Professional Documents
Culture Documents
Users Guide
by
Melvin R. Loseke
COPYRIGHTS
1987, 1992, and 1995 by Melvin R. Loseke, 972.370.0967, www.loseke.com
All rights reserved. This publication contains proprietary information which is protected by copyright. No part of
this publication may be reproduced, transcribed, stored in a retrieval system, translated into any language or
computer language, or transmitted in any form whatsoever without the prior written consent of the publisher.
NOTICE
Melvin R. Loseke makes no representations or warranties of any kind whatsoever with respect to the contents
hereof and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose.
Melvin R. Loseke shall not be liable for errors contained herein or for incidental or consequential damages in
connection with the furnishing, performance or use of this publication or its contents.
Melvin R. Loseke reserves the right to revise this publication from time to time and to make changes in the
content hereof without obligation to notify any person of such revision or changes.
The hard drive should be large enough to handle current usage plus AutoCad or AutoCad LT, PrecisionPlus
(approximately 300MB), structure files you may wish to store, and have at least 400 MB of free space to
accommodate operation of applications.
Additional NOTES:
Install CDs for version 8.8.5 and older are not compatible with 64-bit Windows. Contact Loseke Technologies, Inc.
for assistance if you do not have a full install CD for version 8.8.5 or newer.
The program requires a parallel printer port (LPT1) or a USB port, depending on the type of sentinel (hardware
lock).
Printers and plotters must have Windows drivers. A printer driver must be installed even if a printer is not
attached.
The plotting modules of the program generate drawings as DWG format, compatible with AutoCad LT (98 and
newer) and full AutoCad (R14 and newer). DWG files created using AutoDesk’s RealDWG technology, which
require a processor with with SSE2 Technology
NOTE: If you want to use existing hardware that does not meet the above recommendations, please contact
Loseke Technologies, Inc. for technical support.
Note: if you are installing to a computer with Windows 10, Windows 8, Windows 7, or Windows Vista, you
MUST turn the User Access Control (UAC) OFF when installing and running PrecisionPlus.
Windows Vista:
If you have "classic view" set as the default control panel option:
1). go to control panel
2). double click user accounts
3). click the "Turn User Account Control on or off" link
4). check (or uncheck) the checkbox "Use User Account Control (UAC) to help protect your computer" to turn on
or off
5). click OK
If you have "Control Panel Home" set as the default control panel option:
1). go to control panel
2). click "User Accounts and Family Safety"
3). click "User Accounts"
4). click the "Turn User Account Control on or off" link
5). check (or uncheck) the checkbox "Use User Account Control (UAC) to help protect your computer" to turn on
or off
6). click OK
1). Turn off the User Access Control (UAC) under User Accounts in Control Panel.
Reference the prior page for Instructions for turning off UAC.
2). Close out of all applications and insert the CD into the CD tray. When / if the PrecisionPlus setup program
auto-launches, click exit to exit out of the setup.
5). Double (left) click on Setup.EXE and follow the screen instructions to install PrecisionPlus, clicking Next to go
to the next screen.
6). After you click Finish on the screen labeled “InstallShield Wizard Completed”, you will see a meter on the
screen labeled “Updating Working Directory” indicating the copy progress. This will copy files to your working
directory. Please wait while all files are copied to your hard drive.
7). After the files have copied, set the font path for AutoCad, then click Save and Continue. If you have not yet
installed AutoCAD/LT, click Save and Continue; you can specify the font path later, following the instructions in
the Plotting Manual.
8). If you have not previously installed a sentinel driver, or if your computer has an older driver, you will be
prompted to install a sentinel driver. If you exit without installing the driver, you can install it later, following the
instructions below.
10). Before you launch PrecisionPlus, you will need to set the shortcut to Run as an Administrator. To do so:
Right click on the PrecisionPlus shortcut and click Properties.
a). Go to the Compatibility Tab
b). Check the box next to: “Run this program as an Administrator” at the bottom of the screen.
c). Check the box next to: “Run this program in compatibility mode for:” and select Windows XP (Service
Pack 3) in the dropdown box below it.
d): Click Apply, then click OK.
