You are on page 1of 20

Energy management

27 Automatic transfer
ansfe
er switch
h controllers

Supervision of two or
three-phase power sources
Emergency demand supervision
for standby generating set
Tie-breaker management
Control of contactors, motorised
circuit breakers and motorised
changeover switches
Closed transition
Automatic non-priority load
management
Event logging
Remote control and supervision
Front optical port
Built-in NFC technology
Expandable with EXP modules
Communication protocols
Modbus-ASCII, RTU and TCP
Real time clock
Enclosed automatic transfer
switches ATS.

SEC
EC. - PAGE
Auto
oma
m tic tr
t ansfer
err swi
w tc
tchh controllerrs fo
forr 2 po
powe
wer ssoour
urce
ces
ATTL100 typpe modu ular version for controollllin
i g 2 po
powe
weer so sou urce
urce
ur cess wi
with th
h sin
ingl
gle-
e-ph
p as
ph asee cont
coont
ntrool ......................................... 227
7 - 7
ATL5
L5
L 500 typee non expanddab
a lee with synopt
pttiicc and NFC C for con ontr
trol
o liling
ng
g 2 pow werr sou urc
rces ................................. ......
rces ........... 27 - 7
ATL6 600 and ATL601 tytype
pee non expandablee fo for cont
co
ont
n ro
ollllin
ing g 2 po
powe
werr soource
we urces.
ur ces.
ce s..............................................
........................ 27 - 8
ATL6 610
10 typpe expandablee with EXP momodu
dule
du lees fo
for co
for cont
n ro
nt r llllin
ing
in g 2 poowe
werr sources ..............................
..................................... 27 - 8
ATL80 00 type expandable with EX XP mo
mod lees fo
modu f r co
conttro
cont rolllliin
roll ing 2 power sources annd 1 tie ti br
breaker .............................. 27 - 9
Auutomattic tr
tran
an
nsf
s er switch conttro
roll
lller
ers fo
for
or 3 po
power sources
ATL900
AT 0 ttype
ype ex
expandable
xpandable with EXP
P modules
modu
modu
mo dulles for controlling
g 3 power
po sources
s and 2 tie breakers ............................ 27 - 10
Enccl
closed
oss auttom
o atic transsfe
ferr switches ATS
ATP
TP series
s riees
se es with AT
ATL600
TL6
L60
00 automatic transfer
00 transsfe
fer
er switch
switch controller and contactors ......................................................... 27 - 11
Access
esssorie
es
Dual power
owerr supply module
m du
mo dulle ....................................................................................................................................... 27 - 12
Communication
nicat
atio
at ion
io n devices,
devic software and accessories ................................................................................................. 27 - 13

Dimensions ............................................................................................................ 27 - 14
Wiring diagrams ...................................................................................................... 27 - 15
Technical characteristics ............................................................................................ 27 - 18
27

Page 27-7 Page 27-7 Page 27-8

ATL100 ATL500 ATL600 - ATL601


• Modular housing • Management of two power sources • Management of two power sources
• Management of two power sources • Self-seeking power supply • AC power supply
• Single-phase control. • 2 programmable digital inputs • 6 programmable digital inputs
• 3 programmable digital outputs • 7 programmable relay outputs.
• Built-in NFC technology for parameter
settings with App .

Page 27-8 Page 27-9 Page 27-10

ATL610 ATL800 ATL900


• Management of two power sources • Management of 2 power sources and 1 tie • Management of 3 power sources and 2 tie
• AC and DC power supply breaker breakers
• 6 programmable digital inputs • AC and DC power supply • AC and DC power supply
• 7 programmable relay outputs • 8 programmable digital inputs • 12 programmable digital inputs
• Real time clock (RTC) • 7 programmable relay outputs • 4 current inputs
• Expandable with EXP series modules • Built-in NFC technology for parameter settings • 10 programmable relay outputs
(inputs and outputs, communication ports). with App • 1 programmable static output
• Real time clock (RTC) • Built-in NFC technology for parameter
• Non-priority load management settings with App
• Closed transition with brief parallel • Real time clock (RTC)
configuration • Non-priority load management
• Built-in RS485 communication • Closed transition with brief parallel
• Built-in PLC logic configuration
• Expandable with EXP series modules (inputs • Built-in RS485 communication
and outputs, communication ports). • Built-in PLC logic
• Expandable with EXP series modules
(inputs and outputs, communication ports).

Page 27-11 Page 27-12

ATP ATLDPS1
• Enclosed automatic transfer switches from • Module specifically designed to control power
45 to 160A supply voltage of motorised circuit breakers
• Management of 2 power sources and changeover switches
• Four-pole interlocked contactors • Continuous monitoring of supply line status
• Automatic transfer switch controller type ATL600 • Management via microcontroller
• Dual power supply module type ATLDPS1 for the management.
measurement and control of voltages present at
supply inputs
• Miniature circuit breakers for the protection of the
measuring lines
• Metallic enclosure IP65.
27 Automatic transfer switch controllers
For 2 power sources.
ATL500

SIMPLE AND
ND READY TO USE
SYNOPTIC
The frontal synoptic provides
a simple and clear view of
the status of the plant,
signalling with LEDs the FRRONTAL KEYBOARD
status of the power sources Withh the frontal keyboard it is possible to
and the status of the seleect the operating mode (manual or
changeover devices. autoomatic) and command manually the
swittching between the power sources
direectly with the buttons I-0-II on the front,
withhout need to program any setting on the
conttroller.

SELF-SEEKING POWER SUPPLY NFC CONNECTION


ATL500 has a self-seeking power supply, which automatically selects the best of ATL500 is provided with built-in NFC connectivity for the programming via
the two available power sources for the internal supply, taken directly from the Android and iOS smart devices (smartphone and tablets) with the LOVATO NFC
two measuring inputs (rated voltage 110...240VAC L-N), without the need of an App in a simple, fast and innovative way, which does not need any connection
external circuit or dual power supply module for the selection of the power for cable and is able to operate even without power supply on the controller.
the auxiliary supply. With the LOVATO NFC App it is possible to configure:
– system parameters: rated system voltage, rated frequency, type of wiring,
ATL500 voltage control mode, etc.
L1
– password for the protection of the access to the settings
2 L2 INTERNAL
LINE 1 AUXILIARY – changeover settings: priority line selection, interlock times, feedback delays,
3 L3 SUPPLY
etc.
4 N
– protection thresholds and tripping delays: min/max voltage, min/max
5
frequency, phase sequence, asymmetry
L1 OUT 1 OUT 2 OUT 3 DIGITAL INPUTS
6
– function of the programmable digital inputs and outputs
L2 INTERNAL
INP 1
INP 2

COM

7
LINE 2 AUXILIARY – function of the potentiometers
L3 SUPPLY
8
– alarms properties.
N
11
12

13
17
18

20
21

14
15
16

THREE-PHASE WITH NEUTRAL VOLTAGE MONITORING INPUTS


ATL500 is provided with three-phase with neutral voltage monitoring inputs for
a complete monitoring of the voltage and frequency of both power sources.
The controller can be configured to be used in three-phase with neutral,
single-phase or two-phase systems.

PROGRAMMABLE DIGITAL INPUTS AND OUTPUTS


The function of the programmable digital inputs and outputs can be configured
via NFC to satisfy different application needs.

HIGH PROTECTION DEGREE POTENTIOMETERS


The controller front and the optional frame seal have been designed to warrant ATL500 is provided with two potentiometers on the back, one for each power
an IP65 protection degree. source, which can be used for the manual setting of the line presence delays
(default setting) or to set the tripping delays of the protection thresholds, in
alternative to the setting via NFC. The function of the potentiometers can be
modified with the LOVATO NFC App.

LINE 1 LINE 2
0...60 sec 0...60 sec

27-2
27 Automatic transfer switch controllers
For 2 power sources.
ATL600 - ATL601 - ATL610

NON-STOP
OP CONTROL!
BACKLIT GRAPHIC
LCD DISPLAY
128x80 pixel, with excellent
legibility with adjustable
brightness and display of
events, alarms and
measurements in 5 languagess:
English, Italian, French,
Spanish and German.

OPTICA AL COMMUNICATION
PORT
The optical port on the front, using a standard USB
or Wi-Fi pooint, permits to communication with a PC,
smartphone and tablet, to carry out programming,
diagnosticss and data download without removing
power to thhe electric panel.

COMPACT SIZE FIXING SYSTEM INPUTS, OUTPUTS, INTERNAL VARIABLES, COUNTERS


The inputs and outputs can be configured by the user to manage the various
application requirements. Also available to the user are limit thresholds,
counters, user alarms and remote control variables (ATL610 only) to customise
the control functions. The limit and counter statuses, if enabled, are shown in
the appropriate pages on the display.

