Contents
1 Introduction and application
2 Features and characteristics
3 Design
3.1 Connections 5.7 Indication of measuring values
3.1.1 Analog input circuits 5.7.1 Measuring indication
3.1.2 Blocking input 5.7.2 Unit of the measuring values displayed
3.1.3 Reset input 5.7.3 Indication of fault memory data
3.1.4 Output relays 5.8 Fault memory
3.1.5 Fault recorder 5.9 Additional functions
3.1.6 Parameter settings 5.9.1 Setting procedure for blocking the
3.2 LEDs protection functions
3.3 Front plate 5.9.2 Reset
5.9.3 Erasure of fault storage
4 Working principle
4.1 Analog circuits 6 Relay testing and commissioning
4.2 Digital circuits 6.1 Power-On
4.3 Voltage supervision 6.2 Testing the output relays
4.3.1 Selection of star or delta connection 6.3 Checking the set values
4.4 Blocking function 6.4 Secondary injection test
6.4.1 Test equipment
5 Operations and settings
6.4.2 Example of the test circuit
5.1 Display
6.4.3 Checking the input circuits and
5.2 Setting procedure
measuring functions
5.3 Systemparameter
6.4.4 Checking the operating and resetting
5.3.1 Display of residual voltage UE as
values of the over/undervoltage functions
primary quantity (Uprim/Usec)
6.4.5 Checking the relay operating time of the
5.3.2 ∆/Y – Switch over
over/undervoltage functions
5.3.3 Setting of nominal frequency
6.4.6 Checking the external blocking and reset
5.3.4 Display of the activation storage
functions
5.3.5 Parameter switch/external triggering for
6.5 Primary test
the fault recorder
6.6 Maintenance
5.4 Protection parameters
5.4.1 1-phase or 3-phase U</U>- tripping 7 Technical Data
5.4.2 Parameter setting of over- and under- 7.1 Measuring input circuits
voltage supervision 7.2 Common data
5.4.3 Adjustment of the slave address 7.3 Setting ranges and steps
5.4.4 Setting of Baud-rate (applies for Modbus- 7.3.1 Interface parameter
Protocol only) 7.3.2 Parameter for the fault recorder
5.4.5 Setting of parity (applies for Modbus- 7.4 Output relays
Protocol only)
8 Order form
5.5 Parameter for the fault recorder
5.5.1 Adjustment of the fault recorder
5.5.2 Number of the fault recordings
5.5.3 Adjustment of trigger occurences
5.5.4 Pre-trigger time (Tpre)
5.6 Date and time
5.6.1 Adjustment of the clock
2 TD_MRU3-1_12.05_GB
1 Introduction and application 2 Features and characteristics
The voltage supervision relay MRU3-1 protects electri- • Microprocessor technology with watchdog,
cal power generators, consumers or operating com- • digital filtering of the measured values by using dis-
ponents generally against over- or undervoltages. crete Fourier analysis to suppress higher harmonics
and d.c. components induced by faults or system
Among other applications the relay can be used: operations,
• for detection of over- or undervoltages in power gen- • two parameter sets,
rating plants and energy supply systems • voltage supervision each with two step under-/ and
• to protect generators against critical overvoltages in overvoltage detection,
case of defective voltage regulators • Completely independent time settings for voltage su-
• as undervoltage protection for motors pervision
• as generator stator earth fault protection • display of all measuring values and setting parame-
• as over- and undervoltage protection with evaluating ters for normal operation as well as tripping via a
the symmetrical components (MRU1-2, detailed in- alphanumerical display and LEDs,
formation on this type can be found in the relevant • display of measuring values as primary quantities
technical description) • 1-phase or 3-phase tripping criterion for the U</U>
step,
There is also a similar protection relay IRU1 available • Storage and display of tripping values in a fault
in a more simpler design, i.e. with less function, with- memory (voltage-failure safe),
out display and without serial interface. • recording of up to eight fault occurences with time
stamp
• for blocking the individual functions by the external
blocking input, parameters can be set according to
requirement,
• suppression of indication after an activation
(LED flash),
• free assignment for output relays,
• display of date and time,
• in complience with VDE 0435, part 303 and IEC
255,
• serial data exchange via RS485 interface possible;
alternatively with SEG RS485 Pro-Open Data Proto-
col or Modbus Protocol.
