 20 43 29 25 45 47
10- IF 0-5 VDC CWR IS USED, SET SETPOINT 16B TO RESET DESIRED AT +5VDC INPUT. 16 LO AMB 20.0°F SEE NOTE 11 30-60 32 20 14 34 36
CAUTION: DO NOT SUPPLY OVER 5.0 VDC TO AI10. 17 DMND LMT/CWR 0.0 0.0
177 11- LOW AMBIENT SETPOINT 16A CAN BE SET TO A MINIMUM OF 0°F (-17°C) IF 18 SUCTION LIMIT SEE TABLE SEE TABLE
LOW AMBIENT OPTION IS SUPPLIED, OR -20°F (-29°C) IF BOTH LOW AMBIENT 10TR-1,2 1 SEC. WARNING
AND ELECTRONIC TX VALVE OPTIONS ARE SUPPLIED. ANTIRECYCLE 15 MIN.
178 CHECK SETPOINTS BEFORE STARTING UNIT.
LIMIT AT +5 VDC INPUT. THERE IS NO DEMAND LIMITING AT 0 VDC INPUT. OPEN CLOSE DO NOT SET THE SETPOINTS IN THE TABLE
CAUTION: DO NOT SUPPLY OVER 5.0 VDC TO AI11. 8TAS-1, 2, 3 165°F 175°F TO A VALUE LOWER THAN THAT INDICATED
179 12- IF 0-5 VDC DEMAND LIMIT IS USED, SET SETPOINT 17A TO THE DESIRED DEMAND FOR YOUR GLYCOL CONCENTRATION. TO
DO SO WILL VOID THE WARRANTY.
180
019338C4
78
5.0 MAINTENANCE ACDX-B/AUDX-B ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
79
5.0 MAINTENANCE ACDX-B/AUDX-B (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
80
5.0 MAINTENANCE ACDX-B/AUDX-B (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Page 1 of 2
81
5.0 MAINTENANCE ACDX-B/AUDX-B (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Page 2 of 2
COMPR.
NO.
1
SUCTION PRESSURE 2
DISCHARGE PRESSURE 2
DISCHARGE TEMPERATURE 2
SUCTION TEMPERATURE 2
DISCHARGE SUPERHEAT 2
(DISCH. TEMP. — SAT. DISCH.)*
3
SUCTION SUPERHEAT 2
(SUCT. TEMP. — SAT. SUCT.)*
3
COMPRESSOR AMPS 2
82
5.0 MAINTENANCE ACDX-B/AUDX-B (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
YES NO
Unit Model No.
Setting Unit: a. Vibration isolator used
b. Spring isolator adjusted for equal height
c. If rubber-in-shear isolators are used, is unit leveled by
shimming
Before Start-Up:
a. Open compressor discharge service valve (if supplied)
b. Open liquid valve(s)
c. Open suction, and discharge valves to pressure gauges
(if supplied)
d. Check rotation of all fan motors
e. Start auxiliary equipment (pumps, fans, etc.)
f. Is crankcase heater operating? Operate 24 hours prior to
unit start-up.
g. Check the compressor oil level through the crankcase sight
glass. The oil level should be 1/2 of the glass. If the level
is low, add oil in accordance with the directions in the
maintenance instructions
h. Check all control settings as specified on unit wiring diagram
i. Air purged from chilled water system
83
5.0 MAINTENANCE ACDX-B/AUDX-B (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
PRES TEMP PRES TEMP PRES TEMP PRES TEMP PRES TEMP PRES TEMP
0 -41.4 55 30.1 110 64.4 165 88.6 220 108.0 276 124.5
1 -38.8 56 30.9 111 64.9 166 89.0 221 108.3 278 125.1
2 -36.4 57 31.7 112 65.4 167 89.4 222 108.6 280 125.6
3 -34.1 58 32.4 113 65.9 168 89.8 223 109.0 282 126.1
4 -31.8 59 33.2 114 66.4 169 90.2 224 109.3 284 126.7
5 -29.7 60 33.9 115 66.9 170 90.6 225 109.6 286 127.2