CALENDAR CLOCK (ATL610)


Built-in calendar-clock with backup reserve power.

DUAL POWER SUPPLY (ATL610)


110...240VAC and 12/24VDC supply.

EXPANDABILITY (ATL610)
Basic functions of the transfer switch controllers can be easily extended using
EXP series expansion modules:
44mmm - Relay outputs
1.73”” - Digital and analogue inputs and outputs
9mm
m - Opto-isolated RS232 interface
0.35”
3 - Opto-isolated RS485 interface
- Opto-isolated Ethernet interface.
Using modules dedicated to communications the device can be controlled and
supervised by the and softwares and controlled remotely
and configured with the software.

The fixing system with metal


Slim frame profile and reduced
screws guarantees excellent, lasting
total depth simplify installation of
hold over time.
the transfer switch controller also in
very compact electric panels.
STATISTICS AND EVENTS
The recorded statistical data is
HIGH PROTECTION DEGREE
available to the user for
The controller front and the optional
understanding how the system
frame seal have been designed to
operates. A cyclical internal memory
warrant an IP65 protection degree.
records up to 100 events.

27
MAINTENANCE COUNTERS
EMERGENCY DEMAND MAX
ATL features two counters used for 2
maintenance; the first monitors the SUPERVISION FOR STANDBY
operating time and the second GENERATING SET
counts the number of switching In applications where one of the two
operations. Exceeding the limit set supply sources is a generating set,
on the counters activates the the transfer switch controller has
corresponding alarm. specific functions to supervise the
generator starting and stopping
operations.
12/24VDC battery supply input (only for ATL601 and ATL610)

27-3
27 Automatic transfer switch controllers
For 2 and 3 power sources.
ATL800 - ATL900

VERSATILE CONFIGURATION
ATL800
Managementt of 2 energy sources and 1 tie breaker.
6 preconfigurred system layouts.
Non-priority lo
oad management.
Management of transition with brief parallel configuration.
RS485 built-in
n.
Built-in NFC technology
t for parameter settings with
App .
App and softw ware: , , , .

GRAPHIC LCD AND 8 LANGUAGE INPUTS, OUTPUTS, INTERNAL STATISTICS AND EVENTS PROGRAMMABLE PLC LOGIC
TEXT VARIABLES, COUNTERS The statistical data recorded by the With the built-in PLC functions, new
The backlit graphic display simplifies The input and output functions are transfer switch controller is switching logic can be defined
the user interface and permits good preconfigured with the most available to the user for analysing through appropriate combinations
visibility in environments with poor frequently used settings; the user the performance of the switching of input, output and internal variable
lighting. For ATL800 and ATL900 can easily modify the predefined system. A cyclical internal memory signals.
the texts are available in 8 configuration and adapt the switch records up to 250 events, providing
languages: English, Italian, French, to their application requirements. All useful information on the history of
Spanish, German, Portuguese, the inputs and outputs can be the system controlled. TIMER
Polish and Russian. configured. There are various types 8 timer variables are available for
The new interface allows the user to of programmable internal variables: use in the system’s PLC logic, in
see, clearly and simply: - Limit thresholds BUILT-IN CALENDAR CLOCK combination with the outputs or
- System status - Remote control variables A built-in calendar clock with user alarms. Each timer variable has
- Measurements - User alarms backup reserve energy permits each an input variable that controls it.
- Statistical data - Programmable counters event to be identified using the time When this variable changes state,
- Threshold control - Timer. and date on which it occurred. so does the timer variable, but it
- Alarm pop-up windows. The limit, counter and enabled timer remains in the new state only for the
statuses are available for display on time specified then returns
dedicated pages. automatically to the starting
BUILT-IN RS485 COMMUNICATION
condition.
Thanks to the built-in RS485
communication port, ATL800 and
ATL900 are already set up for NFC CONNECTION
remote supervision and control. In Programming the parameters via
addition to this communication port, tablet and smartphone is now
the user can install two further possible also through NFC wireless
types of communication from those technology.
available in the EXP... expansion Bringing a smartphone or tablet
MAINTENANCE COUNTERS modules. with NFC connection enabled close
Two counters can be used for to the display of the ATL800-900
scheduling maintenance on the activates the App LOVATO and
transfer systems installed: the first DUAL AC/DC SUPPLY the switch connected is recognised
for recording the operating time and ATL switches can deal with all automatically. It will then be
the second for monitoring the supply solutions demanded by the possible to modify the parameters
number of switching operations. market. The best and safest solution and program the ATL.
Exceeding the limit set on the is the simultaneous use of AC and
counters activates the DC supply. The switches can then
corresponding alarm. be supplied by the AC line available USB AND WI-FI COMMUNICATION
and, during switching, in the INTERFACES
absence of the AC line, the switch ATL800 and ATL900 feature a front
will be supplied by the battery via optical port for programming via
HIGH PROTECTION RATING the DC inputs. Non-stop control! AC optional USB (CX01) or Wi-Fi
The controller front and the frame supply ensures supply during (CX02) communication interface.
seal have been designed to warrant system monitoring and DC supply Advantages:
an IP65 protection degree. guarantees constant supply during - Not necessary to disconnect the
switching. supply from the panel to connect
to the switch
- Electrical safety (no physical
connection)
- Convenience of operating on the
front.

27-4
27 Automatic transfer switch controllers
For 2 and 3 power sources.
ATL800 - ATL900

FULL OPTIONAL, FOR EVERY REQUIREMENT


ATL900
Management of 3 energy power sources and 2 tie breakers.
4 current inputs for the three-phases and neutral.
14 preconfigured d system layouts.
Non-priority loadd management.
Management off transition with brief parallel configuration.
RS485 built-in.
Built-in NFC techhnology for parameter settings with App .
App and softwa are: , , , .

WI-FI COMMUNICATION THREE TYPES OF TRANSITION AVAILABLE


INTERFACE (VIA CX02) Open transition In-phase transition Closed transition
This connection can be used to: The switch transfers the load between The switch transfers the load between With switches and external protections,
- Copy the parameters the two sources, interrupting the the two sources, interrupting the configured appropriately, the two
All the parameters of the ATL can supply for a period of time that can be supply for a period of time that can be sources will be synchronised (where
be saved in the CX02 memory and programmed by the user. programmed. In this case the load is possible) or spontaneous
if necessary loaded back into the passed to a new source if spontaneous synchronisation will be expected within
same device (backup function) or synchronisation is found; a limit time. In presence of all
a new switch (replication of the the amplitude, phase and frequency of synchronisation conditions the load will
configuration). the two sources must not differ from be transferred with closed transition
- Clone the device settings the maximum value set. and instantaneous parallel without
In addition to copying the interrupting supply.
parameters, the current values of
the statistical data, counters and
events can be saved in the
memory in order to completely
replicate an ATL on another device
of the same type or restore the
ATL to a previously saved state.

ATL900: management of three sources and two tie breakers EXPANDABILITY


A single transfer switch controller can ATL800 and ATL900 functionality
be used to manage applications which can be extended thanks to the EXP...
in the past required several transfer series expansion modules. Three
switch controllers in a cascade expansion slots are available, and
connection. while the switch is restarting the
24 system layouts are available. modules are recognised and
configured entirely automatically.
4 current inputs The following EXP... modules are
The current inputs permit the available:
monitoring of the demand load and - Digital I/O modules EXP10...
defining of the correct switching - Analogue I/O modules
strategy. Knowing the power demanded - USB, RS232, RS485, Ethernet and
by the system and the rated power of Profibus communication modules
the sources, ATL900 can - GPRS/GSM modem
select the best source available that can Since the additional modules are
supply the loads correctly. shared with other LOVATO Electric 27
products, it is possible to save in
management costs, guaranteeing
flexibility and ease of installation,
above all when the system has
already been commissioned.
MAX
3

