EcoStruxure For Data Center

EcoStruxure for DC

Specific EcoStruxure Architecture

Building Management SystemOverview

Electrical Power Monitoring System

Dashboard/ Graphic Example

Q&A

Confidential Property of Schneider Electric | Page 2


Internal
EcoStruxure for data centers is supported with a portfolio of reference designs

Fully Documented & Validated Designs by domain experts – Power, IT & Building

Campus/Enterprise

Supervisory system/
Overlay

Site
Misc protocols BACnet
WebServices EBO HMI
WorkStation or
Third party systems WebStation

Misc
protocols

EcoStruxure
EWS Web Services (EWS)
SmartConnector Server 1 EBO Server 2 PME Server

TCP/IP

Mechanical Electrical
Modbus TCP Modbus TCP

Mechanical EGX EGX Electrical


AS-P AS-P
Monitoring Link150 Link150 Monitoring

Modbus RTU Hardwired I/O Modbus RTU

Mechanical Mechanical Environmental Electrical


Monitoring Control Monitoring Monitoring

Internal
for Data Centers

EcoStruxure™ Architecture

Enterprise,
Apps,
Analytics &
End-to-end Cybersecurity

Services EcoStruxure EcoStruxure EcoStruxure


EcoStruxure
Enterprise Central Building Advisor Power Advisor
Asset Advisor

Edge
Control
EcoStruxure EcoStruxure EcoStruxure Power Monitoring Expert
Building Operation SmartConnector EcoStruxure Power SCADA Operation

Smar tX Uniflair EcoStruxure APC APC Galaxy


Smar t-UPS Netshelter Set Series Pact Series Power meters
Connected
Products
Tap into your Cooling systems to control
and manage the Data Center Solutions The most trusted UPS Standard and Custom U Comprehensive, robust W orld Class Breakers Power Quality, Uptime
building’s potential Racks for IT Equipment ni
through smart devices tem perature and hum idity in the world for portfolio of power distribution & Switches & Efficiency
for critical IT and process business applications. in any environm ent nt and motor control centers
environm ents er
ru

© 2020 Schneider Electric, All Rights Reserved | Page 4

Internal
Integrated Building and Power Management Architecture

Apps,
Analytics &
Services
(Cloud) EcoStruxure EcoStruxure EcoStruxure
BuildingAdvisor Asset Advisor Power Advisor

Solution applicable for


Edge BMS system
Control
• DDC (BACnet) Field Controllers
(On Premise) EcoStruxure Power Monitoring Expert (PME) - EPMS
EcoStruxure Building Operation(EBO) - BMS • Up to 100.000 BMS points

EPMS system
• Up to 3,000 EPMS devices
• Schneider Electric’s PQM meters
Mechanical Services Electrical Services
• Monitoring (no control) applications
• HVAC control and monitoring • Fire Alarm System (FAS) • MV/LV Switchboards
(Chiller, AHU, FCU, Fan) • VESDA • Substations
• Mech Panels • Emergency Warning Intercom • Lighting Control System
System (EWIS) • Emergency Lighting System
• Generator System
• Solar PV System
Security Services Other Services • Electrical Metering
• Uninterruptible Power Supply
• Physical Security Information • Lift Management System
(UPS)
Management (PSIM) • Drainage/Wastewater System
• Access Control System (ACS) • Battery Storage
• Water Metering
• Closed Circuit Television (CCTV) • Gas Metering

© 2020 Schneider Electric, All Rights Reserved | Page 5


EcoStruxure™ Building Operation - BMS Proven Software

EcoStruxure™ Building Operation software is


the edge control heart of the system to create
future-ready smart buildings
An open integration platform that integrates multiple
systems and devices to collect, analyze and manage
data across the enterprise
Monitor, manage and control building operations
on one network to increase efficiency
Turn system data into actionable intelligence to optimize
building performance and create productive
environments

Confidential Property of Schneider Electric | Page 9


Internal
Internal
A truly open, end-to-end IP solution Edge Control Software
Maximize opportunities in today’s data-intensive modern buildings

Open Connected
• Go beyond HVAC and get simple integration across • Enable data transmission from connected equipment
complex third-party systems to diagnose and resolve issues faster
• Create limitless custom solutions through developer • Conveniently monitor, manage and even commission
APIs with Smart Connector Framework buildings from mobile devices

Future-ready
• Leverage IP to ease adoption and implementation of
future technology expansions

Insightful
• Take advantage of cloud-based analytics and
predictive services to improve building performance