Important:
For additional common data of all MR-relays please
refer to technical description "MR - Digital Multifunc-
tional Relays".
TD_MRU3-1_12.05_GB 3
3 Design
3.1 Connections
4 TD_MRU3-1_12.05_GB
3.1.4 Output relays
The MRU3-1 is equipped with 5 output relays. The memory part of the fault recorder is designed as
• Relay 1; C1, D1, E1 and C2, D2, E2 circulating storage. In this example 7 fault records can
• Relay 2; C3, D3, E3 and C4, D4, E4 be stored (written over).
• Relay 3; C5, D5, E5
• Relay 4; C6, D6, E6 Memory space 6 to 4 is occupied.
• Relay 5; Signal self-supervision (internal failure of Memory space 5 is currently being written in
the unit ) C7, D7, E7
All trip and alarm relays are working current relays, the
relay for self supervision is an idle current relay.
recording duration
Writing over
TD_MRU3-1_12.05_GB 5
3.1.6 Parameter settings 3.2 LEDs
System parameters All LEDs (except LED RS, FR and P2) are two-coloured.
Uprim/Usek Primary/secondary measured value The LEDs on the left side, next to the alphanumerical
display of the voltage transformers display light up green during measuring and red after
∆/Y Selection of switching groups tripping.
fN Rated frequency
P2|FR Parameter switch/ext. triggering for the The LEDs below the push button <SELECT/RESET> are
fault recorder lit green during setting and inquiry procedure of the
LED-Flash Suppression of LED flashing after setting values which are printed on the left side next to
activation the LEDs. The LEDs will light up red after parametrizing
of the setting values next to their right side.
Protection parameters The LED marked with letters RS lights up during setting
1/3 1-phase U</U> or 3-phase U</U> of the slave address of the device for serial data com-
tripping munication.
U< Tripping value for undervoltage low set
element The LED marked with the letters FR is alight while the
tU< Tripping delay time for undervoltage low fault recorder is being adjusted.
set element
U<< Tripping value for undervoltage high set If the ! LED is displayed, date and time are shown.
element
tU<< Tripping delay time for undervoltage high
set element 3.3 Front plate
U> Tripping value for overvoltage low set
element
tU> Tripping delay time for overvoltage low
set element
U>> Tripping value for overvoltage high set
element
tU>> Tripping delay time for overvoltage high
set element
Additional functions
Blocking function
Relay configuration
Fault memory
Figure 3.5: Front plate MRU3-1
6 TD_MRU3-1_12.05_GB
4 Working principle
The input voltages are galvanically insulated by the in- The voltage relay MRU3-1 protects electrical genera-
put transformers. The noise signals caused by inductive tion systems, consumers and appliances in general
and capacitive coupling are suppressed by an analog against over- and/or undervoltage. The relay is
R-C filter circuit. equipped with an independent, 2-step over- (U>, U>>)
and undervoltage supervision (U<, U<<) with sepa-
The analog voltage signals are fed to the A/D- rately adjustable tripping values and delay times. Volt-
converter of the microprocessor and transformed to age measuring is 3-phase. In this process there is a
digital signals through Sample- and Hold- circuits. The continuous comparison of the line conductor voltages
analog signals are sampled with a sampling frequency in case of a delta connection and of the phase volt-
of 16 x fN, namely, a sampling rate of 1.25 ms for ages in case of a star connection with the preset limit
every measuring quantity, at 50 Hz. values.
TD_MRU3-1_12.05_GB 7
4.3.1 Selection of star or delta 4.4 Blocking function
connection
No. Dynamic Behaviour U</<< U>/>>
All six connections of the input voltage transformers are
led to screw terminals. The nominal voltage of the de- 1 voltage to external free pro- free pro-
vice is equal to the nominal voltage of the input trans- blocking input is ap- gramma- gramma-
formers. Dependent on the application the input trans- plied ble ble
formers can be connected in either delta or star. The 2 blocking input is released released
connection for the phase-to-phase voltage is the delta released instanta- instanta-
connection. In star connection the measuring voltage is neously neously
3 supply voltage is blocked blocked
reduced by 1/ 3 . During parameter setting the con-
switched on for for 200
nection configuration either Y or delta has to be ad-
200 ms ms
justed.