27-5
27 Automatic transfer switch controllers
ATL series

ATL100 ATL500 ATL600 - ATL601 ATL610 ATL800 ATL900


POWER SUPPLY
Rated DC supply voltage –– –– 12/24VDC (ATL601) 12/24VDC 12/24/48VDC 12/24/48VDC
Rated AC supply voltage 110...230VAC 110...240VAC 110...240VAC (ATL600) 110...240VAC 110...240VAC 110...240VAC
(self-powered)
Frequency 45...66Hz 45...66Hz 45...66Hz (ATL600) 45...66Hz 45...66Hz 45...66Hz
FRONT PANEL / HOUSING
Backlit display –– –– LCD graphic 128x80 pixel LCD graphic 128x80 pixel LCD graphic 128x80 pixel LCD graphic 128x112 pixel
Languages –– –– 5 5 8 8
Size Modular housing (3U) 144x144x52.2mm/ 144x144x52.2mm/ 144x144x52.2mm/ 240x180x45mm/ 240x180x45mm/
5.67x5.67x2.05” 5.67x5.67x2.05” 5.67x5.67x2.05” 9.45x7.09x1.77” 9.45x7.09x1.77”
Degree of protection IP40 on front / IP40 / optional IP65 IP40 / optional IP65 IP40 / optional IP65 IP65 IP65
IP20 terminals
Expandable with EXP... series modules –– –– –– 2 modules 3 modules 3 modules
VOLTAGE AND CURRENT MEASUREMENT INPUT
Power sources that can be controlled –– 2 2 2 2 3
Voltage inputs per line 1 phase + neutral 3 phases + neutral 3 phases + neutral 3 phases + neutral 3 phases + neutral 3 phases + neutral
Rated voltage Ue 110...230VAC 110...240VAC L-N 480VAC 480VAC 600VAC 600VAC
Current inputs –– –– –– –– –– 4 (by 5A or 1A CTs)
Frequency range 45...66Hz 45...66Hz 45...66Hz 45...66Hz 45...66Hz 45...66Hz
BUILT-IN DIGITAL INPUTS AND OUTPUTS
Number of inputs –– 2 6 6 8 12
Number of outputs 3 3 7 7 7 11
Contact configuration 3 NO 2 NO + 1 changeover 6 NO + 1 changeover 6 NO + 1 changeover 4 NO + 3 changeover 6 NO + 4 changeover +
1 SSR
INTERFACE
Programming with NFC technology ––  –– ––  
Front optical USB communication port –– ––  with CX01  with CX01  with CX01  with CX01
Front optical Wi-Fi communication port –– ––  with CX02  with CX02  with CX02  with CX02
USB communication –– –– ––  EXP1010  EXP1010  EXP1010
RS232 communication –– –– ––  EXP1011  EXP1011  EXP1011
RS485 communication –– –– ––  EXP1012  (built-in)  (built-in)
Ethernet communication –– –– ––  EXP1013  EXP1013  EXP1013
Profibus communication –– –– ––  EXP1014  EXP1014  EXP1014
Communication via Modem –– –– –– ––  EXP1015  EXP1015
FUNCTIONS
Number of tie breakers that can be managed –– –– –– –– 1 2
Programmable source type (utility or generation) ––     
Closed transition –– –– –– ––  
Non-priority load management –– –– –– ––  
Switching management with power thresholds –– –– –– –– –– 
PLC logic –– –– –– ––  
Timers –– –– –– ––  
System layout available on display –– –– –– –– 6 14
Custom system layouts –– –– –– ––  
User alarms –– ––    
Limits –– ––    
Counters –– ––    
Event logging –– –– 100 100 250 250
Real time clock with backup reserve energy –– –– ––   
Acoustic alarms –– –– –– ––  
Analogue inputs –– –– –– ––  EXP1004  EXP1004
Analogue outputs –– –– –– ––  EXP1005  EXP1005
Accessory for remote alarm status –– –– –– –– ––  RGKRR

27-6
27 Automatic transfer switch controllers
For 2 power sources

Non expandable General characteristics ATL100


per ATL100 is a single-phase automatic transfer switch controller
modular pkg in modular housing. It monitors 2 single-phase voltage
inputs and it connects to the output the line that is within the
n° [kg] limits. The priority line is the line 1. The 2 outputs can
ATL100 Automatic transfer switch 1 0.300 control contactors or motorized changeover switches to
controller for 2 power perform the transfer between the lines.
sources with single-phase
control, modular housing, Operational characteristics ATL100
110...230VAC supply – Self-powered
– Input voltage range: 80...300VAC
ATL100 – Frequency range: 45...66Hz
– 2 relay outputs with 1 NO contact 4A 250VAC
– 1 relay output with 1 NO contact 3A 250VAC.

Non expandable Order code Description Qty Wt General characteristics ATL500


per ATL500 is an automatic transfer switch controller for the
flush-mount pkg automatic or manual switching of the load from the MAIN
LINE to a stand-by or emergency SECONDARY LINE and vice
n° [kg] versa.
ATL500 Automatic transfer switch 1 0.580 With the integrated outputs, it is possible to control
controller with NFC technology contactors or motorised changeover switches.
and synoptic, for 2 power The main features are:
new sources with three-phase
control (144x144mm/5.7x5.7”),
– Self-seeking power supply from the two measurement
inputs
self-seeking power supply – Measurement inputs for three-phase + neutral voltage
110...240VAC values, also suitable for 1 and 2 phase lines
– Synoptic on front with LEDs for a simple and clear
visualisation of the status of the lines and the changeover
devices
– Parameter programming via NFC technology and
ATL500 App LOVATO downloadable from Google Play Store
and App Store. With App LOVATO is possible to set:
rated system parameters, line control settings,
changeover settings, password and I/O functions
– Frontal keyboard for the selection of the operating mode
and the manual command of the changeover devices
– 2 programmable digital inputs
– 3 programmable relay outputs
Accessories Order code Description Qty Wt – Potentiometers on the back for the manual setting of the
per line presence delays or the tripping delays of the
pkg protection thresholds.
n° [kg]
EXP8001 IP65 gasket seal for 1 0.009 Operational characteristics ATL500
ATL500/600/601/610 – Power supply:
• Self-seeking power supply from the measurement inputs
110...240VAC L-N (range: 90...300VAC L-N)
– Voltage measurement inputs:
• Rated voltage Ue: 110...240VAC L-N / 190...415VAC L-L
• Measuring range: 90...300VAC L-N / 155...519VAC L-L
• Frequency range: 45...66Hz
– Programmable digital inputs:
EXP8001 • Negative inputs
– Programmable relay outputs:
• 2 each with 1 normally open contact (NO - SPST) rated
8A 250VAC
• 1 with 1 changeover contact (NO/NC - SPDT) rated
8A 250VAC
– Enclosure:
• Flush-mount housing: 144x144mm/5.7x5.7"
• IEC degree of protection: IP40 on front; IP65 with
optional seal EXP8001; IP20 at rear.

Certifications and compliance


Certifications obtained: EAC, RCM (only for ATL500).
Compliant with standards: IEC/EN/BS 61010-1,
IEC/EN/BS 61010-2-030, IEC/EN/BS 60947-1,
IEC/EN/BS 60947-6-1, IEC/EN/BS 61000-6-2,
IEC/EN/BS 61000-6-3.

27

Accessories Dimensions Wiring diagrams Technical characteristics


page 27-12 and 13 page 27-14 page 27-15 page 27-18 27-7
27 Automatic transfer switch controllers
For 2 power sources