Confidential Property of Schneider Electric | Page 8


Internal
SmartX Edge Server – AS-P & AS-B
Hardware
Next-generation automation servers Innovation

AS-P – Ideal for enterprise installation and transition


simplification
Network controller and server in one
Faster dual-core processor for improved performance AS-P & AS-B conform
to the BACnet® B-BC
Large 512 MB RAM memory size profile at protocol
revision 12

Dual Ethernet ports, future-ready to elevate BACnet IP communication to


the field controller level
Communications hub: BACnet, LonWorks, Modbus, Web Services
Centralized control, database, serving out to user interfaces
(WorkStation, WebStation and apps)
UL-864 certification for smoke control

AS-B – Ideal for small-to-medium main plant applications


Powerful, compact all-in-one BMS design

Confidential Property of Schneider Electric | Page 11


Internal
Internal
SmartX Edge Server I/O modules
Hardware
Modular and scalable footprint to meet your specific needs Innovation

Each SmartX AS-P server supports up to 32 I/O modules


• Includes AS-P, Power Supply and associated I/O modules
• Extension cable for multiple row installations (max 5 per automation
server)
• Can control up to over 400 I/O points (depending onconfiguration)

17 different I/O modules allows for centralized control of large


mechanical systems
• A variety of digital and analog inputs and outputs to ensure each
installation is customized

Power Supply
• 24V power across a common bus
Confidential Property of Schneider Electric | Page 12
Internal
Internal
SmartX Edge Server I/O modules
Hardware
Key hardware features Innovation

Easy to install
• DIN rail or wall mount
• Hot swap / plug and play

2piece design with patented locking handles

Separate wiring base


• Backplane built-in
• Auto addressing

Field marking feature with protective windows


• Factory or custom label
Confidential Property of Schneider Electric | Page 13
Internal
Internal
System Topology Examples

Star Daisy Chain Daisy Chain Loop Two Options:


Isolated Field Bus – Field Bus on
IT Backbone IT Backbone IT Backbone independently configured Ethernet
port 2 (of SmartX Edge Server) or
Server Server Server
a dedicated network card on an
Eth Port2 Eth Port2 Managed Switch Eth Port2 Enterprise Server
Managed Switch Managed Switch

Field Controller on IT backbone

MP-C/V MP-C/V
RSTP*

MP-C/V MP-C/V MP-C/V


MP-C/V MP-C/V

Choose For: Choose For: Choose For:


• Cost and simplicity
MP-C/V MP-C/V
• High performance and reliability • Cost and simplicity over high *RSTP: Rapid Spanning Tree Protocol
• Simplicity over high availability availability and performance • Increased availability with redundancy [requires managed switch, MP-C/V only, not AS]

Network topology support System scale


• ES supports up to 600 MP-C/V controllers
• Daisy chain supports up to 50 controllers
• AS-P supports up to 200 MP-C/V controllers
• RSTP (loop) supports up to 39 controllers
• AS-B supports up to 50 MP-C/V controllers

Internal
Internal
Cyber Security

How BMS brings the benefits of open systems, whilst being as secure as possible.
Concepts & mechanism of Cyber Security:
• All human users are uniquely

• Identification and Authentication •
Auto logoff
Audit log withsystem-wide
identified

• • Admin logon password management


Authorisation synchronized timestamps
Imported User Accounts are disabled
• •
Activity logs provide non-repudiation
• Confidentiality • …
by default

• …
• Data Integrity
• Restricted Data Flow
• Timely Response to Events
• Resource Availability

• Encrypted transmission of data.

• Clickjacking protection options

• Password data is obscured from view

• Passwords are stored and transmitted securely

Confidential Property of Schneider Electric | Page 15


Internal
Internal
EcoStruxure™ Building Operation – Multi Sites Easily
integrate
up to 10
Enterprise Servers

Campus
Enterprise
Workstations
Central

Data Centre 1 Data Centre 2 Data Centre 3 Data Centre 4


Site Layer

Connected
Products
and

Internal
BUIDLING ADVISOR (BA)

Building Advisor gives analytics to identify faults and diagnose issues


• Fault/ Alarm Analytics Report. Building AdvisorPortal

• Monthly Alarm Totals. (Alarms per month)


Data secured transfer
• Alarm Status Summary (Total alarm, Oldest Active HVAC equipment
Alarm, Average age of Alarm)
BMS
• Top Ten Alarms. (10 Alarms happens most often)
Protocol level communication
Airport Utilities
• Alarm by Hour of Day (Time of Alarms happen)
Alarms
• And so on.
• Report and Consultation by SE remote experts.
• Advice on maintenance priorities and actions.