6 -27.7 61 34.7 116 67.4 171 91.0 226 109.9 288 127.7
7 -25.7 62 35.4 117 67.9 172 91.3 227 110.2 290 128.3
8 -23.8 63 36.1 118 68.3 173 91.7 228 110.5 292 128.8
9 -22.0 64 36.9 119 68.8 174 92.1 229 110.8 294 129.3
10 -20.2 65 37.6 120 69.3 175 92.5 230 111.2 296 129.8
11 -18.5 66 38.3 121 69.8 176 92.8 231 111.5 298 130.3
12 -16.9 67 39.0 122 70.2 177 93.2 232 111.8 300 130.9
13 -15.3 68 39.7 123 70.7 178 93.6 233 112.1 302 131.4
14 -13.7 69 40.4 124 71.2 179 93.9 234 112.4 304 131.9
15 -12.2 70 41.0 125 71.7 180 94.3 235 112.7 306 132.4
16 -10.7 71 41.7 126 72.1 181 94.7 236 113.0 308 132.9
17 -9.2 72 42.4 127 72.6 182 95.0 237 113.3 310 133.4
18 -7.8 73 43.0 128 73.0 183 95.4 238 113.6 312 133.9
19 -6.4 74 43.7 129 73.5 184 95.8 239 113.9 314 134.4
20 -5.1 75 44.3 130 74.0 185 96.1 240 114.2 316 134.9
21 -3.8 76 45.0 131 74.4 186 96.5 241 114.5 318 135.4
22 -2.5 77 45.6 132 74.9 187 96.9 242 114.8 320 135.9
23 -1.2 78 46.3 133 75.3 188 97.2 243 115.1 322 136.4
24 0.0 79 46.9 134 75.8 189 97.6 244 115.4 324 136.8
25 1.2 80 47.5 135 76.2 190 97.9 245 115.7 326 137.3
26 2.4 81 48.1 136 76.6 191 98.3 246 116.0 328 137.8
27 3.6 82 48.7 137 77.1 192 98.6 247 116.3 330 138.3
28 4.8 83 49.4 138 77.5 193 99.0 248 116.6 332 138.8
29 5.9 84 50.0 139 78.0 194 99.3 249 116.9 334 139.2
30 7.0 85 50.6 140 78.4 195 99.7 250 117.2 336 139.7
31 8.1 86 51.2 141 78.8 196 100.0 251 117.5 338 140.2
32 9.2 87 51.7 142 79.3 197 100.4 252 117.8 340 140.7
33 10.2 88 52.3 143 79.7 198 100.7 253 118.1 342 141.1
34 11.3 89 52.9 144 80.1 199 101.1 254 118.3 344 141.6
35 12.3 90 53.5 145 80.5 200 101.4 255 118.6 346 142.1
36 13.3 91 54.1 146 81.0 201 101.7 256 118.9 348 142.5
37 14.3 92 54.6 147 81.4 202 102.1 257 119.2 350 143.0
38 15.3 93 55.2 148 81.8 203 102.4 258 119.5 352 143.4
39 16.2 94 55.8 149 82.2 204 102.8 259 119.8 354 143.9
40 17.2 95 56.3 150 82.6 205 103.1 260 120.1 356 144.3
41 18.1 96 56.9 151 83.0 206 103.4 261 120.3 358 144.8
42 19.1 97 57.5 152 83.4 207 103.8 262 120.6 360 145.2
43 20.0 98 58.0 153 83.9 208 104.1 263 120.9 362 143.7
44 20.9 99 58.6 154 84.3 209 104.4 264 121.2 364 146.1
45 21.8 100 59.1 155 84.7 210 104.8 265 121.5 366 146.6
46 22.6 101 59.7 156 85.1 211 105.1 266 121.8 368 147.0
47 23.5 102 60.3 157 85.5 212 105.4 267 122.0 370 147.5
48 24.4 103 90.8 158 85.9 213 105.7 268 122.3 372 147.9
49 25.2 104 61.3 159 86.3 214 106.1 269 122.6 374 148.3
50 26.1 105 61.8 160 86.7 215 106.4 270 122.9 376 148.8
51 26.9 106 62.4 161 87.1 216 106.7 271 123.1 378 149.2
52 27.7 107 62.9 162 87.5 217 107.0 272 123.4 380 149.6
53 28.5 108 63.4 163 87.9 218 107.4 273 123.7
54 29.3 109 63.9 164 88.3 219 107.7 274 124.0
84
5.0 MAINTENANCE ACDX-B/AUDX-B (CONT.) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
5.11 Notes
85
101 Burgess Road, Harrisonburg, VA 22801
Phone: (540) 434-0711 FAX (540) 432-6690
January 2000 www.dunham-bush.com Form No. 6122B