PrecisionPlus Loading Instructions for 64-Bit Operating Systems (Windows 7 & Vista)
1. Check your hardware and operating system configuration against the Hardware Requirements.
2. Close out of all applications.
3. Put the CD into the CD drive.
4. The CD should auto launch. (If it does not, double click on My Computer. Double click on the CD drive
(Example D:). Double click on the icon shown here:
Note:
The 64-bit installation program allows for only one version of PrecisionPlus to be installed on a single computer.
1. Check your hardware and operating system configuration against the Hardware Requirements.
2. Close out of all applications.
3. Put the CD into the CD drive.
4. The CD should auto launch. (If it does not, double click on My Computer. Double click on the CD drive
(Example D:). Double click on the icon shown here:
You will also need to install a sentinel driver, if you did not do so as part of the PrecisionPlus installation. You can
do this by selecting Help on the PrecisionPlus toolbar, then Tools, Load Sentinel Driver. Or install the driver from
the PrecisionPlus install CD by following these steps:
1. Double click on My Computer.
2. Click once on the CD drive (example D:).
3. Click on the File menu and choose Open.
4. Double click on the Sentinel_Drivers folder.
5. Double click on Sentinel Protection Installer 7.5.0.exe and follow the prompts to install the driver.
If you wish to install a “free-ware” program to generate PDF files, you can install CuteWriter by going to
http://www.cutepdf.com/Products/CutePDF/writer.asp, selecting Download CuteWriter and following the prompts.
A version of CuteWriter is also provided on the PrecisionPlus install CD. Here are the instructions for installing
from that source:
Browse to the CuteWriter folder on the CD:
Double Click on My Computer
Click once on the CD drive (example D:)
Click on the File menu and choose Open
Double click on the CuteWriter folder
Double click on CuteWriter.EXE and follow the screen prompts.
Reboot.
Again browse to the CuteWriter folder on the CD.
Double click on Converter.EXE to run this install program.
After installing CuteWriter, you will be able to print to PDF file format. Instructions for using CuteWriter are in the
file HowToUseCuteWriterOnYourPC.PDF, located in the CuteWriter folder of the CD.
NOTE: You can utilize Loseke Technologies’ software and its output without a PDF writer program. However, you
may find it convenient to save reports and/or plots in PDF file format.
If you wish to install a “free-ware” program to view DWG files, you can download DWG TrueView from AutoDesk’s
website at www.autodesk.com
MENU BAR
FILE MENU
Close Structure & Save As – Save the structure into a new file and/or directory and close the structure. If the
directory specified does not exist, the program will create it.
Setup - These options are described in the Program Setup section of this manual.
Print Sketch – This option will print a “sketch” of the building as displayed on the screen.
Printer Setup – The Printer Setup section of this manual contains more information on this menu choice.
Copy Drawing Files – Copy all of the DWG drawing files and script files from the program directory to a user-
specified directory. If the specified directory does not exist, the program will create it. If there are already files in
the destination directory, the program will remind you that if you continue, any files with the same name will be
overwritten.
Generate Drawings – Generate the plots and provide an option to launch the CAD application. The CAD
application will list the plots available. This menu choice is only available after you have run a building.
Post Editor – Add items to, or deduct items from, the Bill of Material reports. Create or modify Part Groups. See
the Post Editor section of the Users Guide for additional information.
Design Programs – This menu choice is only available after you have opened an inventory file, and opened or
created a structure with a building. The available options will vary depending on your license. Consult the Design
Manual for information on specific design modules.
Counter Update – Update the sentinel counter, if required. See the General section of this manual for details
about running this program.
Setup Files – Select Setup to see a list of available options. Further information is available in the File
Maintenance, Plotting and Design Manuals as well as in other portions of this Users Guide.