4 3ph measuring volt. released released
is suddenly applied
Sec. winding of 5 one or several meas- released released
mains V.T.
uring voltages are
a A3
switched off suddenly
U12 (phase failure)
A4
Table 4.1: Dynamic behaviour of MRU3-1 functions
b A5
Sec. winding of
mains V.T.
a A3
U1
A4
b A5
U2
A6
c A7
U3
A8
8 TD_MRU3-1_12.05_GB
5 Operations and settings
5.1 Display
TD_MRU3-1_12.05_GB 9
5.2 Setting procedure The difference lies in the method of voltage measuring.
With the setting "v = 50 Hz or v = 60 Hz“ voltage
For parameter setting a password has to be entered measuring is independent of the existing frequency.
first (please refer to 4.4 of description "MR-Digital Mul- This means, the voltage value can be correctly meas-
tifunctional Relays"). ured between 40 Hz and 70 Hz without adverse ef-
fects from the frequency.
5.3 Systemparameter
With the setting "f“ = 50/60 Hz the measured voltage
5.3.1 Display of residual voltage UE as value is influenced by the frequency. (see Table 5.2)
primary quantity (Uprim/Usec)
Declination of measuring value at 50Hz
The residual voltage can be shown as primary measur-
ing value. For this parameter the transformation ratio of 100,5
the VT has to be set accordingly. If the parameter is set [%]
100,0
to "sec", the measuring value is shown as rated secon- 99,5
99,0
dary voltage. 98,5
98,0
97,5
Example: 44 46 48 50 52 54 56 [Hz]
The voltage transformer is used for 10 kV/100 V. The
transformation ratio is 100 and this value has to be set
accordingly. If still the rated secondary voltage should
Declination of measuring value at 60Hz
be shown, the parameter is to be set to 1.
100,5
[%] 100,0
5.3.2 D/Y – Switch over 99,5
99,0
98,5
Depending on the mains voltage conditions, the input 98,0
voltage transformers can be operated in delta or Y 97,5
connection. Change-overs are effected via the <+> 54 56 58 60 62 64 66 [Hz]
Setting v = 50 f = 50 v = 60 f = 60
Rated frequency* 50 Hz 50 Hz 60 Hz 60 Hz
Influence on voltage none 0.5..1%/Hz none 0.5..1%/Hz
measurement (see table 5.1) (see table 5.1)
Fault recorder Recording Recording Recording Recording
distorted** correct*** distorted** correct***
Influence on all other none none none none
functions
Table 5.2: Deviation of measured value at 50 Hz or 60 Hz
10 TD_MRU3-1_12.05_GB
5.3.4 Display of the activation storage
If after an activation the existing current drops again With the setting S2_FR parameter set 2 can be acti-
below the pickup value, e.g. U<, without a trip has vated via the blocking input and/or the fault recorder
been initiated, LED U< signals that an activation has via the reset input.
occured by flashing fast. The LED keeps flashing until it The relevant function is then activated by applying the
is reset again (push button <RESET>). Flashing can be auxiliary voltage to one of the external inputs.
suppressed when the parameter is set to NOFL.
Important note:
5.3.5 Parameter switch/external When functioning as parameter change over facility,
triggering for the fault recorder the external input RESET is not available for resetting.
When using the external input BLOCKING the protec-
By means of the parameter-change-over switches it is tion functions must be deactivated by software block-
possible to activate two different parameter sets. ing separately (refer to chapter 5.9.1).
Switching over of the parameter sets can either be
done by means of software or via the external inputs
RESET or blocking input. Alternatively, the external in- 5.4 Protection parameters
puts can be used for Reset or blocking of the triggering
of the fault recorder. 5.4.1 1-phase or 3-phase U</U>-
tripping
Software- Blocking input RESET input
parameter used as used as Switching-over of the parameter permits selection be-
SET1 Blocking input RESET input tween 1-phase and 3-phase tripping of the U</U>
SET2 Blocking input RESET input steps.
B_S2 Parameter switch RESET input Keys <+> or <-> are used to change the value and
R_S2 Blocking input Parameter switch <ENTER> to store it.
B_FR External trigger- Reset input
ing of the fault Note
recorder When the MRU3-1 is to be used for measuring the re-
R_FR Blocking input External trigger- sidual voltage in systems with isolated or compensated
ing of the fault neutral or as generator earth fault protection, the
recorder measuring voltage has to be applied to terminals
S2_FR Parameter switch External trigger- A3-A4. Undervoltage functions U< and U<< have to
ing of the fault be set to "EXIT" and overvoltage functions U> and U>>
recorder have to be adjusted to the required pickup values.
