Scope of functions
50
51
50N
51N
49
Fig. 1
7SJ50 numerical overcurrent–time/overload protection relay
Overcurrent–time protection
100
The function is based on a common 100 70
phase measurement. A definite–time or 70
an inverse–time characteristic can be se- t [s] 50 t [s] 50
lected. For the earth currents, the same
type of characteristic is used as for the 20
20
phase currents. For the definite time
characteristic, the tripping time t is com- 10
10
puted as follows:
7 7
5 5
tp = 1.6
t C tp
tp = 1
2 2
tp = 0.5
Three different inverse–time characteris- 1 1
tics according to BS 142 resp. IEC 255–4 0.7 0.7
are available: tp = 0.2
0.5 0.5 tp = 1.6
Normal inverse (Fig. 2)
tp = 0.1
tp = 1
0.2
t 0.14 tp tp = 0.05
0.2
( p) 0.02 –1 tp = 0.5
0.1
0.1
0.07
0.07
Very inverse (Fig. 3) 0.05
tp = 0.2
0.05
t 13.5 t 0.02
p
p –1 tp = 0.1
0.02
0.01 tp = 0.05
1 2 3 5 7 10 20
0.01
Extremely inverse (Fig. 4) /p
1 2 3 5 7 10 20
/p
t 80 tp
( p) 2 –1 Fig. 2 Fig. 4
Tripping time characteristics normal inverse Tripping time characteristics extremely inverse
t tripping time
tp time multiplier 100
fault current 70
t [s] 50
p current setting
C settable factor 1, 2 or 4
20
10
7
5
tp = 1.6
1
0.7 tp = 1
0.5
tp = 0.5
0.2
tp = 0.2
0.1
0.07 tp = 0.1
0.05
tp = 0.05
0.02
0.01
1 2 3 5 7 10 20
/p
Fig. 3
Tripping time characteristics very inverse
Overload protection
If the overload protection without thermal
memory feature is selected the charac- t [s]
t [s]
teristic shown in Fig. 5 is valid for fault
currents
w1.1 @ p
1 000
For different settings of tp, the tripping 1000
700
700
time t can be computed as follows 500
500
300
300
t + 35 @ tp 200
200
(ń p) 2 –1 150
150
100
100
70 tp = 80
70 tp = 80 50
By using the overload protection with 50
memory feature, the preload with all vari- 30 tp = 40
30 tp = 40
20
ations is taken into account. 20 tp = 20
15
15 tp = 20
The tripping time t can be computed us- 10
10 tp = 10
ing the following equation (total memory tp = 10 7
7
according to IEC 255–8) 5
5
tp = 5
tp = 5 3
(ń p –( preń p
)2 )2 3
2
t + t @ In 2 tp = 2,5 1,5
tp = 2,5
(ń) 2 –k 2 1,5
1
1 0,7
0,7
0,5
t tripping time after start of overload 0,5
0,3
t 35.5 tp 0,3
0,2
0,2 0,15
I p current setting 0,15
0,1
Ipre previous current 0,1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1000
700
500
300
200
150
100
70
50
30 tp = 80
20
15 tp = 40
10
7 tp = 20
5
3 tp = 10
2
tp = 5
1,5
1
0,7 tp = 2,5
0,5
0,3
0,2
0,15
0,1
1 2 3 4 5 6 7 8
/p
Fig. 6
Tripping time characteristics with memory feature
(80 % preload)
Application examples
Solidly L1 >> t2
earthed L1 >> t2
L2 t >
Neutral Earth–fault current
insulated
I smaller than rated current
E E> tE
resp.
L3 > t1 L2
Fault detection (E) L3 > t1
L1, L2, L3
With current grading
and time grading >> t E>
t L1 >> t2
>
> >
>> Fault detection
t
>> > L2
> L1, L2, (E), L3
L3 > t1
(E)
Fault detection
L1, L2, L3
L1 >> t2
t E E> tE
M
L1 >> t2 L2
A L3 t therma
B Cable
C L2
D
A B C D
L3 t > Fault detection
(E) L1, L2, L3
Fault detection
L1, L2, L3
t L1 >> t2
L1 >> t2
A M L2
B E t E>
C
D L2 L3 t thermal
L3 > Cable
A B C D t (E)
Fault detection
Fault detection L1, L2, L3
L1, E, L3
Technical data
Input circuits Rated current N 1 or 5 A
Rated frequency fN 50/60 Hz
Thermal overload capability of current inputs
continuous 4 x N
10 s 30 x N
1s 300 x N
Burden of current inputs at N approx. 0.5 VA
1 1A1
IL1 IL1
IL2 4 1A2
IL2
IL3 2 2A1
5 2A2
3 3A1
IN IL3
6 3A2
IN
3B3 28 L+
Relay blocked 4B1 27 Relay monitor
9 4A3
Remote reset or 2B4 19
Binary input
blocking I 10 4A4
2B3 12
Command
2B2 11 Tripping I>
relay 1
2B1 18
L+ 22 4A1
1B4 21
Power supply L– 23 4A2 1B3 14
Command
1B2 13 Tripping I
relay 2
8 1B1 20
Fig. 8
Connection diagram for motor overload and short–circuit protection with sensitive detection of neutral current (four–wire system)
1 1A1
IL1 IL1
4 1A2 7SJ50
IL2/E
IL3 IL2/E 2 2A1
5 2A2
3 3A1 Signal contact 1 3B2
IN IL3 26 Phase failure
6 3A2
IN Signal contact 2 3B1 25 I >
E
Fig. 9
Connection diagram for motor overload and short–circuit protection with sensitive detection of neutral current (four–wire system)
Dimension drawings in mm
7.3 56.3
75 30 172 29.5 70 13.2 30
5.4
Diam. 5 or M4
255.8
244
266
245
M5
Diam. 6
71
Fig. 10
7SJ50 with housing 7XP2020–2 (for panel flush mounting)
92 27 29.5
15 21
22 28
Cutout 20 x 60
(without paint)
280
344
266
40
39
1 7
14
8
71
77 260
Fig. 11
7SJ50 with housing 7XP2020–1 (for panel surface mounting)
Export Regulations
In accordance with present German and permissible without the approval of the Subject to change.
US export regulations export licences (da- relevant authorities except where current Relevant are the criteria stated in the
ted 02.95) are not required for the prod- German export regulations contain coun- delivery note and in the invoice.
ucts listed in this catalog. try–specific restrictions. An export licence may be required due
Export and re–export are therefore to country–specific application of the
product.
Trademarks Dimensions
All product designations used are trade- All dimensions in this catalog are given in
marks or product names of Siemens AG mm
or of suppliers.
Responsible for
Technical contents: Norbert Schuster,
Siemens AG, EV S T11, Nürnberg
General editing: Claudia Kühn–Sutiono,
Siemens AG, EV MK 2, Erlangen
Bereich
Energieübertragung und -verteilung
Geschäftsgebiet Power
Zähler, Sekundär- und Netzleittechnik
P. O. Box 48 06 Transmission
D-90026 Nürnberg and Distribution
10
Siemens Aktiengesellschaft Order No.: E50001-K5712–A111-A1–7600
Siemens LSA 2.1.1 . March 1995
Printed in the Federal Republic of Germany