INVENTORY MENU
For more information about these inventory items, see page File Maintenance 2-1 in the File Maintenance Manual.
Edit Inventory – Edit an inventory file by selecting the inventory table from the list.
Application Search Orders, Create Sets, Add Sections To Sets, Select Sets To Use and Through-Fastened
Factors options related to cold-formed section properties and usage. See the File Maintenance Manual, pages
File Maintenance 2-27-1 through 2-28.
Hole Locations – See pages File Maintenance 2-29-1 and following in the File Maintenance Manual.
When you open a structure or create a new structure and add a building to it, five additional choices appear on the
menu bar: Structure, Building, General Frame, Reports and Window.
STRUCTURE MENU
The Input section of this Users Guide describes structure menu options New Building, Remove Building, Save
Structure as Template, Save Building as Template, Setup, Loads, Connect Buildings, View Structure and
Run Structure.
Frame Member & Joint Locations – View structure frame member numbers, joint numbers and joint locations
after designing the mainframe.
Calculate Now – Bring up the Calculations box. Choose the calculations for the program to perform. This option is
only active if you have accessed the General Frame screens.
Add Standard Details – Add standard details to the current structure. See page Plotting 9-6-1 in the Plotting
Manual for additional information about standard details and their use.
BUILDING MENU
This menu is available only when a building is open. The Input section of this Users Guide describes the building
input for Geometry, Setup, Endwalls, Purlin/Girt Support Conditions, Roof and Sidewall Lateral Bracing,
Endwall Girt Lateral Bracing, Roof and Sidewall Diagonal Bracing, Endwall Diagonal Bracing, Panels, Trim
and Ridge Condition, Girt Locations, Overhangs, Overhang Purlin Bracing, Accessories, Openings,
Loads, Purlin Spaces, Load Combinations, Additional Loads and Floor Tributary Widths.
Building Status – Display the messages generated during the last run of the building.
Change Name – Change the current building name as shown at the top of the PrecisionPlus for Windows screen
(maximum 30 characters).
GENERAL FRAME
The Input section of this Users Guide describes the mainframe input for Frame, Setup, Floor Beams, Floor
Joists, Overhang Beams, Flange Brace Locations, Columns and Rafters.
REPORTS
See the Printer Setup section of the manual prior to selecting a report to print. Choose the report that you want to
print or view. See the Output section of this manual for more information about reports.
Inventory – Select the inventory report you wish to open. A print preview of the report will be displayed. Click on
Output – This choice is active if you have generated output for a building or mainframe.
Print All – This choice will display a screen on which you may select one or more output reports to be printed.
Click to place a check mark next to the report(s) that you want to print. You can save default groups of reports to
print by selecting the desired reports, entering a name for the report group in the box at the top of the screen and
clicking Save. Previously saved report groups can be modified and saved. Report groups can be deleted by
selecting the report group name from the drop-down list and clicking Delete. Available design reports match your
specified selections under File, Setup, Reports. If Bill of Material reports (Quote Confirmation, Management, Sales
and Shipper) are selected, the text version will be printed.
Copy All – This choice displays a screen where you can select one or more output reports to copy to a specified
location. The Browse button can be used, or you can enter the desired directory path. If the specified directory
does not exist, it will created. The default directory is a subfolder of the PrecisionPlus directory, with the same
name as the structure. Bill of Material reports (Quote Confirmation, Management, Sales and Shipper) will be
copied in the text or PDF, depending on format specified under File, Setup, Reports tab. Available design reports
match your specified selections under File, Setup, Reports.
Coil – Secondary Framing is only available if you have the Coil Report option checked on the Options tab of the
Program Setup screen.
Crane Runway Design is only available if you have run the Crane Runway Beam program. See the Crane
Runway Beam section of the Design Manual for information about printing this report.
Card Image is active only after you have run the Card Image program. Frame Design and Frame Geometry
reports are generated by the Card Image program. See the Card Image section of the Design Manual for
additional information.