The frequency must be set to 50 or 60 Hz. The pa-
With the settings SET1 or SET2 the parameter set is rameter 1-phase or 3-phase tripping mut be set to
activated by software. Terminals C8/D8 and D8/E8 U<>1 (1-phase tripping).
are then available as external reset input or blocking
input.
TD_MRU3-1_12.05_GB 11
5.4.2 Parameter setting of over- and 5.4.5 Setting of parity (applies for
undervoltage supervision Modbus-Protocol only)
The setting procedure is guided by two coloured LEDs. The following three parity settings are possible :
During setting of the voltage thresholds the LEDs U<,
U<<, U> and U>> are lit green. During setting of the • "even" = even parity
trip delays tU>, tU>>, tU< and tU<< the according LEDs light • "odd" = odd parity
up red. • "no" = no parity check
Thresholds of the voltage supervision The setting can be changed by push buttons <+> and
<-> and saved by pressing <ENTER>.
During setting of the threshold U>, U>>, U< and U<<
the displays shows the voltages directly in volt. The
thresholds can be changed by the <+> <-> push but- 5.5 Parameter for the fault recorder
tons and stored with <ENTER>.
5.5.1 Adjustment of the fault recorder
The undervoltage supervision (U< and U<<) as well as
the overvoltage supervision (U> and U>>) can be de- The MRU3-1 is equipped with a fault recorder (see
activated by setting the threshold to "EXIT". chapter 3.1.5). Three parameters can be determined.
5.4.3 Adjustment of the slave address (1)* 2 recordings for a duration of 8 s (with 50 Hz)
(6.66 s with 60 Hz)
By pressing push buttons <+> and <-> the slave ad- (3)* 4 recordings for a duration of 4 s (with 50 Hz)
dress can be set in the range of 1 - 32. During this ad- (3.33 s with 60 Hz)
justment the LED RS lights up. (7)* 8 recordings for a duration of 2 s (with 50 Hz)
(1,66 s with 60 Hz)
* is written over when a new trigger signal arrives
5.4.4 Setting of Baud-rate (applies for
Modbus-Protocol only) Caution:
If the fault recorder is used, the frequency should be
Different transmission rates (Baud rate) can be set for set to f = 50 Hz or f = 60 Hz (see chapter 5.3.3).
data transmission via Modbus Protocol.
The rate can be changed by push buttons <+> and
<-> and saved by pressing <ENTER>.
12 TD_MRU3-1_12.05_GB
5.5.3 Adjustment of trigger occurences 5.7 Indication of measuring values
P_UP (PickUP) Storage is initiated after recognition In normal operation the following measuring values
of a general activation. can be displayed.
TRIP Storage is initiated after a trip has
occured. • Voltages (LED L1, L2, L3 green)
A_PI (After Pickup) Storage is initiated after the last • In star connection all phase-to-neutral voltages
activation threshold was fallen • In delta connection all phase-to-phase voltages
short of.
TEST Storing is activated by simultaneous
actuation of the keys <+> and <->. 5.7.2 Unit of the measuring values
During the recording time the displayed
display shows “Test”.
The measuring values can optionally be shown in the
display as a multiple of the "sek" rated value (x ln) or
5.5.4 Pre-trigger time (Tpre) as primary current (A). According to this the units of the
display change as follows:
By the time Tpre it is determined which period of time
prior to the trigger occurence should be stored as well. Indication as Range Unit
It is possible to adjust a time between 0.05s and the Sec. voltage 000V - 999V V
max. recording interval (2, 4 and 8s). With keys <+> Primary voltage .00V – 999V V
and <-> the values can be changed and with 1k00 – 9k99 kV
<ENTER> be saved. 10k0 – 99k0 kV
100k – 999k kV
1M00 –- MV
5.6 Date and time 3M00
Table 5.3: Units of the display
5.6.1 Adjustment of the clock
Date : Year Y=00 All faults detected by the relay are indicated on the
Month M=01 front plate optically. For this purpose, the three LEDs
Day D=01 (L1, L2, L3) and the four function LEDs (U<, U<<, U>,
U>>) are equipped at MRU3-1. Not only fault mes-
Time : Hour h=00 sages are transmitted, the display also indicates the
Minute m=00 tripped protection function. If, for example an overcur-
Second s=00 rent occurs, first the respective phase LED will light up.
