Professional Documents
Culture Documents
Spring 2019-2020
Solar PV Systems Lab
Experiment 5
Characterizations of PV Operating
Outdoor
Students’ Names ID’s#
Sara Rami U17100214
Aryam Raafat U17104443
Shatha T. A. Thabet U1520309
Khadija Abdulla U15102721
1
Conclusion Page 12
References Page 12
Figure 1 Apparent daily path of the sun across the sky from sunrise
to sunset.
Figure 2 EoT over all the days of a year
Figure 3 Beam (direct) and diffuse irradiance in Abu dhabi on 22nd
Feb
Table 1 Parameters for Sharjah
Table 2 Horizontal irradiance and reference irradiance
Table 3 Tilt angle conditions
Table 4 STC parameters
Introduction:
2
Figure 1: Apparent daily path of the sun across
the sky from sunrise to sunset.
EoT=9.87sin(2B)−7.53cos(B)−1.5sin(B)EoT
Where :-
B=360365(d−81)B=360365(d−81)
in degrees and d is the number of days since the start of the year. The time correction EoT is
plotted in the figure below.
3
Figure 2: EoT over all the days of a year
⋀
LST =UTC +1 h∙
15°
4
The Hour Angle converts the local solar time (LST) into the number of degrees which the sun
moves across the sky. The Hour Angle is 0° at solar noon. Since the Earth rotates 15° per hour,
each hour away from solar noon corresponds to an angular motion of the sun in the sky of 15°. In
the morning the hour angle is negative, in the afternoon the hour angle is positive.
Objectives:
1- Learn to apply the concept of solar altitude and the azimuth angle, using outdoor Profitest
system.
2- Calculate the angle of incidence for different cases.
3- Calculate the Local Solar Time, and the performance of the PV.
Equipment:
PV panels
Cables
Profitest system
Reference cell
Thermal couple sensor
PC
Angle meter app
Procedure:
5
received by the panel). Using LST read the reference irradiance, find the beam, diffuse
and global irradiance.
4- Measure the performance of your tilt PV panel.
5- Repeat measurement for two different β (angle meter app can be used to measure the
° °
angle). If possible, one of the β should satisfy θ=90 −( β+ γ s )=0 . Complete table 3.
6- Record the STC parameter and temperature coefficients from the nameplate of the panel
(usually on the panel backside) .
Calculations:
360 360
B= × ( d−81 ) = × ( 56−81 )=−24.72
364 364
ET = 9.87 sin (2 B¿)−7.53 cos ( B )−1.5 sin ( B )=¿ ¿
9.87 sin (2(−24.72)¿ )−7.53cos (−24.72 )−1.5 sin (−24.72 )=¿−13.7 minutes ¿¿
UAE is in the GMT +4 time-zone, 11:00 am
UTC = LT – time-zone = 11 – 4 = 7 hours
Λ 55.4 −13.7
LST = UTC + + ET(in hours) = 7 + + =10.46 hours = 10:28
15 15 60
ω=( LST −12 h ) × 15° =( 10.46−12 ) ×15=−23.1 °
sinγ=sinφ∙ sinδ + cosφ ∙ cosδ ∙ cosω
¿ sin ( 25.5 ) sin (−9.78 ) +cos ( 25.5 ) cos (−9.78 ) cos (−23.1 )=0.74
−1
γ=sin ( 0.74 )=48.16 °
6
cosδ ∙ sinω cos (−9.78 ) sin (−23.1)
sinα= = =−0.58
cosγ cos (48.16)
−1
α =sin (−0.58 )=−35.42 °
Experimental Data:
Parameters for Sharjah on February 25th, 2019 at 11:00
am
Latitude 𝜑 25.5 ˚N
Longitude 𝛬 55.4˚E
Day number d 56
Solar declination 𝛿 -9.78˚
ET (in minutes) -13.7
Local Solar Time LST 10:28 / 10.46 hours
Hour angle 𝜔 -23.1˚
Solar altitude 𝛾𝑆 48.16˚
Solar azimuth 𝛼𝑆 -35.42˚
Table 1: Parameters for Sharjah
10.46
7
Beam irradiance (W/m2) 880
Diffuse irradiance (W/m2) 110
Global irradiance (beam+diffuse) 974 990
(W/m2)
Error = A1global – A2global (W/m2) 974-990 = -16
B=37
1 B=17
0.8 B=52
0.6
0.4
0.2 8
0
0 5 10 15 20 25
Volatge (V)
P-V Curves for Different B
30
25
20
Power (W)
B=37
15 B=17
B=52
10
0
0 5 10 15 20 25
Volatge (V)
Question #3:
Using Table 3, plot irradiance sensor reading (W/m2) vs. cos𝜃 and perform linear curve
fitting (since 𝐸𝑑𝑖𝑟𝑒𝑐𝑡_𝑔𝑒𝑛 = 𝐸𝑑𝑖𝑟𝑒𝑐𝑡_𝑣𝑒𝑟𝑡𝑖𝑐𝑎𝑙 ∙cos𝜃 if we ignore diffuse irradiance). Is your
result a good fit to a linear curve?
