NGR Design Calculation ETX_Size

Item Value Unit Comment V38

To Protect S ≥ 34,294.61 kVA Transformer / Generator apparent power 60,000 kVA


U1ph 33.00 kV phase voltage
U1pn 19.05 kV neutral / ground voltage
IEF 600.00 A short current, neutral / total
ZT 31.75 Ω required total impedance ETX + NGR

ST-ETX S 200.00 kVA Station Transformer nominal power


ZNyn11 vector group
I0EF 600.00 A EF short time rating 10 sec I0EF 2005.53 A
10 sec short time duration / overload Factor 18.9 1
U1n 19.05 kV voltage phase - neutral (design) U2ph 0.420 kV
U1ETX 5.70 kV applied voltage phase - neutral (with NGR) U2pn 0.242 kV
I10 3.50 A primary full load current I20 274.93 A
I1EF0 200.00 A EF phase current 10 s/h N 78.57
S10s 606 kVA short time rating, max.10 sec 18.9 1
S30s 1,052 kVA short time rating, max.30 sec 10.9 2
Z0p 28.50 Ω primary phase impedance
Z0T 9.50 Ω ETX primary total EF impedance
24% load distribution ETX - NGR
BIL 36/70/170 kV rated / frequency / impulse

NGR IEF 600.00 A neutral max. current I0EF 648.47 A


UNGR 17.63 kV applied voltage phase - neutral (with ETX)
RNGR 29.38 Ω resistance 10 s/h
PNGR 10,577 kW
76% load distribution NGR - ETX
BIL 24/50/125 kV rated / frequency / impulse Un 19.05 kV

Last Calculation 12-May-2022 23:05

Example
a) Earthing Transformer b) Earthing Transformer + Station Transformer

NGR_Heat_Calc_HEE_Pekan_60MVA_33kV_NER_V38.2.xlsm, ETX_Size page 1 / 1