LED I> lights up at the same time. After tripping the
The clock starts with the set date and time as soon as LEDs are lit permanently.
the supply voltage is switched on. The time is safe-
guarded against short-term voltage failures (min. 6
minutes).
Note:
The window for parameter setting is located behind
the measured value display. The parameter window
can be accessed via the <SELECT/RESET> key.
TD_MRU3-1_12.05_GB 13
5.8 Fault memory
14 TD_MRU3-1_12.05_GB
5.9 Additional functions
The blocking function of the MRU3-1 can be set ac- The relays are assigned as follows: LEDs U<, U<<, U>
cording to requirement. By applying the aux. voltage and U>> are two-coloured and light up green when
to D8/E8, the functions chosen by the user are the output relays are assigned as alarm relays and tU<,
blocked. Setting of the parameter should be done as tU<<, tU>, tU>>, red as tripping relays.
follows:
Definition:
• When pressing push buttons <ENTER> and <TRIP> Alarm relays are activated at pickup.
at the same time, message "BLOC" is displayed (i.e. Tripping relays are only activated after elapse of the
the respective function is blocked) or "NO_B" (i.e. tripping delay.
the respective function is not blocked). The LED allo-
cated to the first protection function U< lights red. After the assignment mode has been activated, first
• By pressing push buttons <+> <-> the value dis- LED U< lights up green. Now one or several of the
played can be changed. four output relays can be assigned to under voltage
• The changed value is stored by pressing <ENTER> element U< as alarm relays. At the same time the se-
and entering the password. lected alarm relays for under voltage element 1 are
• By pressing the <SELECT/RESET> push button, any indicated on the display. Indication "1_ _ _" means
further protection function which can be blocked is that output relay 1 is assigned to this under voltage
displayed. element. When the display shows "_ _ _ _", no alarm
• Thereafter the menu is left by pressing relay is assigned to this under voltage element. The as-
<SELECT/RESET> again. signment of output relays 1 - 4 to the current elements
• If the <SELECT/RESET> key is actuated again, the can be changed by pressing <+> and <-> push but-
blocking menu is left and the assignment mode is tons. The selected assignment can be stored by press-
accessed. ing push button <ENTER> and subsequent input of the
password. By pressing push button <SELECT/RESET>,
Function Description Display LED LED U< lights up red. The output relays can now be
U< Undervoltage step 1 BLOC green assigned to this voltage element as tripping relays.
U<< Undervoltage step 2 BLOC green
U> Overvoltage step 1 NO_B green Relays 1 - 4 are selected in the same way as de-
U>> Overvoltage step 2 NO_B green scribed before. By repeatedly pressing of the
<SELECT/RESET> push button and assignment of the
Table 5.4: Blocking function for two parameter sets
relays all elements can be assigned separately to the
relays. The assignment mode can be terminated at any
Assignment of the output relays: time by pressing the <SELECT/RESET> push button for
Unit MRU3-1 has five output relays. The fifth output re- some time (abt. 3 s).
lay is provided as permanent alarm relay for self su-
pervision is normally on. Output relays 1 - 4 are nor- Note:
mally off and can be assigned as alarm or tripping re- • The function of jumper J2 described in general de-
lays to the voltage functions which can either be done scription "MR Digital Multifunctional Relays" does
by using the push buttons on the front plate or via se- not apply for MRU3-1. For relays without assign-
rial interface RS485. The assignment of the output re- ment mode this jumper is used for parameter setting
lays is similar to the setting of parameters, however, of alarm relays (activation at pickup or tripping).
only in the assignment mode. The assignment mode A form is attached to this description where the setting
can be reached only via the blocking mode. requested by the customer can be filled-in. This form is
By pressing push button <SELECT/RESET> in blocking prepared for telefax transmission and can be used for
mode again, the assignment mode is selected. your own reference as well as for telephone queries.