Irradinace vs cos Ɵ
1060
1040 1036
Irradinace (W/m^2)
980
974
960
940
0.9 0.92 0.94 0.96 0.98 1 1.02
9 CosƟ
Yes, the result is a good fit to a linear curve
Question #4:
For 𝛽 = 0°, calculate the module temperature from NOCT in Table 4, and compare to the
temperature sensor reading in Table 3.
NOCT =45 ˚ C
NOCT −20 45−20
Tpv=Tamb+ × E=24 + ×974=54.43 ˚ C
800 800
Our sensor Temperature was 46.7˚C , error= 14.2%.
Question #5:
For 𝛽 = 0°, using the STC values from Table 4 while applying equations from Experiment
#4, calculate the expected (1) ISC, (2) VOC and (3) Pmax under the recorded temperature
and irradiance (from Table 3).
You must show the detailed calculation with equations for all three parameters
considering both effects of irradiance and temperature.
Compare your calculated results to the actual measurement results.
974
Isc (at 974W/m2, 25˚C) = 3.16 × = 3.077A
1000
∆ I = αI × ∆ T = 0.037% × (54.43-25) = 1.088%
Isc (at 974W/m2, 54.43˚C) = 3.077 + 1.088%*3.077 = 3.11 A
10
974
Pmax(at 974W/m2, 25˚C) ≅ 50 × = 48.7 W
1000
∆ P = αP × ∆ T = -0.48% × (40.8-25) = -14.12%
Pmax (at 974W/m2, 54.43˚C) = 48.7 – 14.12%*48.7 = 41.82 W
974
Voc (at 974W/m2, 25˚C) = Voc(STC) + nVTln( )=
1000
22.2 +36×(0.026)×ln(0.974) = 22.17 V
∆ V = αV × ∆ T = -0.34% × (54.43-25) = -10%
Voc (at 974W/m2, 54.43˚C) = 22.17 – 10%*22.17 = 19.95 V
Actual values:
Voc= 19.73 V
Error= 1.11%
Isc= 1.77 A
Error= 75.7%
Pmax= 24.82 W
Error= 68.49%
Discussion:
• This experiment was done by operating PV panel outdoor by applying the concepts of
solar angles altitude and azimuth using the outdoor profit-test system.
• To apply the concepts, we must theoretically solve to find the tilt angle by using the
solar angles to get the solar declination, Local Solar Hours and Hour angle.
• According to our data observation 𝛽 max = 37° which has the highest irradiance.
• The maximum irradiance power max = 1036 W/m^2 , at 𝛽 max = 37° according to
our process.
• After finding the tilt angle which has the optimum irradiance, we started operating PV
panel outdoor positioned at three different tilt conditions.
• Then we found the beam irradiance, diffuse irradiance and global irradiance for a
certain reference (Abu Dhabi).
• By using the tilt condition, we found the angle of incidence and finally recorded the
STC parameters and temperature coefficients.
Sources of Error:
11
• PV panel not positioned in the correct direction.
• By shading the PV panel like student passing in front of PV, while data being
recorded.
• Using bricks to hold the module instead of a practical stand which caused shaking and
instability during capturing the sun irradiance .
• The humidity and weather conditions.
• The dissimulation of profit system with the PV panel.
Conclusion:
In conclusion, the aim of this experiment has been successfully achieved by applying the
concepts of solar altitude and azimuth angles practically using the outdoor profitest system so we
understood the significance of the altitude angle and azimuth angle to get the best tilt angle as
well as the best angle of incidence. Moreover, the angle of incidence has been calculated and the
performance of PV panel has been studied.
References:
12