To Protect S ≥ 34,294.61 kVA Transformer / Generator apparent power 60,000 kVA
U1ph 33.00 kV phase voltage U1pn 19.05 kV neutral / ground voltage IEF 600.00 A short current, neutral / total ZT 31.75 Ω required total impedance ETX + NGR
ST-ETX S 200.00 kVA Station Transformer nominal power
ZNyn11 vector group I0EF 600.00 A EF short time rating 10 sec I0EF 2005.53 A 10 sec short time duration / overload Factor 18.9 1 U1n 19.05 kV voltage phase - neutral (design) U2ph 0.420 kV U1ETX 5.70 kV applied voltage phase - neutral (with NGR) U2pn 0.242 kV I10 3.50 A primary full load current I20 274.93 A I1EF0 200.00 A EF phase current 10 s/h N 78.57 S10s 606 kVA short time rating, max.10 sec 18.9 1 S30s 1,052 kVA short time rating, max.30 sec 10.9 2 Z0p 28.50 Ω primary phase impedance Z0T 9.50 Ω ETX primary total EF impedance 24% load distribution ETX - NGR BIL 36/70/170 kV rated / frequency / impulse
NGR IEF 600.00 A neutral max. current I0EF 648.47 A
UNGR 17.63 kV applied voltage phase - neutral (with ETX) RNGR 29.38 Ω resistance 10 s/h PNGR 10,577 kW 76% load distribution NGR - ETX BIL 24/50/125 kV rated / frequency / impulse Un 19.05 kV
Last Calculation 12-May-2022 23:05
Example a) Earthing Transformer b) Earthing Transformer + Station Transformer