DUCT SIZE CALCULATOR (SI) DUCT SIZE CAL

A. AIR VOLOUME (L/s) 700 A. AIR VOLOUME (CFM)


W H
B. DUCT SIZE (MM) 660 305 B. DUCT SIZE (INCH)
C. DUCT MATERIAL GALVANISED C. DUCT MATERIAL
D. ABS ROUGHNESS(mm) 0.15 D. ABS ROUGHNESS (ft)
E. EQUIVALAENT DIAMETER (MM) 481.6 E. EQUIVALAENT DIAMETER
F. HYDRAULIC DIAMETER (MM) 417.2 F. HYDRAULIC DIAMETER (I
G. DUCT VELOCITY (m/s) 3.5 G. DUCT VELOCITY (FPM)
H. VELOCITY PRESSURE (Pa) 7.3 H. VELOCITY PRESSURE (Inc
I. REYNOLDS NO.(Re) 96,332 I. REYNOLDS NO.(Re)
J. FRICTION FACTOR (f) 0.01950 J. FRICTION FACTOR (f)
K. DUCT FRICTION (Pa/ M) 0.340 K. DUCT FRICTION (Inch/ 100

For this calculation pleae check only duct friction & heig For this calculation pleae chec

HEIGHT AS PER AVAILABILITY OF SPACE. HEIGHT AS PER AVAILABILI


DUCT FRICTION AS PER RECOMMENDED VALUE. DUCT FRICTION AS PER REC

ONLY INPUT YELLOW FIGURE. ONLY INPUT YELLOW FI


DON'T CHANGE ANY OTHER VALUE OR FORMULAE. DON'T CHANGE ANY OTHER

A= 6.8317E+20 A=
B= 2.8168E-07 B=
f= 0.01994415 f=
DUCT SIZE CALCULATOR (IP)

R VOLOUME (CFM) 4000


W H
CT SIZE (INCH) 46 14 1219.2
CT MATERIAL GALVANISED
S ROUGHNESS (ft) 0.0005
UIVALAENT DIAMETER (INCH) 26.6
DRAULIC DIAMETER (INCH) 21.5
CT VELOCITY (FPM) 894.4
LOCITY PRESSURE (Inch) 0.050
YNOLDS NO.(Re) 164,352
ICTION FACTOR (f) 0.01767
CT FRICTION (Inch/ 100 FT) 0.049

this calculation pleae check only duct friction & height

IGHT AS PER AVAILABILITY OF SPACE.


CT FRICTION AS PER RECOMMENDED VALUE.

LY INPUT YELLOW FIGURE.


N'T CHANGE ANY OTHER VALUE OR FORMULAE.

3.29721E+21
0
0.0163831537