WINDOW MENU
Detailed Frames – This option displays the building sketch in greater detail. Detailed mainframes will not be
perfectly accurate. However, detailed sketches will help you in determining if all information needed for a frame
has been entered. For example, if information for an interior rafter is missing, this will be visible on the detailed
mainframes sketches. The frame description (from General Frame ➔ Frame) will appear next to each frame.
Simple Frames – This option displays the building sketch faster and with normal detail.
Frame Profile – This option displays a two-dimensional sketch of a frame. If multiple frames have been input on a
building, the program will allow you to select the frame to display. Member depths and segments lengths for the
rafters are displayed on the frame profile. Use the sketch options screen to change the font size and to zoom to
view these numbers. To print the frame profile, select File, Print Sketch. For multiple frame buildings, you will be
prompted for which frame to print. Choose a frame and click on OK to print to the default printer.
NOTE: You may want to remove the display of the endwall columns when switching to this view.
Endwall Columns, Bays, Diagonal Bracing, Purlins, Girts, Framed Openings, and Overhangs. When these
are checked, the related elements will be drawn on the sketch of the building. Remove the check associated with
an item to remove it from the sketch. Note that this does not remove the related element from the building; it only
modifies the displayed sketch.
The numbered list shows the buildings open in the current structure. The check mark indicates the active building.
See the General Section of the Users Guide for details about Help options.
SKETCH OPTIONS
To change the angle of the sketch of the building, click with the right mouse button on the sketch to invoke the
dialog box.
Enter the desired X and Y View Angles for displaying the building sketch. To set the sketch to two dimensional,
input X view angle as 0 and Y view angle as 90.
Edit the Zoom percentage for closer or farther views of the building sketch.
Input a number, or increase the number, in the Scale Frame Font to display the frame labels in a larger font.
Input a number, or increase the number, in the Scale Member Font to control segment length font size and in the
Scale Joint Font to control member depth font size.
Input a formatting number to adjust how the member sizes and web depths are displayed when Frame Profile is
selected.
Adjust the sketch colors by selecting Default Colors, Black or User Controlled.
When you select the radio button for User Controlled, you can select your desired color for the elements from the
associated drop-down list. Available colors are Black, Red, Green, Yellow, Blue, Magenta, Cyan, White and
Orange.
STATUS BAR
This bar appears at the bottom of the PrecisionPlus for Windows screen.
The first box on the status bar gives status information about the program. This will give actions that the program
is performing such as “Redrawing Building 1” or information about the system resources available. The second
box displays the current inventory file. This box will be blank if you do not have an inventory open. The third box
displays the name of the current structure file. The box on the far right is the clock.
Control the display of the clock and status bar on Program Setup Screen – Tab Options. See the Program Setup
section of this manual.
When you rest the mouse pointer on a tool bar icon, further information about that tool bar icon will be displayed
on the status bar. You can hide or display specific icons and edit the status bar text displayed when you point to an
icon (see the Program Setup section).
RECOMMENDED RANGES
Recommended ranges (building width and sidewall height) for selected mainframe types is listed below.
NOTES:
Modular buildings may have up to ten interior columns.
The maximum number of bays on any building is 30.
Double clicking with the left mouse button on a numeric field will bring up a screen similar to the following:
Change the Lower Limit, Upper Limit, and Formatting for this field. For a numeric field in a grid, you must first click
on the grid square with the left mouse button. Then double click with the left mouse button to bring up the Change
Ranges/Formatting screen for that field.
When you know that a number that you are going to input will be below or above the existing ranges for that field,
you should change the range first and then input the value desired.
1 1 X
2 1 X
3 1 X
4 1 X
5 2 X X
6 2 X X
7 2 X X
8 2 X X
9 3 X X X
10 3 X X X
11 3 X X X
12 3 X X X
13 3 X X X
14 4 X X X X
15 4 X X X X
16 4 X X X X
17 4 X X X X
18 4 X X X X
19 5 X X X X X
20 5 X X X X X
BUILDING TEMPLATE
Create a building template for a typical building by following these steps.
