You are on page 1of 4

DUCT SIZE CALCULATOR (SI) DUCT SIZE C

A. AIR VOLOUME (L/s) 700 A. AIR VOLOUME (CFM)


W H
B. DUCT SIZE (MM) 660 305 B. DUCT SIZE (INCH)
C. DUCT MATERIAL GALVANISED C. DUCT MATERIAL
D. ABS ROUGHNESS(mm) 0.15 D. ABS ROUGHNESS (ft)
E. EQUIVALAENT DIAMETER (MM) 481.6 E. EQUIVALAENT DIAME
F. HYDRAULIC DIAMETER (MM) 417.2 F. HYDRAULIC DIAMETE
G. DUCT VELOCITY (m/s) 3.5 G. DUCT VELOCITY (FPM
H. VELOCITY PRESSURE (Pa) 7.3 H. VELOCITY PRESSURE
I. REYNOLDS NO.(Re) 96,332 I. REYNOLDS NO.(Re)
J. FRICTION FACTOR (f) 0.01950 J. FRICTION FACTOR (f)
K. DUCT FRICTION (Pa/ M) 0.340 K. DUCT FRICTION (Inch/

For this calculation pleae check only duct friction & height For this calculation pleae
factor height factor

HEIGHT AS PER AVAILABILITY OF SPACE. HEIGHT AS PER AVAILA


DUCT FRICTION AS PER RECOMMENDED VALUE. DUCT FRICTION AS PER

ONLY INPUT YELLOW FIGURE. ONLY INPUT YELLOW


DON'T CHANGE ANY OTHER VALUE OR FORMULAE. DON'T CHANGE ANY OTH

A= 6.8317E+20 A=
B= 2.8168E-07 B=
f= 0.01994415 f=
DUCT SIZE CALCULATOR (IP)

R VOLOUME (CFM) 4000


W H
CT SIZE (INCH) 46 14 1219.2
CT MATERIAL GALVANISED
S ROUGHNESS (ft) 0.0005
UIVALAENT DIAMETER (INCH) 26.6
DRAULIC DIAMETER (INCH) 21.5
CT VELOCITY (FPM) 894.4
LOCITY PRESSURE (Inch) 0.050
YNOLDS NO.(Re) 164,352
ICTION FACTOR (f) 0.01767
CT FRICTION (Inch/ 100 FT) 0.049

this calculation pleae check only duct friction &


ght factor

IGHT AS PER AVAILABILITY OF SPACE.


CT FRICTION AS PER RECOMMENDED VALUE.

LY INPUT YELLOW FIGURE.


N'T CHANGE ANY OTHER VALUE OR FORMULAE.

3.297214E+21
5.465843E-11
0.0163831537

You might also like