TD_MRU3-1_12.05_GB 15
5.9.2 Reset
Manual Reset
• Pressing the push button <SELECT/RESET> for some
time (about 3 s)
Electrical Reset
• Through applying auxiliary voltage to C8/D8
Software Reset
• The software reset has the same effect as the
<SELECT/RESET> push button (see also communica-
tion protocol of RS485 interface)
16 TD_MRU3-1_12.05_GB
6 Relay testing and 6.2 Testing the output relays
commissioning
NOTE!
Prior to commencing this test, interrupt the trip circuit to
The following test instructions should help to verify the
the circuit breaker if tripping is not desired.
protection relay performance before or during commis-
sioning of the protection system. To avoid a relay
By pressing the push button <TRIP> once, the display
damage and to ensure a correct relay operation, be
shows the first part of the software version of the relay
sure that:
(e.g. „D08-“). By pressing the push button <TRIP>
• The auxiliary power supply rating corresponds to the
twice, the display shows the second part of the soft-
auxiliary voltage on site.
ware version of the relay (e.g. „4.01“. The software
• The rated frequency and rated voltage of the relay
version should be quoted in all correspondence. Press-
correspond to the plant data on site.
ing the <TRIP> button once more, the display shows
• The voltage transformer circuits are connected to the
"PSW?". Please enter the correct password to proceed
relay correctly.
with the test. The message "TRI?" will follow. Confirm
• All signal circuits and output relay circuits are con-
this message by pressing the push button <TRIP>
nected correctly.
again. All output relays should then be activated and
the self supervision alarm relay (watchdog) be deener-
gized one after another with a time interval of 1 sec-
6.1 Power-On
ond. Thereafter, reset all output relays back to their
normal positions by pressing the push button
NOTE!
<SELECT/RESET>.
Prior to switch on the auxiliary power supply, be sure
that the auxiliary supply voltage corresponds to the
rated data on the type plate.
6.3 Checking the set values
Switch on the auxiliary power supply to the relay and
By repeatedly pressing the push button <SELECT>, all
check that the message "ISEG" appears on the display
relay set values may be checked. Set value modifica-
and the self supervision alarm relay (watchdog) is en-
tion can be done with the push button <+><-> and
ergized (Contact terminals D7 and E7 closed).
<ENTER>. For detailed information about that, please
It may happen that the relay is tripped because of un-
refer to chapter 4.3 of the description “MR – Digital
der- voltage condition after power-on. (The message
multifunctional relays”.
"TRIP" on the display and LED L1, L2, L3 and U< light
As relay input energizing quantities, three phase volt-
up red). An undervoltage condition has been detected
ages should be applied to MRU3 relay input circuits.
after power-on, because no input voltages are applied
Depending on the system conditions and the voltage
to the relay. In this case:
transformer used, three voltages can be connected to
• Press the push button <ENTER>, thus entering into
the relay input circuits with either star or delta connec-
the setting mode. Now set the parameters U< and
tion. In case of a star connection the phase-to-neutral
U<< to "EXIT" to block the undervoltage functions. Af-
voltage will be applied to the voltage input circuits,
ter that, press the <SELECT/RESET> for app. 3 s to
while the phase-to-phase voltages will be connected to
reset the LEDs and "TRIP" message.
the voltage input circuits in case of a delta connection.
• The undervoltage tripping after power on can also
The voltage input connection must be set as a parame-
be eliminated by applying three phase rated volt-
ter, and should correspond with the actual voltage in-
ages after power-on and reset the LED and "TRIP"
put connection:
message.
• Apply auxiliary voltage to the external blocking input Star connection: Phase-to-neutral voltages will be
(Terminals E8/D8) to inhibit the undervoltage func- measured and evaluated.
tions (refer to 6.5) and press the <SELECT/RESET> Delta connection: Phase-to-phase voltages will be
for app. 3 s to reset the LEDs and "TRIP" message. measured and evaluated.
TD_MRU3-1_12.05_GB 17
6.4 Secondary injection test
18 TD_MRU3-1_12.05_GB
6.4.3 Checking the input circuits and 6.4.5 Checking the relay operating time
measuring functions of the over/undervoltage functions
Apply three voltages of rated value to the voltage input To check the relay's operating time, a timer must be
circuits (terminals A3 - A8) of the relay. Check the connected to the trip outpnut relay contact (Contact
measured voltages, frequency and vector surge on the terminals D1/E1). The timer should be started simulta-
display by pressing the push button <SELECT/RESET> neously with the voltage change from sound condition
repeatedly. to a faulty condition and stopped by the trip relay con-
tact. The operating time measured by timer should
The voltages are indicated on the display in volts, at have a deviation about 3% of the set value or < 20
Y-connection: ms.