Open an existing structure or create a new structure. Change the building type, dimensions and all else that you
want to be default for a building. When you have completed the input, choose Save Building as Template from the
Structure menu. The following screen will appear.
Enter the Filename (8 characters maximum). Apostrophes, quotation marks, commas, periods and slashes are
not allowed. Enter a Description for the building. Example description is “This is a 50x100x12 building with 2
framed openings.”
Click on OK to save the building as template. When you do this, all items related to the building will be saved. The
building code information, customer information and pricing information from the Structure setup screens will not
be saved. Save the building as a structure template to save this information. Note that templates must be saved in
the directory where the program is loaded (e.g., C:\WINBLDG) while structure files can be saved to alternate
directories.
Note that the building template will save the current building only. If you have more than one building in the
structure, you will need to save the structure with all buildings or save each building as a template separately.
STRUCTURE TEMPLATE
Create a structure template by opening an existing structure or creating a new structure. Enter all information you
wish to have saved. Saving a structure as a template will save all buildings in the structure as well as the building
code, customer information and pricing. You can also save a structure with no buildings. The following screen will
appear when you choose Save Structure as Template from the Structure menu.
Enter the Filename (8 characters maximum). Apostrophes, quotation marks, commas, periods, slashes and
spaces are not allowed. Enter a description. The description may include spaces. Do not press <Enter> in the
description box. Click on OK to save the structure template. Note that templates must be saved in the directory
where the program is loaded (e.g., C:\WINBLDG) while structure files can be saved to alternate directories.
NEW STRUCTURE
Choose New Structure from the File menu or click on the icon to create a new structure. The following screen will
appear.
Choose a structure template (see previous page for instructions on creating a structure template) and click on OK
to continue. In the Create a New Structure dialog box, enter an eight character filename. Apostrophes, quotation
marks, commas, periods and slashes are not allowed. Click on Save. The structure template that you have
chosen will be loaded. If the structure template loaded has no buildings, you must add a building to the structure. If
it has one or more buildings, enter the information needed and run the building as usual.
NOTE: You will need to select a structure template compatible with the input units you desire (imperial or metric).
Report output units can be specified on the Structure Setup screen (see the Structure Input section of this
manual).
To add a new building to the structure, click on the icon or choose New Building from the Structure menu. The
following screen will appear:
Choose the building template that will provide a default building geometry.
Input the Building Name. The building name can be a short description of the building or a sequence number for
multiple buildings in the structure. Apostrophe marks (‘), quote marks (“), commas, periods or slashes are not
allowed. This name will appear on the costing reports after the description.
If you have opened or created a structure template using a different building code than the building template, you
will want the load combinations recalculated. To have the program recalculate these, check the box next to
Recalculate Load Combinations.
To add a new frame to the building, click on the General Frame icon or choose General Frame ➜ Frame from the
menu. The following screen will appear:
Click on Edit to change the frame name. The frame name can be a short description of the frame or a sequence
number for multiple frames in the building. This name will appear on the after plotting reports following the
description.
Click on Delete to delete the frame from the building. The first frame on the building cannot be deleted.
To rerun this building at any time in the future, choose Open Structure from the File menu or click on the
icon. The building(s) may be run as many times as desired. When running a previously saved building, the
program will not allow you to change the input units from imperial to metric, or from metric to imperial.
When you make changes on a screen, you will need to evaluate all related input items. A few examples are:
If you change the length of the building, the sidewall bay lengths will be recomputed.
The endwall column spacing is computed for the new building width.
If you change the number of bays, new braced bay locations will be computed for wind bracing.
If you change the building length, new values will be computed for diaphragm panel lengths.
If your building had special endwall column spacing for framed openings with omit jamb conditions, the input on
these screens may no longer be valid.