Non expandable Order code Description Qty Wt General characteristics ATL600 - ATL601 - ATL610
per The automatic transfer switch controllers ATL600 / ATL601 /
pkg ATL610 are used for the automatic or manual switching of
the load from the MAIN LINE to a stand-by or emergency
n° [kg] SECONDARY LINE and vice versa. They have two outputs for
ATL600 Automatic transfer switch 1 0.600 the “automatic” and/or “manual” control of contactors or
controller with LCD display and motorised circuit breakers and switches.
optical port for 2 power sources The main features are:
with three-phase control – Supply input:
(144x144mm/5.7x5.7”), • Single in AC for ATL600
110...240VAC supply • Single in DC for ATL601
ATL601 Automatic transfer switch 1 0.600 • Dual in AC and DC for ATL610
controller with LCD display and – Measurement inputs for three-phase + neutral voltage
optical port for 2 power sources values; also suitable for 1 and 2 phase lines
with three-phase control – 128x80 pixel backlit graphic LCD to view measurements,
ATL600 events and alarms in 5 languages (English, Italian, French,
(144x144mm/5.7x5.7”),
12...24VDC supply Spanish and German)
– 2 status indication LEDs
– 6 programmable digital inputs
– 7 programmable relay outputs
Expandable with Order code Description Qty Wt – Viewing of L-L and L-N voltage values of the controlled
per lines
EXP... modules pkg – Status viewing of contactor or motorised circuit breakers
and switches
n° [kg] – Configuration programming of lines, control and
ATL610 Automatic transfer switch 1 0.680 supervision parameters for emergency demand of
controller with LCD display and generating set
optical port for 2 power sources – Event logging
with three-phase control – Microprocessor supervision of functions; including virtual
(144x144mm/5.7x5.7”), real time clock for ATL610
110...240VAC and 12/24VDC, – Communication interface by front optical port with CX01
supply expandable with or CX02 dongle using USB or Wi-Fi
EXP... series modules – Compatible with , supervision and energy
management software, remote control and
configuration software and with the application for
Order code Description Android/iOS
ATL610 – Modbus-RTU, ASCII and TCP communication protocol.
EXPANSION MODULES FOR ATL610
Snap on fixing of two modules on ATL610 rear. CONTROL FUNCTIONS OF THE LINES
Inputs and outputs. – Phase sequence and phase loss
– Minimum and maximum voltage
EXP1000 4 opto-isolated digital inputs – Voltage asymmetry
EXP1001 4 opto-isolated static outputs – Minimum and maximum frequency.
EXP1002 2 digital inputs and 2 static outputs,
opto-isolated Operational characteristics ATL600 - ATL601 - ATL610
– Power supply:
EXP1003 2 relay outputs with changeover contact • Power supply voltage: 110...240VAC (ATL600);
5A 250VAC 12/24VDC (ATL601); 12/24VDC - 110...240VAC (ATL610)
EXP1006 2 relay outputs, normally open contact – Voltage measurement inputs:
EXP10... 5A 250VAC • Rated voltage Ue: 100...480VAC (L-L)
EXP1007 3 relay outputs, normally open contact • Measuring range: 50...576VAC (L-L)
5A 250VAC • Frequency range: 45...66Hz
– Programmable digital inputs:
EXP1008 2 opto-isolated digital inputs and 2 5A relay
• Negative inputs
outputs, normally open contact 250VAC – Programmable relay outputs:
Communication ports. • 6 each with 1 normally open contact (NO - SPST) rated
EXP1010 Opto-isolated USB interface 8A 250VAC
• 1 with changeover contact (NO/NC - SPDT) rated 8A
EXP1011 Opto-isolated RS232 interface 250VAC
EXP1012 Opto-isolated RS485 interface – Enclosure:
EXP1013 Opto-isolated Ethernet interface • Flush-mount housing: 144x144mm/5.7x5.7”
• IEC degree of protection: IP40 on front; IP65 with
EXP1014 Opto-isolated Profibus-DP interface optional seal EXP8001; IP20 at rear.

EXP... expansion modules fixing on ATL610 Certifications and compliance


Certifications obtained: cULus, RCM, LOVAG (only for
ATL600 - ATL610), EAC.
Compliant with standards: IEC/EN/BS 61000-6-3 (only for
ATL601), IEC/EN/BS 61000-6-4 (only for ATL600 - ATL610),
IEC/EN/BS 60947-1, IEC/EN/BS 60947-6-1,
IEC/EN/BS 61000-6-2, IEC/EN/BS 61000-6-3, UL508,
CSA C22.2 n° 14.

MAX
2

Accessories Dimensions Wiring diagrams Technical characteristics


27-8 page 27-12 and 13 page 27-14 page 27-15 page 27-18
27 Automatic transfer switch controllers
For 2 power sources

Expandable with Order code Description Qty Wt General characteristics


per The automatic transfer switch controller ATL800 is used for
EXP... modules pkg the automatic or manual switching of the load between two
lines in accordance with the selected switching logic. It has
n° [kg] outputs for the “automatic” and/or “manual” control of
ATL800 Automatic transfer switch 1 1.000 contactors or motorised circuit breakers and switches.
controller (240x180mm/ It can also manage a third control device as tie breaker or
9.45”-7.09”) with LCD display, non-priority load management. The layout and system status
optical port and NFC for 2 lines are displayed directly on the graphic LCD.
control and 1 tie breaker, The main features are:
110...240VAC supply and – AC and DC supply inputs
12/24/48VDC, expandable – Measurement inputs for three-phase + neutral voltage
with EXP... series modules values; also suitable for 1 and 2 phase lines
– 128x80 pixel backlit graphic LCD to view measurements,
ATL800 events and alarms in 8 languages (English, Italian, French,
Spanish, German, Portuguese, Polish and Russian)
– Active operating mode indicator LED
– Viewing of L-L and L-N voltage values of the controlled
lines
– Viewing the status of contactors or motorised circuit
Order code Description breakers both via display and LED
– 6 system layouts available
EXPANSION MODULES. – Management of a tie breaker
Snap on fixing of three modules on rear of ATL800. – 8 programmable digital inputs
Digital inputs and outputs. – 7 programmable relay outputs
EXP1000 4 opto-isolated digital inputs – Viewing of L-L and L-N voltage values of the controlled
lines
EXP1001 4 opto-isolated static outputs – Configuration programming of lines, type of source
EXP1002 2 digital inputs and 2 static outputs, (line/generator), control and supervision parameters for
opto-isolated emergency demand of generating set
EXP10... – Possibility of transferring load with closed transition and
EXP1003 2 relay outputs 5A 250VAC, changeover contact
spontaneous or controlled genset synchronisation
EXP1006 2 relay outputs, normally open contact – Non-priority load management
5A 250VAC – Built-in programmable PLC logic
EXP1007 3 relay outputs, normally open contact – Built-in RS485 communication
5A 250VAC – Event logging
EXP1008 2 opto-isolated digital inputs and 2 5A relay – Virtual calendar clock (RTC)
outputs, normally open contact 250VAC – Communication interface by front optical port with CX01
or CX02 dongle using USB or Wi-Fi
Analogue inputs and outputs. – Parameter programming via NFC technology and the App
EXP1004 2 opto-isolated analogue inputs 0/4...20mA or downloadable from Google Play Store and App Store
PT100 or 0...10V or 0...+-5V – Compatible with , supervision and energy
EXP1005 2 opto-isolated analogue outputs 0/4...20mA or management software, remote control and
0...10V or 0...+-5V configuration software and with the application for
Android/iOS
Communication ports. – Modbus-RTU, ASCII and TCP communication protocol.
EXP1010 Opto-isolated USB interface
EXP1011 Opto-isolated RS232 interface CONTROL FUNCTIONS OF THE LINES
– Phase sequence and phase loss
EXP1012 Opto-isolated RS485 interface – Minimum and maximum voltage
EXP1013 Opto-isolated Ethernet interface – Voltage asymmetry
EXP1014 Opto-isolated Profibus-DP interface – Minimum and maximum frequency.

Operational characteristics
EXP... expansion module fixing on ATL800 – Power supply:
• Power supply voltage: 100...240VAC;
12/24/48VDC
– Voltage measurement inputs:
• Rated voltage Ue: 100...600VAC (L-L)
• Frequency range: 45...66Hz
– Programmable digital inputs:
• Negative inputs
– Programmable relay outputs:
• 2 each with 1 normally open contact (NO - SPST) rated
12A 250VAC
MAX • 2 each with 1 normally open contact (NO - SPST) rated
3 8A 250VAC
• 3 each with 1 changeover contact (NO/NC - SPDT)
8A 250VAC
– Enclosure:
• Flush-mount housing: 180x240mm/7.09x9.45”
• IEC degree of protection: IP65 on front; IP20 at back.

Certifications and compliance


Certifications obtained: cULus, EAC, RCM, LOVAG.
27
Compliant with standards: IEC/EN/BS 61010-1,
IEC/EN/BS 61010-2-030, IEC/EN/BS 61000-6-2,
IEC/EN/BS 61000-6-4, IEC/EN/BS 60947-1,
IEC/EN/BS 60947-6-1, UL508 and CSA C22.2 n° 14.

