Professional Documents
Culture Documents
Use this guide to help you decide what points to trend in your building automation system (BAS). If your
BAS has limited capabilities, you may not be able to trend all the recommended points. If that is the
case, just trend as many as you can.
Occupancy Scheduling
Potential Issues to Identify
• No night setback for heating or cooling
• No weekend setback for heating or cooling
• Excessive supply fan cycling (indicates that night and/or weekend setback temperatures are too
close to normal operating setpoints).
Points to Trend
For each monitored air handler, plot supply fan status vs. time. Status should change to Off during
unoccupied times. Add zone temperature to the graph. You could also trend data for support systems
such as pumps, chillers, and boilers.
1
Discharge Air Temperature Control
Points to Trend
For each air handler monitored, review plots of discharge air temperature and discharge air setpoint vs.
time and supply air temperature vs. supply air setpoint. On the same trend graph, plot the reheat
valves. You may also want to plot chilled water valves.
Trended data for discharge temperature reset control that is working should show temperature
setpoints that vary as the building wakes up in the morning, change as the building becomes occupied,
and continue to change during the late morning and early afternoon hours. Changing outdoor ambient
temperatures and solar loading will also cause temperature setpoints to change. This can vary as much
as 10-15°F over the course of the day.
2
Discharge Static Control
Potential Issues to Identify
Look for situations where:
• Most dampers are nearly closed during cooling (static pressure too high)
• Several VAV boxes on an air handler have dampers fully open (static pressure is too low and VAV
boxes are not able to meet zone loads)
• Dampers are not modulating as conditions change (VAV boxes are not being controlled or are
not responding to control signals).
Points to Trend
For each air handler, review a plot of the damper positions of all VAV units vs. time. Also plot discharge
static pressure and discharge static pressure setpoint vs. time. Next plot fan speed vs. time.
If the static pressure control is constant, then the fan speed (load) should vary.
3
Air Handler Heating & Cooling
Potential Issues to Identify
• Unoccupied or 24/7 operation
• Unoccupied hour setback
• Lower or higher than expected discharge air temperature
• Excessive outdoor air intake during occupied periods and during pre-heating and pre-cooling
periods
• Significant reheat during summer (cooling) season
• Non-modulating fan (if VAV)
• Higher than normal static pressure
• Setpoint and static pressure resets
• Simultaneous heating and cooling
• Reversed heating and cooling lockouts
• Economizer not used or not working properly.
Points to Trend
• Outdoor, mixed, and return air temperatures vs. time
• Discharge air temperature and discharge air temperature setpoint vs. time
• Discharge static pressure and setpoint vs. time
• Mixed air damper position vs. time
• Fan status and fan speed vs. time
• Cooling coil and heating coil valve positions vs. time
• Heating and cooling setpoints vs. time
• Chilled water and hot water valve positions vs. time
• Occupancy mode vs. time
• Any cubic feet per minute (CFM) device that is part of the air handler control.
4
Air Handler Economizer
Potential Issues to Identify
Your goal is to identify incorrect economizer operation. There are numerous causes of incorrect
operation that you will verify or identify during the building walkdown. Some of these are:
• Incorrect control strategy
• Stuck dampers
• Disconnected or damaged linkages
• Failed actuator
• Disconnected wires
• Failed, uncalibrated, or miscalibrated sensors
• 2 x 4 or other object jammed in damper.
Points to Trend
For each air-side economizer, review plots of:
• Outdoor air temperature, mixed air temperature, return air temperature, and discharge air
temperature vs. time
• Outdoor air damper position (percent open), outdoor air temperature, and return air
temperature vs. time
• Outdoor air damper position and chilled water valve position (percent open) vs. time.
Look for outdoor air dampers not open to economizer under favorable conditions (outdoor air
temperature between 40°F and 60°F).
Look for outdoor air damper not closing to minimum position for freeze prevention when outdoor
temperature is less than 40°F or so.
5
Zone Conditioning
Potential Issues to Identify
• No night setback
• Significant reheat for interior zone terminal unit during occupied hours
• Overcooling or overheating
• Significant reheat during summer (cooling) season for exterior zone unit
• Supply air temperature too cool or too warm
• No use of supply air reset
• Certain zones (e.g., corner offices) driving air handler operation
• Some zones out of control, oscillating between heating and cooling.
Points to Trend
Trend as many as possible from the following list:
• Zone air temperature and setpoint
• VAV damper position
• Reheat valve position (if supply air is reheated at the zone)
• Recool valve position (if supply air is recooled at the zone)
• Zone occupancy mode
• Zone CFM and CFM setpoint
• Zone discharge air temperature
• Fan status or fan command (for fan-powered units only).