You are on page 1of 5

Licensed copy: leedsm, LEEDS BECKETT UNIVERSITY, 03/11/2017, Uncontrolled Copy, © Concrete Society

A single copy of this

Concrete Society

publication is licensed to

leedsm
on
03/11/2017

This is an uncontrolled copy - not for contract use


LEEDS BECKETT UNIVERSITY

This is an uncontrolled copy. Ensure use of the most current version of this document
by searching the Construction Information Service at http://uk.ihs.com
CONCRETE ADVICE No. 05

Holding down bolts to BS 8110-1


Licensed copy: leedsm, LEEDS BECKETT UNIVERSITY, 03/11/2017, Uncontrolled Copy, © Concrete Society

Deryk Simpson, BSc CEng MICE

This document provides suggested guidance on the design of holding down bolts for
attaching steel or precast concrete stanchions to reinforced or unreinforced concrete
(1)
foundations, using the design procedures in BS 8110-1 . Guidance on the design of
(2) (3)
holding down bolt design to Eurocode 2 is given in a separate Advice 42 . Design
approaches are given for resisting the uplift on the bolts and for the allowable bearing
pressure underneath the stanchion base plate. This document only covers bolts in
tension or compression and does not cover bolts in shear. Proprietary fixings are not
included in this document. The manufacture’s technical literature should be consulted
for the load capacity of proprietary fixings.

factor of 1.6 unless a lower partial load


1 Uplift - bolts in tension factor can be justified by calculation.

There are two possible ways of checking Cone shear stress =


bolts in uplift. The first is applicable to Design uplift load ÷ Surface area of cone
single bolts and pairs of bolts, which are or cones
effectively bonded over their full embedded
length and have small or no anchor plates. The actual ‘cone’ shear stress should be
The second method is applicable if the less than the design shear stress value
(1)
bolts are not effectively bonded over the obtained from Table 3.8 of BS 8110 . The
embedded length but rely on an individual enhancement in design shear stress for
anchor plate for embedment, or when a tension reinforcement is only applicable if
group of bolts is fastened to a relatively top structural reinforcement is present in
large stiff anchor plate embedded in the two directions at right angles. The lower of
concrete. the two percentages should be used for
the As value in Table 3.8. For nominally
METHOD 1 – Effectively bonded bolts reinforced or unreinforced sections use the
design shear stress value for 100As/bvd
Check shear stress values of 0.15% or less from Table 3.8.
The following procedure can be used to
check the depth and number of bolts in If the cone shear stress exceeds the
tension, for fully bonded cast-in bolts and design shear stress then the bolts will
post-drilled and grouted bolts. Assume the need to be deeper and/or more bolts
tension in the bolts is resisted by shear provided.
stress on the surface area of 90°cones of
concrete within the foundation around Note: The Appendix to this Advice sheet
each bolt. The depth of the cone is to be includes a method for calculating the
taken as the depth to the top of the bolt surface area of non-intersecting cones and
anchor plate not the full depth of the bolt. tabulated values for the combined areas of
pairs of intersecting cones for different
The uplift load is to be the factored design depths and spacings of pairs of bolts.
load not the characteristic load. If the uplift
load value results from non-limit-state
design calculations assume a partial load
Page 2 of 4 CONCRETE ADVICE NO. 05

Check bond stress: Cast-in bolts METHOD 2 – Anchor plate pull out
If the shear stress is less than the relevant design
shear stress, the anchorage of the individual bolts This method assumes that the anchor plate
should be checked. The method for calculating the embedded in the concrete tries to pull out of the
Licensed copy: leedsm, LEEDS BECKETT UNIVERSITY, 03/11/2017, Uncontrolled Copy, © Concrete Society

