You are on page 1of 2

ONYX Series Version 22.

0 Firmware Release Notes


November 17, 2014

NFS-320 version 022.000.004 (22.0 B4) is the latest production firmware version and includes
the following modifications:
 Includes a Tracking Alarm Type Code for Monitor Modules
 Includes support for the SWIFT wireless devices
 No longer supports the RFX Wireless Interface and devices. Do not upgrade to
version 20.0 (or higher) firmware if RFX is part of the system

NFS2-640 version 022.000.004 (22.0 B4) is the latest production firmware version and includes
the following modifications:

 Includes a Tracking Alarm Type Code for Monitor Modules


 Addresses an issue where DVC troubles are not properly displayed on the CPU2-640 in
direct connect applications
 Includes support for the SWIFT wireless devices
 No longer supports the RFX Wireless Interface and devices. Do not upgrade to
version 20.0 (or higher) firmware if RFX is part of the system

NFS2-3030 version 022.000.009 (22.0 B9) is the latest production firmware version and includes
the following modifications:
 Includes a Tracking Alarm Type Code for Monitor Modules
 Includes the ability for the NFS2-3030 in Network Display Mode to display the active
pipe(s) of the VESDA VLS detector
o Requires the VESDA-HLI-GW with firmware version 3.22.132 or higher.
 Includes support for the SWIFT wireless devices
 No longer supports the RFX Wireless Interface and devices. Do not upgrade to
version 20.0 (or higher) firmware if RFX is part of the system

NCA-2 version 022.000.009 (22.0 B9) is the latest production firmware version and includes the
following modifications:

 Supports the Tracking Alarm Type Code for Monitor Modules


 Includes the ability to display the active pipe(s) of the VESDA VLS detector
o Requires the VESDA-HLI-GW with firmware version 3.22.132 or higher.

Requirements:
 The latest release of NFS-320, NFS2-640, NFS2-3030 and NCA-2 firmware requires
VeriFire Tools version 8.20 or higher
 Recommended firmware versions for ONYX series panels on NOTI-FIRE-NET with
version 22.0 panels:
 NFS-3030 version 002.013.002
 LCM-320 version 009.000.007
 LCD-160 version 002.007.002
 NFS2-3030 version 022.000.009
 LCM-320 version 009.000.007
 LCD-160 version 007.000.007
 NFS-640 version 003.017.001
 NFS2-640 version 022.000.004
 NFS-320 version 022.000.004
 NCA version 003.012.004
 NCA-2 version 022.000.009
 LCD-160 version 007.000.007
 NCM-PCA version 003.060.006
 NCM-PCB version 010.002.002
 HS-NCM version 020.004.003
 DVC version 007.030.005
 DAA version 003.070.001
 DAA2 version 001.080.001
 DAX version 001.020.001
 DS-DB version 001.040.001
 DS-AMP version 001.001.001
 DVC-RPU version 002.001.001

 If version 22.0 firmware will be used on Noti-Fire-Net version 5.0 or higher


ONYXWorks must be version 3.22 or higher. NCS does not support this version of
NFS2-3030 firmware, upgrade to ONYXWorks.

Notes:

The latest version of VeriFire Tools can be downloaded from the esd.notifier site.

ONYXWorks version 3.22 upgrade can be ordered from Customer Service (OW-SW-US-3).