Hours of Alarm

EcoStruxure Building Advisor is


giving accurate and in-depth
• TotalAlarms insight of building performance
• OldestAlarm
• Average age of alarm

Confidential Property of Schneider Electric | Page 18


Internal
Internal
Typical EPMS Architecture – Open, Scalable, Future Ready

Server: Thin Clients:


Application + Database Main User Interface (Web based)

IP Backbone

Modbus

and ION
Protocols
Power Protection Breakers, RTUs,
Meters Relays Trip Variable
PLCs
Units, Speed
UPSs Drives Water,
Gateways Air,
Gas,
PQ Steam
Correction
Equipment Final
Distribution
Breakers,
Sensors,
Confidential Property of Schneider Electric | Page 26 Gateways
Internal
EPMS Communication Protocol

Communication Protocol
➢ Modbus RTU, Modbus TCP/IP
➢ OPC DA (Server / Client) for real-time data exchange
➢ EWS (SOAP 1.2, WSDL) to export real time data, historical data andalarms
➢ ETL to import / export historical data from/to csv, xls, OLEDB, SQL and etc.
➢ ODBC (database) / PQDIF (PQ data) / COMTRADE (waveform) export/import
➢ ION (proprietary protocol for ION device communication)
➢ BACnet, KNX, DNP3, SNMP, IEC61850, IEC104
➢ OPC UA (Server / Client) for real-time data exchange
➢ OPC AE (Server) for alarms and events expose
➢ Smart Connector (RESTful API) for integrations to 3rd party systems

Confidential Property of Schneider Electric | Internal


Recommended EPMS Monitoring Devices
Protection PQ Meter Power Meter Energy Meter / I/O Statusw/ Other Devices/
Metering
Accuracy
BCPM timestamp Systems 66kV
Class

0.1s

Trafo

22kV G
GEN
0.2s
Trafo

0.2s
MSB/EMSB

0.5s

UPS DB SDB/EDB

0.5s

0.5s PDU DB

1.0

Confidential Property of Schneider Electric | Page 28 To DB


Internal
Recommended Device Connection
HTML5 Web Clients

PME+SQL Server

Modbus TCP/IP Backbone Network

Critical Device Status via


Modbus Gateway Data Concentrator (RIO)
Managed Switch Hardwire interface SER

Modbus TCP
Up to 15 devices

Legacy Device Status / Analog value (WAGES)


RS485 Daisy-Chain Network (Modbus RTU)
Smart Breaker IED PQM
(Applicable to all Modbus RTU devices)

Internal
Power Advisor
.

Internal
Power Advisor Reports

Confidential Property of Schneider Electric

Internal
PUE DASHBOARD

1) TOTAL BUILDING LOAD (kW) = ∑ All HVSB INCOMING POWER METER (kW)
2) TOTAL IT LOAD (kW) = ∑ All PDU INCOMING POWER METER (kW)

PUE = TOTAL FACILITY/ BUILDING LOAD


TOTAL IT LOAD Internal
SUMMARY DASHBOARD

Internal
MAIN HOME

Internal
MAIN BUILDING

Internal
DATAHALL FLOOR PLAN
LAYOUT

Internal
CHILLER GRAPHIC

Internal
CRAH, FWU, VRV GRAPHIC

Internal
UPS, Generator, LV Schematic Graphic

Internal
STS, PDU and RACK Graphic

Internal
Schneider BMS & CPOS Project Reference

No. Data Center Project Reference Scope Country


1. Local Data Center Kuningan (2022) – 10,500 point BMS, CPOS, EPMS Indonesia
2. Singapore Data Center Project Phase 1– Karawang (2022) – 38,000 points BMS, CPOS, EPMS Indonesia
3. US Data Center Phase 1 – Karawang (2022) EPMS Indonesia
4. Local Government Telco Phase HDC Phase 1 (2022) – 15,000 points BMS, CPOS, & DCIM Indonesia
5. UK Data Center Phase 1 – Jakarta (2021) – 10,000 points BMS & EPMS Indonesia
6. Singapore DC – Cikarang (2021) – Water Leak Sensor Water Leak System Indonesia
7. Local Government Telco DC – 3 sites (Sentul, BSD, Surabaya) BMS Indonesia

8. Local Government ISP DC – 3 sites (Jatiluhur, Taman Tekno, TB Simatupang) BMS & EPMS Indonesia

9. Private ISP Data Center - Cibinong BMS Indonesia