anchorage bond stress around a reinforcement bar concrete by a punching shear failure. The anchor
in BS 8110 can be used, i.e. plate effectively becomes the loaded area for a
punching shear design, which is undertaken in
fb = Fs / ʌîij× D) accordance with Section 3.7.7 in BS 8110-1. If the
plate is large the stiffness of the baseplate may
where need to be checked. The design procedure for
Fs = design force in the bar checking stiffness of stanchion baseplates could be
ij = diameter of the bolt used.
D = depth of the bolt
fb = anchorage bond stress should not exceed fbu For the purposes of design for resistance to uplift
fbu = design ultimate anchorage bond stress. the symbols in BS 8110-1 would have the following
meaning:
The method of calculating fbu is given in 3.12.8.4 in
BS 8110-1. An assessment of the bond uo = perimeter of anchor plate
characteristics of the bolt will need to be made. u = effective punching shear perimeter around
Bolts that are plain round bar with only a limited anchor plate
length of thread at the top should be considered as d = depth to top of anchor plate below the mid-
‘Plain Bars’ for Table 3.26 of BS 8110-1. Bolts that plane of the top reinforcement
are threaded full length can be considered as ‘Type V = maximum design uplift load (i.e. factored
2 Deformed Bars’ in Table 3.26. uplift load)
vc = design concrete shear stress from Table 3.8.
Note: The amount of reinforcement provided
around the bolts has no effect on the anchorage If lightly reinforced or reinforced in one direction
bond stress. only, take 100As/bvd as less than 0.15. If reinforced
If fb exceeds fbu the bolts will need to be deeper in the top in both directions take the lesser value for
and/or more bolts provided. 100 As/bvd.

Check bond stress: Post-grouted bolts Design procedure


In the cases where bolts are grouted into drilled Check shear stress at the face of the anchor plate:
holes it may be prudent to check two anchorage
bonds, i.e. vmax = V / (u0d)

x On the grout/bolt interface. The calculation will vPD[VKRXOGQRWH[FHHG¥fcu or 5 N/mm² if less.


be as above, except that a value of fbu will need
to be determined for the grout material, based If vmax exceeds the above values it will be
upon the characteristic compressive strength of necessary to increase the size of the anchor plate.
the grout or the manufacturer’s technical
information. Check the shear stress on the critical perimeter:
x On the grout/drilled hole interface. The
calculation will be similar to that above, except v = V / (ud)
that ij= hole diameter and fbu will be the lesser
of that for the foundation concrete or the grout. where
An assessment of the bond characteristics of
the perimeter of the drilled hole will need to be u = length of critical perimeter, located at a
made. This will depend on the roughness of the distance of 1.5d from the anchor plate.
inside of the hole. For a ‘smooth’ hole (e.g.
produced by diamond drilling) the ‘Plain Bar’ v should not exceed the appropriate vc value from
values in Table 3.26 of BS 8110-1 could be Table 3.8. If v exceeds the Table 3.8 value there
used. For a ‘rough’ hole (e.g. produced by are a number of options available:
percussive drilling) the ‘Type 2’ values in Table
3.26 could be used. x Lengthen the bolts, thus setting the anchor plate
deeper into the concrete
In all cases if fb exceeds fbu, deepen and/or x Increase the size of the anchor plate. Note: it
increase the number of bolts. may require stiffening if increased in size.
x Increase the amount of top reinforcement to
increase vc
Page 3 of 4 CONCRETE ADVICE NO. 05

x Provide shear reinforcement. This would be For proprietary materials, refer to manufacturer’s
regarded as a last resort due to the practical literature for design stresses at the appropriate
difficulties and cost of installing shear links in ages.
foundations. In this instance the shear would
Licensed copy: leedsm, LEEDS BECKETT UNIVERSITY, 03/11/2017, Uncontrolled Copy, © Concrete Society

have to be checked on the next shear perimeter, Notes:


and if necessary subsequent shear perimeters. x The information given above is based on
Clause 5.2.3.4 in BS 8110 and Clause 3.8.4 in
Reference 4.
2 Base plate sizing-compression x In Table 1, the strength at 3 days is assumed to
be 40% of the value at 28 days, and the
strength at 7 days is assumed to be 60% of the
The following procedures will give the absolute
value at 28 days. This is applicable to Portland
minimum stanchion base plate size and apply to pin
cement materials only. Higher percentages
jointed bases only. For stanchion bases required to
may be used if confirmed by testing or past
resist overturning moments refer to the relevant
knowledge of the materials.
codes of practice and design guides for the design
of the base plate size. x The design bearing stresses can be used as
the maximum values for the design of base
Use factored design loads not characteristic loads. plates that are subject to an overturning
If the compression load results from a non limit- movement or non-uniform stress distribution.
state design assume a partial load factor of 1.6, x The procedures assume a uniform distribution
unless a lower value can be justified by calculation. of stress below the base plate, i.e. that the
The design of the base plates will form part of the base plate is stiff. If the stress is not uniform,
structural steelwork design. i.e. a flexible base plate, different procedures
will be needed to size the base plate.
Base plate area =
Maximum design compressive load y Design x The materials defined in Table 1 are as follows:
ultimate bearing stress ƒ Grout: Mixture of cement (usually Portland
cement) to water in proportion of about 2:1
Two cases should be considered and the larger by weight.
area used. ƒ Sanded grout: Mixture of cement, sand
and water in approximately equal
Infill material/concrete foundation interface proportions by weight.
Take design ultimate bearing stress = 0.6 fcu(1)
where fcu(1) is the characteristic strength of the ƒ Mortar: Mixture of cement, sand and water
foundation concrete. in proportions of about 1:3:0.4 by weight.