Accessories Dimensions Wiring diagrams Technical characteristics


page 27-12 and 13 page 27-14 page 27-16 page 27-18 27-9
27 Automatic transfer switch controllers
For 3 power sources

Expandable with Order code Description Qty Wt General characteristics


per The automatic transfer switch controller ATL900 is used for
EXP... modules pkg the automatic or manual switching of the load between three
lines in accordance with the selected switching logic. It has
n° [kg] outputs for the “automatic” and/or “manual” control of
ATL900 Automatic transfer switch 1 1.800 contactors or motorised circuit breakers and switches. It can
controller (240x180mm/ also manage two more control devices as tie breakers or
9.45”-7.09”) with LCD display, non-priority load management. It has four current inputs for
optical port and NFC for 3 lines managing switching with power thresholds. The layout and
control and 2 tie breakers, system status are displayed directly on the graphic LCD.
110...240VAC supply and The main features are:
12/24/48VDC, expandable – AC and DC supply inputs
with EXP... series modules – Measurement inputs for three-phase + neutral voltage
values; also suitable for 1 and 2 phase lines
– 4 current measurement inputs
ATL900
– 128x112 pixel backlit graphic LCD to view measurements,
events and alarms in 8 languages (English, Italian, French,
Spanish, German, Portuguese, Polish and Russian)
– Active operating mode indicator LED
– Viewing of L-L and L-N voltage values of the controlled
lines
Order code Description – Viewing the status of contactors or motorised circuit
breakers both via display and LED
EXPANSION MODULES. – 6 system layouts available
– Management of a tie breaker
Snap on fixing of three modules on rear of ATL900.
– 12 programmable digital inputs
Digital inputs and outputs.
– 10 programmable relay outputs
EXP1000 4 opto-isolated digital inputs – 1 static output
EXP1001 4 opto-isolated static outputs – Viewing of L-L and L-N voltage values of the controlled
lines
EXP1002 2 digital inputs and 2 static outputs, – Configuration programming of lines, type of source
EXP10... opto-isolated (line/generator), control and supervision parameters for
EXP1003 2 relay outputs 5A 250VAC, changeover contact emergency demand of generating set
EXP1006 2 relay outputs, normally open contact – Possibility of transferring load with closed transition and
spontaneous or controlled genset synchronisation
5A 250VAC
– Non-priority load management
EXP1007 3 relay outputs, normally open contact – Built-in programmable PLC logic
5A 250VAC – Built-in RS485 communication
EXP1008 2 opto-isolated digital inputs and 2 5A relay – Event logging
outputs, normally open contact 250VAC – Virtual calendar clock (RTC)
– Communication interface by front optical port using USB
Analogue inputs and outputs. CX01 or Wi-Fi CX02 dongle
EXP1004 2 opto-isolated analogue inputs 0/4...20mA or – Parameter programming via NFC technology and the App
PT100 or 0...10V or 0...+-5V downloadable from Google Play Store and App Store
EXP1005 2 opto-isolated analogue outputs 0/4...20mA or – Compatible with , supervision and energy
0...10V or 0...+-5V management software, remote control and
configuration software and with the application for
Communication ports. Android/iOS
EXP1010 Opto-isolated USB interface – Modbus-RTU ASCII and TCP communication protocol.
EXP1011 Opto-isolated RS232 interface CONTROL FUNCTIONS OF THE LINES
EXP1012 Opto-isolated RS485 interface – Phase sequence and phase loss
– Minimum and maximum voltage
EXP1013 Opto-isolated Ethernet interface – Voltage asymmetry
EXP1014 Opto-isolated Profibus-DP interface – Minimum and maximum frequency.
EXP1015 GPRS/GSM modem Operational characteristics
– Power supply:
• Power supply voltage: 100...240VAC;
EXP... expansion module fixing on ATL900 12/24/48VDC
– Voltage measurement inputs:
• Rated voltage Ue: 100...600VAC (L-L)
• Frequency range: 45...665Hz
– Programmable digital inputs:
• Negative inputs
– Programmable relay outputs:
• 3 each with 1 normally open contact (NO - SPST) rated
12A 250VAC
• 3 each with 1 normally open contact (NO - SPST) rated
8A 250VAC
MAX • 4 each with 1 changeover contact (NO/NC - SPDT)
3 8A 250VAC
• 1 30VDC 50mA static output
– Enclosure:
• Flush-mount housing: 180x240mm/5.7x5.7”
• IEC degree of protection: IP65 on front; IP20 at back.
, , , and software
and App
See section 29.
EXP expansion modules
See page 30-2.
Certifications and compliance
Certifications obtained: cULus, EAC, RCM, LOVAG.
Compliant with standards: IEC/EN/BS 61010-1,
IEC/EN/BS 61010-2-030, IEC/EN/BS 61000-6-2,
IEC/EN/BS 61000-6-4, IEC/EN/BS 60947-1,
IEC/EN/BS 60947-6-1, UL508 and CSA C22.2 n° 14.

Accessories Dimensions Wiring diagrams Technical characteristics


27-10 page 27-12 and 13 page 27-14 page 27-17 page 27-18
27 Automatic transfer switch controllers
Enclosed automatic transfer switches ATS

Order code Opera- Power Dimensions General characteristics


ting (400V) (HxWxD) The enclosed automatic transfer switches ATP series are
current provided in metallic enclosure IP65, complete with automatic
AC1 transfer switch controller type ATL600, four-pole contactors
BF series, dual power supply module type ATLDPS1 and
[A] [kVA] [mm (in)] miniature circuit breakers (MCB) type P1MB for the
Auxiliary supply 230VAC, with four-pole contactors versions. protection of the measuring lines.
ATP0045T4A230C600A 45 31 500x400x200 They are used for the automatic or manual switching of the
(19.68x15.75x7.87”) load between two lines (“MAIN LINE” and “SECONDARY
LINE”).
ATP0060T4A230C600A 60 42 500x400x200 They are available in versions from 45 to 160A in four-pole
(19.68x15.75x7.87”) configuration.
ATP0080T4A230C600A 80 55 500x400x200
(19.68x15.75x7.87”) CONTROL FUNCTIONS OF THE LINES
ATP0100T4A230C600A 100 69 500x400x200 – Phase sequence and phase loss
(19.68x15.75x7.87”) – Minimum and maximum voltage
– Voltage asymmetry
ATP0125T4A230C600A 125 87 600x400x250 – Minimum and maximum frequency
(23.62x15.75x9.84”)
ATP0160T4A230C600A 160 111 600x400x250 Operational characteristics
(23.62x15.75x9.84”) – Power supply:
• Auxiliary supply voltage: 230VAC (taken from the input
lines)
– Voltage measurement inputs:
• Rated voltage Ue: 100...480VAC (L-L)
ATP... • Measuring range: 50...576VAC (L-L)
• Frequency range: 45...66Hz
– 6 programmable digital inputs
– 7 programmable relay outputs:
• 6 each with 1 normally open contact (NO-SPST) rated 8A
250VAC
• 1 with 1 changeover contact (NO/NC – SPDT) rated 8A
250VAC
– Enclosure:
• Metallic enclosure
• Flanges for cable entries in the top and bottom sides
• PVC locking system with double-comb tool insert
• Opening with left hinges
• IEC degree of protection: IP65.

Certifications and compliance


Certification obtained: EAC.
Compliant with standards: IEC/EN/BS 61439-2.
MCBs for the protection of the
measuring lines P1MB series

Dual power supply module type


ATLDPS1

Automatic transfer
switch controller type
ATL600

27

Four-pole interlocked contactors


BF series

Terminal blocks

Accessories Dimensions
page 27-12 and 13 page 27-14 27-11
27 Automatic transfer switch controllers
Accessories

Dual power supply module Order code Description Qty Wt General characteristics
per ATLDPS1 is capable of measuring and controlling voltages at
pkg its inputs selecting the most ideal to connect to the output. It
is suitable to supply motorised circuit breakers and
n° [kg] changeover switches in automatic switching systems of 2
ATLDPS1 For controlling and 1 0.300 three-phase supply lines.
selecting supply for The two voltage inputs of the module are independent and
motorised circuit breakers insulated; each is capable of supplying the internal
and changeover switches measuring circuit managed by the microcontroller.
110...230VAC configurable It reduces the number of components and improves
installation safety.
Main ATLDPS1 features include:
– Voltage value selectable via bypass terminals
– Minimum and maximum voltage tripping thresholds
– 2 single-phase L+N inputs
– 1 single-phase L+N output
– L1 priority line
ATLDPS1
– Use with motorised control units powered at 110VAC or
230VAC
– Output voltage monitoring
– Internal relay self-diagnosis
– Indicating LEDs for abnormal conditions and status of
110VAC 230VAC inputs and outputs.
MIN MAX MIN MAX Operational characteristics
Line absent < 88V > 152V < 176V > 288V – Rated supply voltage: 110...230VAC configurable
– Frequency: 50/60Hz
Line present < 92V > 144V < 185V > 273V – Input voltage range: 80...300VAC
– Voltage tripping thresholds min / max: 80% and 120% of
Using the thresholds above ATLDPS1 outputs one of the power supplies available according to the logic preset value
shown in the table: – 2 line inputs L1-L2: Single-phase, between phase and
neutral
Status LED Status LED Output LED ATLDPS1 Alarm LED – Current output: 4A max.
Line 1 Line 1 Line 2 Line 2 Output contact Fault – Priority line: L1 when both input values are within limits
– Fixed delay time between line switching: 0.5s
OK ON <MIN OR >MAX OFF ON - from line 1 ON ON - OK Closed OFF – 4 status indication LEDs for voltage of each line within
OK ON OK ON ON - from line 1 ON ON - OK Closed OFF limits, voltage present at output, relay output anomaly
<MIN OR OFF OK ON ON - from line 2 ON ON - OK Closed OFF – Mounting: 35mm DIN rail (IEC/EN/BS 60715)
>MAX or screw-type by means of removable clips
– Modular housing, 3 module
<MIN OFF <MIN OFF OFF OFF OFF Open OFF – IEC degree of protection: IP40 on front; IP20 at rear.
>MAX OFF <MIN OR >MAX OFF OFF OFF ON Open ON
Certifications and compliance
<MIN OR OFF >MAX OFF OFF OFF ON Open ON
Certifications obtained: cULus, EAC, RCM, LOVAG.
>MAX
Compliant with standards: IEC/EN/BS 61010-2-030,
OK ON ON - Fault IEC/EN/BS 61010-2, IEC/EN/BS 61000-6-2,
>MIN ON OFF OFF Open ON
<MIN OR >MAX OFF Internal relays IEC/EN/BS 61000-6-4, IEC/EN/BS 60947-1,
IEC/EN/BS 60947-6-1, UL508 and C22.2 n° 14.
OK ON Open ON
<MIN OR OFF >MIN ON OFF OFF Internal
>MAX relays