• Phase-to-neutral voltages: LED L1, L2, L3
Delta-connection:
• Phase-to-phase voltages: LED L1+L2, L2+L3, L3+L1 6.4.6 Checking the external blocking
and reset functions
Change the voltages around the rated value and
check the measured voltages on the display. The external blocking input blocks the selected voltage
functions.
Compare the voltage displayed with the reading at
voltmeter. The deviation for the voltage must not ex- Care must be taken that these terminals are also as-
ceed 1%. signed the blocking function (refer to chapter 5.9.1).
The external blocking input inhibits undervoltage func-
By using an RMS-metering instrument, a greater devia- tions. To test the blocking function apply auxiliary sup-
tion may be observed if the test voltages contains har- ply voltage to the external blocking input of the relay
monics. Because the MRU1 relay measures only the (terminals E8/D8). Inject a test voltage which could
fundamental component of the input signals, the har- cause tripping for the functions above mentioned. Ob-
monics will be rejected by the internal DFFT-digital fil- serve that there is no trip and alarm.
ter. Whereas the RMS-metering instrument measures
the RMS-value of the input signals. Remove the auxiliary supply voltage from the blocking
input. Apply test voltages to trip the relay (message
„TRIP“ on the display). Return the test voltages to the
6.4.4 Checking the operating and reset- sound condition and apply auxiliary supply voltage to
ting values of the over/under- the external reset input of the relay (terminals C8/D8).
voltage functions The display and LED indications should be reset im-
mediately.
Apply three voltages with the rated value and gradu-
ally increase (decrease) the voltages until the relay
starts, i.e. at the moment when the LED U> (or U<)
lights up or the voltage alarm output relay (contact ter-
minals D4/E4) is activated. Read the operating volt-
age indicated by the voltmeter. The deviation must not
exceed 1% of the set operating value.
TD_MRU3-1_12.05_GB 19
6.5 Primary test
6.6 Maintenance
20 TD_MRU3-1_12.05_GB
7 Technical Data
Power consumption in
voltage circuit: < 1 VA per phase at UN
Thermal withstand in
voltage circuit: continuously 2 x UN
TD_MRU3-1_12.05_GB 21
7.3 Setting ranges and steps
22 TD_MRU3-1_12.05_GB
8 Order form
TD_MRU3-1_12.05_GB 23
Setting list MRU3-1
Project: SEG-Job.-no.:
Date:
All settings must be checked at site and should the occasion arise, adjusted to the object/item to be protected.
System parameter
Protection parameter
24 TD_MRU3-1_12.05_GB
Fault recorder
Default Actual
Function Unit settings settings
FR Number of recordings 4
FR Saving of the recording at the occurrence TRIP
FR Time prior to trigger impulse s 0.05
Clock Year setting year Y=00
Clock Month setting month M=01
Clock Day setting day D=01
Clock Setting of the hour hour h=00
Clock Setting of the minute minute m=00
Clock Setting of the second second s=00
Blocking function
TD_MRU3-1_12.05_GB 25
Setting of code jumbers
Code jumper J1 J2 J3
Default Actual Default Actual Default Actual
settings settings settings settings settings settings
Plugged
Not plugged X No function X
Code jumper Low/High-range for reset input Low/High-range for blockage input
Default settings Actual settings Default settings Actual settings
Low=plugged X X
High=not plugged
26 TD_MRU3-1_12.05_GB
Woodward SEG GmbH & Co. KG
Krefelder Weg 47 ⋅ D – 47906 Kempen (Germany)
Postfach 10 07 55 (P.O.Box) ⋅ D – 47884 Kempen (Germany)
Phone: +49 (0) 21 52 145 1
Internet
Homepage http://www.woodward-seg.com
Documentation http://doc.seg-pp.com
Sales
Phone: +49 (0) 21 52 145 635 ⋅ Telefax: +49 (0) 21 52 145 354
e-mail: kemp.electronics@woodward.com
Service
Phone: +49 (0) 21 52 145 614 ⋅ Telefax: +49 (0) 21 52 145 455
e-mail: kemp.pd@woodward.com