Base plate/infill material interface For further information refer to Clause 3.8.1 in
Take design ultimate bearing stress = 0.4 fcu(2) Reference 4.
where fcu(2) is the characteristic strength of the
bedding infill material. The characteristic strength
will depend on the age at which the bedding/infill
material is subject to the full load. Table 1 lists
typical values for fcu(2).

Table 1: Typical values for fcu(2) (based on Reference 4)

Material Cube strength at 28 days 0.4 fcu values (N/mm²)


(N/mm²) 3 days 7 days 28 days
Cement grout 12 – 15 1.9 – 2.4 2.9 – 3.6 4.8 – 6.0
Sanded grout 15 – 20 2.4 – 3.2 3.6 – 4.8 6.0 – 8.0
Mortar 20 – 25 3.2 – 4.0 4.8 – 6.0 8.0 – 10.0
Fine concrete Use 28 day cube strength 0.16 fcu 0.24 fcu 0.4 fcu
Page 4 of 4 CONCRETE ADVICE NO. 05

(4)
APPENDIX: SURFACE AREA OF CONES AROUND EMBEDDED BOLTS

Single bolts
2
The surface area (AS) of a 90°cone around a single bolt of embedded depth D is 4.443 × D
Licensed copy: leedsm, LEEDS BECKETT UNIVERSITY, 03/11/2017, Uncontrolled Copy, © Concrete Society

Note: This expression cannot be used if bolts are closer together than 2D or closer to the edge of a
foundation than 1.5D.

Pairs of bolts
D = Embedded depth of the bolts
X = Horizontal distance between the bolt centres.
AD = Combined surface area of the two 90°cones around each bolt.
2
If X is greater than 2D, AD = 8.886 × D
If X is less than 2D the cones overlap.
The values for AD are listed in the following table.

X= 100 150 200 300 450 600 750 1000


D EFFECTIVE CONICAL AREA OF 2 CONES
3 2
(mm) ( ×10 mm )
100 71.5 82.5 88.9 88.9 88.9 88.9 88.9 88.9
150 141.6 160.8 178.0 199.9 199.9 199.9 199.9 199.9
200 233.7 260.5 285.9 329.8 355.4 355.4 355.4 355.4
300 484.3 525.8 566.4 643.4 742.0 799.7 799.7 799.7
450 1027 1090 1152 1274 1448 1602 1728 1799
600 1769 1853 1937 2103 2345 2574 2784 3072
750 2711 2817 2922 3131 3439 3737 4021 4451
1000 4726 4867 5008 5288 5705 6114 6513 7149

References
1. BSI. BS 8110-1: 1997 Structural use of concrete, Part 1: Code of practice for design and construction.
(withdrawn)
2. BSI. BS EN 1992-1-1: 2004 Eurocode 2: Design of concrete structures – Part 1-1: General rules and
rules for buildings
3. THE CONCRETE SOCIETY. Holding down bolts using EC2, Concrete Advice 42, The Concrete Society
2010
4. THE CONCRETE SOCIETY. Holding down systems for steel stanchions, The Concrete Society, Cement
and Concrete Association and CONSTRADO, 1980

Impartial advice can be sought from The Concrete Society. Members are entitled Contacts
to substantial discounts on services and products including site visits and
investigations, dependent on status. For publications and information, The The Concrete Society 01276 607140
Concrete Society Bookshop holds a wide range of books and pamphlets along Bookshop 07004 607777
with an extensive library stock. We provide many services such as literature www.concrete.org.uk
searches and notification of new references to our extensive catalogue www.concretebookshop.com

Issued Dec 2006


Reviewed Sept 2017

CONCRETE Advice Sheets are produced and published by The Concrete Society. The information and advice
contained in the Advice Sheets is based on the experience and knowledge of the Concrete Society’s
Technical Staff. Although The Society does its best to ensure that any advice, recommendation or information
it gives is accurate, no liability or responsibility of any kind (including liability for negligence), howsoever and
from whatsoever cause arising is accepted in this respect by The Concrete Society, its servants or agents.
Readers should also note that all Concrete Society publications are subject to revision from time to time and
should therefore ensure that they are in possession of the latest version.

You might also like