Dimensions
27-12 page 27-14
27 Automatic transfer switch controllers
Accessories

Communication devices Order code Description Qty Wt General characteristics


per Communication devices for connection of LOVATO Electric
pkg products to personal computers, smartphones and tablets.
n° [kg] CX01
The USB/optical device, complete with cable, allows the
CX01 USB/optical device with 1 0.090
connection of products compatible with PCs without having
PC  ATL600/610/800/900 with
to disconnect the power supply from the electric panel.
optical port for programming
CX01 The PC identifies the connection as a standard USB.
data download, diagnostics and
firmware upgrade CX02
CX02 Wi-Fi device for connecting 1 0.090 By Wi-Fi connection, compatible LOVATO Electric products
PC  ATL600/610/800/900 with can be viewed on PCs, smartphones and tablets with no need
optical port for programming, for cabling.
data download, diagnostics and CX03
cloning Antenna compatible with major part of worldwide mobile
CX02
CX03 GSM penta-band antenna 1 0.090 networks thanks to the use of 850/900/1800/1900/
(850/900/1800/1900/2100MHz) 2100MHz frequencies.
Protection rating IP67. Fixing hole Ø10mm/3.94”.
Cable length 2.5mm/0.10”.
For dimensions, wiring schemes and technical characteristics,
refer to technical instructions in downloads section of local or
global websites www.LovatoElectric.com or consult Technical
CX03 support.

Software and accessories Order code Description Qty Wt Software


per By using the software, the quick setup of the switch
pkg controllers can be carried out via PC, avoiding parameter
programming errors.
n° [kg] The parameter programming of ATL600/610/800/900
EXP8001 Protective seal IP65 1 0.150 controllers can also be PC saved and quickly uploaded into
for ATL500/600/601/610 another device requiring the same programming.
For ATL610 - ATL800 - ATL900. It permits the correct operation of the system to be checked
through graphic and numerical display of the measurements
51C2 Connection cable 1 0.090 and controller status.
PC  ATL610/800/900 with
EXP1011, length 1.8m and softwares provide for the
51C4 Connection cable 1 0.147 supervision of the ATL600/610/800/900 transfer switch
PC  product RS232/RS485, controllers.
EXP8001 This software has structures and applications based on MS
length 1.8m
SQL relational databases, and the data can be consulted
EXCCON01 RS485/Ethernet converter, 1 0.400 using the most popular browsers.
12...48VDC, including kit It is a highly versatile system, simultaneously accessible to a
for DIN rail fixing large number of users/workstations via intranets, VPN or
EXCM4G01 RS485 gateway/4G modem, 1 0.340 Internet.
new 9...36VDC, including cable
for programming
See section 30 for details.

51C4 App for smartphone and tablet


For ATL900. The (Setup And Maintenance 1) application allows
RGKRR Remote unit for status 1 0.420 the user to program the controller, view alarm conditions,
and alarms, 12/24 VDC, send commands, read measurements, download statistical
12 relay outputs, data and events and send retrieved data by email. The
pulse input connection is made by Wi-Fi with a smartphone or tablet
using the CX02 dongle.
It is iOS and Android compatible.
For more details consult our Technical support.
For ATL500, ATL800 and ATL900, featuring built-in NFC
technology, the App LOVATO application is available for
EXCCON01 parameter programming, downloadable from Google Play
Store and App Store.

EXCCON01
The EXCCON01 converter allows “Slave” devices connected
on an RS485 network to interface with a “Master” featuring
Ethernet port:
– Kit comprising MOXA NPORT5230 converter and DIN rail
mounting accessory DK35
– Programming via web interface
EXCM4G01 – Power supply not included.
See section 31 for details.

EXCM4G01
The EXCM4G01 gateway allows “Slave” devices connected 27
on an RS485 network to interface with a “Master” via 4G
network. See section 31 for details.

RGKRR
It is an expansion unit for remote status and alarms.
RGKRR can be connected at a maximum distance of
1000m/39.37” using the static output of the ATL900.
RGK RR has 12 output relays, 7 normally open
RGKRR (2.5A 250VAC/C38) and 5 changeover contacts
(5A 250VAC/B300).
See section 28 for details.

27-13
27 Automatic transfer switch controllers
Dimensions [mm (in)]

AUTOMATIC TRANSFER SWITCH CONTROLLERS


ATL100 ATL500 - ATL600 - ATL601 - ATL610 Cutout
5 138 (5.43”)
(0.20”) 58 (2.28”) 144 (5.67”) 43
43.7 (1.69”)
(1.72”)
104.7 (4.12”)

45 (1.77”)
98.3 (3.87”)

90 (3.54”)

138 (5.43”)
137 (5.39”)

144 (5.67”)
64.5 (2.54”)
73 (2.87”) 9.2
(0.36”)
(2 max ATL610 only)

ATL800 - ATL900 Cutout


56.4 (2.22”)
240 (9.45”) 32.6 11.3 220 (8.66”)
(1.28”) (0.44”)
180 (7.09”)

160 (6.30”)
EXP10...
(3 max)

DUAL POWER SUPPLY MODULE EXPANSION UNIT CONVERTER GATEWAY


ATLDPS1 RGKRR EXCCON01 EXCM4G01
5 19.8 54.2 (2.13”) 22 29.5
(0.20”) 58 (2.28”)
(0.78”) (0.87”) 98 (3.85”) (1.16”)
43.7
(1.72”)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
L
H
TR

SG

OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 CAN


107 (4.21”)
96 (3.78”)
99.6 (3.92”)
104.7 (4.12”)

100.4 (3.95”)

OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 ON


45 (1.77”)
98.3 (3.87”)

90 (3.54”)

105 (4.13”)

D7
D7 D
D8 D9
D9 D
D1
D10 D1
D18 D
D2
D27 D2
D2

D2
D20 D2
D29 D2
D28 D1
D19 D2
D21 D3
D30 D2
D22

OUT 7 OUT 8 OUT 9 OUT 10 OUT 11 OUT 12 COM

REMOTE RELAYS UNIT


OUT 8 OUT 9 OUT 10 OUT 11 OUT 12 PULSE IN SUPPLY
+COM

__
+
INP

19 20 21 22 23 24 25 26 27 27 29 30 31 32 33 34 35 36

116 (4.57”) 46.5 (1.83”)


Ø4.2 (0.16”)
90 (3.54”)

ENCLOSED AUTOMATIC TRANSFER SWITCHES ATS


ATP0045... - ATP0060... - ATP0080... - ATP0100... ATP0125... - ATP0160...
400 (15.75”) 200 (8.16”) 400 (15.75”) 250 (9.84”)
500 (19.68”)

600 (23.62”)

27-14
27 Automatic transfer switch controllers
Wiring diagrams

ATL100
Connection diagrams
R1

N1

R2

N2
S1

S2
T1

T2
F1❶ F2❶
KM1 KM2

ALARM Y1 Y2
KM2 KM1 Open 230V~
Closed 110V~

KM1 KM2
R

N
S

T
L1

L2
N1

N2

F1❶ F2❶

L1

L2
N1

N2
L1/L L1/N L2/L L2/N F1❷ F2❷ F3❶ F4❶
LINE 1 LINE 2

ATL100 KM1 KM2


Automatic Transfer Switch
L1/L L1/N L2/L L2/N
LINE 1 LINE 2
T1/L T1/N T2/L T2/N
ATL100
Automatic Transfer Switch
KM1 Main Generator KM1 Main Generator
Contact Contact Contact Contact
KM2 KM1 T1/L T1/N T2/L T2/N KM2 KM1 Feedback Feedback
Feedback Feedback
KM2 KM1 KM2 KM2
KM2 KM1

KM1 KM2 7 6 5 4
7 6 5 4 KM1 KM2
KM1 KM2

Closing pos. II

Closing pos. I

Open all pos. 0


Closing pos. II

Common +
Closing pos. I

2 3 2 3
Open all pos. 0
Common +

2 3 2 3

2 (N) 2 (N)

Battery Battery
1 (L) - terminal 1 (L) - terminal
1 1 1 1
Pos. I Pos. II Pos. I Pos. II

Position feedback Position feedback


GEX69...C (External GEX10... on GE...E) GEX69...C (External GEX10... on GE...E)
Motorized Control Unit Motorized Control Unit

 4A maximum fuses
 1A maximum fuses

ATL500 
Connection diagrams Connection diagrams
Contactors control Motorised changeover switches control

 For the correct programming of inputs and outputs, consult the installation manuals available at www.LovatoElectric.com.

27

27-15
27 Automatic transfer switch controllers
Wiring diagrams

ATL600 - ATL601 - ATL610 


Connection diagrams Connection diagrams
Motorised breaker control Motorised changeover switches control
LINE 1 LINE 2 LINE 1 LINE 2
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
QF1 QF1
1 L1 1 L1
2 L2 2 L2
LINE 1 LINE 1
3 L3 3 L3
4 N 4 N

QF2
5 ATL6... QF2
5 ATL6...

ATL600
ATL610
L1 L1

ATL601
ATL610

ATL601
ATL610
ATL600
ATL610
6 L2 6 L2
LINE 2 LINE 2
7 L3 7 L3
8 N 8 N
AC DC AC DC
Q1 Q2 LINE 1 LINE 2 AUX DIGITAL INPUTS SUPPLY SUPPLY Q1 Q2 LINE 1 LINE 2 AUX DIGITAL INPUTS SUPPLY SUPPLY
_ _

INP 1
INP 2
INP 3
INP 4
INP 5
INP 6

INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
~~ + ~~ +

COM

COM
L1 N1 L2 N2 L1 N1 L2 N2

10
11
12
22
23
24

10
11
12
22
23
24
15
16
17
18
19
20
21

15
16
17
18
19
20
21
13
14

31
32

13
14

31
32
25
26
27
28
29
30

25
26
27
28
29
30
9

9
L L
OUT OUT
N N
DUAL POWER SUPPLY DUAL POWER SUPPLY
L1 L2 L3 N L1 L2 L3 N
LOAD LOAD

Q1

CLOSING 1
CLOSING 2
OPENING ALL
POWER SUPPLY
CLOSING

CLOSING
OPENING

OPENING

1 - 2 OPENED
1 CLOSED

2 CLOSED
POWER SUPPLY

POWER SUPPLY
TRIP COIL

TRIP COIL
TRIP

TRIP
STATUS

STATUS
INTERLOCK

INTERLOCK
Q2
Q1 Q2

 For the correct programming of inputs and outputs, consult the installation manuals available at www.LovatoElectric.com.

ATL800 
Power connection diagrams Power connection diagrams
Two breakers Two breakers and a tie breaker
LINE 1 LINE 2 LINE 1 LINE 2
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
QF1 QF1
1 L1 1 L1
2 L2 2 L2
LINE 1 LINE 1
3 L3 3 L3
4 N 4 N

QF2
5
6
L1
L2
ATL800 QF2
ATL800
5 L1
LINE 2
7 L3 6 L2
8 N LINE 2
7 L3
8 N
BRK1 BRK2

BRK1 BRK2

L1 L2 L3 N TB1
LOAD

L1 L2 L3 N L1 L2 L3 N
LOAD 1 LOAD 2

Control connection diagrams Control connection diagrams


Two breakers Two breakers and a tie breaker
CLOSE LINE 1

CLOSE LINE 2

ATL800 EXP1003
OPEN LINE 1

OPEN LINE 2

ATL800
CLOSE TB1
OPEN TB1
CLOSE LINE 1

CLOSE LINE 2
OPEN LINE 1

OPEN LINE 2

OUT 1

OUT 2

OUT 3

OUT 4

A1 A2 -- +
OUT 1

OUT 2

OUT 3

OUT 4

53 54 26 27 55 56 57 39 40 43 58 59 60 41 44 45 14 12 11 24 22 21

A1 A2 F1A T3.15A
53 54 26 27 55 56 57 39 40 43 58 59 60 41 44
L N - +
AC AUX SUPPLY

12 - 48V=
BATTERY

F1A T3.15A

L N
12 - 48V=
BATTERY
AC AUX SUPPLY

BRK2
INTERLOCK

BRK1
INTERLOCK

BRK1 BRK2 TB1


CLOSING
OPENING

CLOSING

CLOSING
OPENING

OPENING

L
POWER SUPPLY

POWER SUPPLY

POWER SUPPLY
TRIP
INTERLOCK

TRIP

TRIP
INTERLOCK

INTERLOCK
STATUS

STATUS

STATUS

BRK1 BRK2 FROM ATLDPS1


CLOSING
OPENING

CLOSING
OPENING
POWER SUPPLY

POWER SUPPLY
TRIP

TRIP
STATUS

STATUS
INTERLOCK

INTERLOCK

FROM ATLDPS1 N

 For the correct programming of inputs and outputs, consult the installation manuals available at www.LovatoElectric.com.

27-16
27 Automatic transfer switch controllers
Wiring diagrams

ATL900 
Power connection diagrams Power connection diagrams
Three breakers Three breakers and two tie breakers
LINE 1 LINE 2 LINE 2 LINE 1 LINE 2 LINE 3
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
QF1 QF1
1 L1 1 L1
2 L2 2 L2
LINE 1 LINE 1
3 L3 3 L3
4 N 4 N

QF2
5
6
L1
L2
ATL900 QF2
5
6
L1
L2
ATL900
LINE 2 LINE 2
7 L3 7 L3
8 N 8 N

QF3 QF3
9 L1 9 L1
10 L2 10 L2
LINE 3 LINE 3
11 L3 11 L3
12 N 12 N
BRK1 BRK2 BRK3 BRK1 BRK2 BRK3

13 S1-1 13 S1-1
14 S1-2 14 S1-2
15 S1-3 15 S1-3
CURRENT CURRENT
16 S1-4 TB1 TB2 16 S1-4
17 S2 17 S2
TA1

18 S2 18 S2
TA2
TA3
TA4

L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
LOAD LOAD 1 LOAD 2 LOAD 3

Control connection diagrams


Three breakers
CLOSE LINE 1

CLOSE LINE 2

CLOSE LINE 3

ATL900
OPEN LINE 1

OPEN LINE 2

OPEN LINE 3
OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

A1 A2
53 54 26 27 55 56 57 39 40 43 58 59 60 41 44 61 62 63 42 45

F1A T3.15A

L N
AC AUX SUPPLY

12 - 48V=
BATTERY

BRK2 BRK1 BRK1


INTERLOCK

INTERLOCK

INTERLOCK

BRK3 BRK3 BRK2

BRK1 BRK2 BRK3


OPENING
CLOSING

CLOSING

CLOSING
OPENING

OPENING
POWER SUPPLY

POWER SUPPLY

POWER SUPPLY
INTERLOCK

STATUS

INTERLOCK

INTERLOCK
TRIP

STATUS

STATUS
TRIP

TRIP

FROM ATLDPS1

Control connection diagrams


Three breakers and two tie breakers
EXP1003 EXP1003
CLOSE LINE 1

CLOSE LINE 2

CLOSE LINE 3

ATL900
OPEN LINE 1

OPEN LINE 2

OPEN LINE 3

CLOSE TB1

CLOSE TB2
OPEN TB1

OPEN TB2
OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

A1 A2

53 54 26 27 55 56 57 39 4043 58 59 60 41 44 61 62 63 42 45 50 51 14 12 11 24 22 21 14 12 11 24 22 21
F1A T3.15A

L N
AC AUX SUPPLY

12 - 48V=
BATTERY

BRK1 BRK2 BRK3 TB1 TB2


CLOSING
OPENING

CLOSING

CLOSING

CLOSING

CLOSING
OPENING

OPENING

OPENING

OPENING
POWER SUPPLY

POWER SUPPLY

POWER SUPPLY

POWER SUPPLY

POWER SUPPLY
TRIP
INTERLOCK

STATUS

TRIP

TRIP

TRIP

TRIP
INTERLOCK

INTERLOCK

INTERLOCK

INTERLOCK
STATUS

STATUS

STATUS

STATUS

FROM ATLDPS1

ATLDPS1 
Connection diagram
LINE 1 LINE 2
L N L N
27

ATLDPS1
L N 11 14 Y1 Y2
OUT ALARM OPEN 230V
CLOSED 110V

 For the correct programming of inputs and outputs, consult the installation manuals available at www.LovatoElectric.com.

27-17
27 Automatic transfer switch controllers
Technical characteristics

TYPE ATL100 ATL500 ATL600 - ATL601 - ATL610 ATL800 ATL900


AC POWER
IEC rated supply voltage Us 110...230VAC 110...240VAC 100...240VAC 100...240VAC 100...240VAC
(ATL600, ATL610)
Operating range 80...300VAC 90...300VAC 90...264VAC 90...264VAC 90...264VAC
(ATL600, ATL610)
Frequency 45...66Hz 45...66Hz 45...66Hz 45...66Hz 45...66Hz
Immunity time for micro-breaking –– ≤200ms (110VAC) ≤50ms (110VAC) ≤40ms (110VAC) ≤40ms (110VAC)
≤400ms (220VAC) ≤250ms (220VAC) ≤200ms (220VAC) ≤200ms (220VAC)
Immunity time for micro-breaking –– –– ≤25ms (110VAC) ≤20ms (110VAC) ≤20ms (110VAC)
(with EXP expansions) ≤120ms (220VAC) ≤100ms (220VAC) ≤100ms (220VAC)
DC POWER
Rated battery voltage –– –– 12-24VDC 12-24-48VDC 12-24-48VDC
(ATL601, ATL610)
Operating range –– –– 7.5...33VDC 7.5...57.6VDC 7.5...57.6VDC
(ATL601, ATL610)
Maximum current consumption –– –– 230mA at 12VDC; 400mA at 12VAC; 510mA at 12VAC;
120mA at 24VDC 220mA at 24VDC; 260mA at 24VDC;
100mA at 48VDC 135mA at 48VDC
Maximum power consumption/dissipation –– –– 2.9W 4.8W 6.5W
VOLTMETER INPUTS
Maximum rated voltage Ue 110...230VAC 415VAC L-L (240VAC L-N) 480VAC L-L (277VAC L-N) 600VAC L-L (346VAC L-N) 600VAC L-L (346VAC L-N)
Measuring range 80...300VAC 155...519VAC L-L 50...576VAC L-L 50...720VAC L-L 50...720VAC L-L
(300VAC L-N) (333VAC L-N) (415VAC L-N) (415VAC L-N)
Frequency range 45...66Hz 45...66Hz 45...66Hz 45...66Hz 45...66Hz
Measurement method True root mean square True root mean square True root mean square True root mean square True root mean square
(TRMS) (TRMS) (TRMS) (TRMS) (TRMS)
Measuring input impedance L-N >8MΩ >0.5MΩ L-N, >0.5MΩ L-N, >0.55MΩ L-N, >0.55MΩ L-N,
>1.0MΩ L-L >1.0MΩ L-L >1.10MΩ L-L >1.10MΩ L-L
Wiring method Single-phase and neutral Single-phase, two-phase, Single-phase, two-phase, three-phase line with or without neutral
three-phase line with neutral and balanced three-phase
AMMETER INPUTS
Rated current Ie –– –– –– –– 1A~ or 5A~
Measuring range –– –– –– –– for scale 5A: 0.02 - 6A~
for scale 1A: 0.02 - 1.2A~
Type of input –– –– –– –– Shunt supplied by current
transformer external
(low voltage) 5A max.
Measurement type –– –– –– –– True root mean square
(TRMS)
Overload capacity –– –– –– –– -20% Ie
Overload peak –– –– –– –– 50A for 1 second
Burden –– –– –– –– <0.6VA
MEASUREMENT ACCURACY
Mains and genset voltage ±0.25% f.s. ±0.25% f.s. ±0.25% f.s. ±1 digit ±0.25% f.s. ±1 digit ±0.25% f.s. ±1 digit
DIGITAL INPUTS
Number of inputs –– 2 6 8 12
Type of input –– Negative Negative Negative Negative
Input current –– <5mA <8mA <8mA <8mA
Low input signal –– ≤2.6V ≤2.2V ≤2.2V ≤2.2V
High input signal –– ≥3.1V ≥3.4V ≥3.4V ≥3.4V
Input signal delay –– ≥50ms ≥50ms ≥50ms ≥50ms
CALENDAR CLOCK
Backup reserve power –– –– Backup capacitor Backup capacitor Backup capacitor
(ATL610)
Operation without power voltage –– –– 5 min approx. (ATL610) 14 days approx. 14 days approx.
RELAY OUTPUTS
Number of outputs 3 3 7 7 10
Configuration – 2NO: AC1 - 4A 250VAC; – 2NO: AC1 - 8A 250VAC; – 6NO: AC1 - 8A 250VAC; – 2NO: AC1 - 12A 250VAC; – 3NO: AC1 - 12A 250VAC;
1.5A 250V~ AC15 AC15 -1.5A 250VAC; AC15 -1.5A 250VAC; B300 AC15 - 1.5A 250VAC; B300 AC15 - 1.5A 250VAC; B300
– 1NO: AC1 - 3A 250VAC; – 1 changeover: – 1 changeover: – 2NO: AC1 - 8A 250VAC; – 3NO: AC1 - 8A 250VAC;
DC1 - 3A 30VDC AC1 - 8A 250VAC, AC1 - 8A 250VAC, AC15 - 1.5A 250VAC; B300 AC15 - 1.5A 250VAC; B300
DC1 - 8A 30VDC; DC1 - 8A 30VDC; – 3 changeover: – 4 changeover:
AC15 - 1.5A 250VAC AC15 - 1.5A 250VAC, AC1 - 8A 250VAC, AC1 - 8A 250VAC,
B300 30VDC1A DC1 - 8A 30VDC; DC1 - 8A 30VDC;
Auxiliary service AC15 - 1.5A 250VAC; AC15 - 1.5A 250VAC;
B300 30VDC 1A B300 30VDC 1A
Auxiliary service Auxiliary service
Mechanical / electrical endurance 1x107 / 1x105 operations 1x107 / 1x105 operations 1x107 / 1x105 operations 1x107 / 1x105 operations 1x107 / 1x105 operations

27-18
27 Automatic transfer switch controllers
Technical characteristics

TYPE ATL100 ATL500 ATL600 - ATL601 - ATL610 ATL800 ATL900


STATIC OUTPUT
Output type –– –– –– –– NO
Operating voltage –– –– –– –– 10-30V
Maximum current –– –– –– –– 50mA
AMBIENT CONDITIONS
Operating temperature -30...+70°C
Storage temperature -30...+80°C
Relative humidity <80% (IEC/EN/BS 60068-2-78)
Maximum pollution degree 2
Overvoltage category 3
Measurement category III
Climatic sequence Z/ABDM (IEC/EN/BS 60068-2-61)
Shock resistance 15g (IEC/EN/BS 60068-2-27)
Vibration resistance 0.7g (IEC/EN/BS 60058-2-6)
HOUSING
Version Modular housing 3 modules Flush-mount
(DIN 43880)
Material Polyamide RAL 7035 Polycarbonate
IEC degree of protection IP40 on front IP40 on front IP65 on front
IP20 on terminals IP65 with optional gasket IP20 on terminals
IP20 on terminals
Weight 300g 580g 600g (ATL600 - ATL601) 1000g 1090g
680g (ATL610)
CERTIFICATIONS AND COMPLIANCE
Certifications obtained EAC EAC, RCM cULus, RCM (except ATL601), EAC, LOVAG (ATL610, ATL800, ATL900)
Compliance with standards IEC/EN/BS 61010-1, IEC/EN/BS 61010-1, IEC/EN/BS 61010-1, IEC/EN/BS 61010-2-030, IEC/EN/BS 61010-2,
IEC/EN/BS 61010-2-030, IEC/EN/BS 61010-2-030, IEC/EN/BS 61000-6-2, IEC/EN/BS 61000-6-4, IEC/EN/BS 60947-1,
IEC/EN/BS 61000-6-2, IEC/EN/BS 61000-6-2, IEC/EN/BS 60947-6-1, UL508 e CSA C22.2 n°14
IEC/EN/BS 61000-6-4, IEC/EN/BS 61000-6-3,
IEC/EN/BS 60947-1, IEC/EN/BS 60947-1,
IEC/EN/BS 60947-6-1 IEC/EN/BS 60947-6-1

27