CALCULATIONS
The dialog boxes on the following page will appear after you make changes on some of the screens. These boxes
show the Calculations that the program will perform. To skip a calculation, uncheck the box. The first box will list
calculations for the outside of each building. At the top of this window is the name of the current building. Click on
Next to go to the calculations for each frame. At the top of this window is the name of the current frame. If you
want to go back to the previous screen, click the Prev button. Click the Next button to advance to the next frame.
When you click the Finish button, the calculations begin.
For example, a change to the building type, building width, or slope will cause the box for Purlin Spacing to be
checked in the Building Calculations dialog box. If you do not want the purlin spacing recalculated, you must
uncheck the purlin spacing checkbox so that it will not recalculate.
Occasionally while running PrecisionPlus the warning or error stating “Please contact Loseke Technologies, Inc.
soon for a program update” may appear. When this occurs, follow these steps:
1. In the PrecisionPlus program, go to File, Counter Update. A screen will appear which states “Do you want to
continue?”. Choose YES and contact Loseke Technologies, Inc.
2. The next screen contains a code number. Each code number has a specific access number that is obtained
from Loseke Technologies, Inc. Input the access number provided by Loseke Technologies, Inc. and click OK.
If the incorrect number is input, an “Invalid Access Number” message will appear. Choose OK and the
program will terminate. The above steps can then be repeated.
HELP MENU
The Help selection has the options described below. Note: You must have a PDF viewer loaded, and its path
specified inside PrecisionPlus to access Users Guide, Product Guide and Design Manual. See the Program Setup
section of this manual.
Users Guide
You may select this option to view the Users Guide in PDF format.
Product Guide
You may select this option to view the non-drawing portions of the Product Guide in PDF format.
Design Manual
You may select this option to view the Design Manual in PDF format. Note: The building code examples are
provided in separate PDF files in the Product_Guide subfolder of the directory where PrecisionPlus is installed.
Access these by using My Computer or Windows Explorer, and clicking on the preferred file to launch your PDF
viewer.
Plotting Manual
You may select this option to view the Plotting Manual in PDF format.
About/Tools
Here you will find information about the version you are running, and how to contact Loseke Technologies.
View Files in Working Directory will launch the Windows Explorer and display the folders and files. The default
folder is the directory where PrecisionPlus is installed. All functions of Explorer are available (copy, move, etc.).
Directory Report can be used to create a report of the displayed files in a specified directory. You can choose to
display all files or selected files. The pre-defined categories are EXE; DLL; RPT; EXE and DLL; EXE, DLL and
RPT; ASC; BLT; DAT; DWG; INP; MDB; PRN; STR; STT; and All Files. You can also specify desired file
extensions and/or names to be displayed. The file names as well as extensions, date, time and size will be shown.
Clicking Ok will create a text file report named _DirRpt.txt in the folder where PrecisionPlus is installed. Clicking
Close will close this screen without creating a report. You may be asked to use this tool when consulting with our
support staff.
Load Sentinel Driver will launch the sentinel driver install program. See the Loading section of this manual for
additional information about the sentinel and related driver.
Update Structure/Inventory can be used to update structure files, templates and inventory files from prior versions
of PrecisionPlus. This is required only for files which have not been incrementally updated with each new release
version of PrecisionPlus. You have the option of updating a single file, or all files of the specified type in the
directory selected.
When inputting a building, the Calculations screen will allow you to modify the default by checking or unchecking
Standard Member Size Initialization and Enhanced Member Size Initialization for each frame.
Enhanced depths are assigned by using the frame design programs with constant member sizes to obtain
member forces. These forces are then used to determine the best flange and web sizes over a wide range of
depths for critical points along the frame. The resulting calculations are used to populate the General Frame input
screens. The user may modify these values on the General Frame input screens.
The enhanced depth initialization program will use the following values from the Mainframe Design Constants:
Max Mem. Length to Web Depth Ratio Column (MAX COL)
Max Mem. Length to Web Depth Ratio Rafter (MAX RAF)
The following formulae are used by the program to determine minimum column depth and minimum rafter depth:
COLUMN MIN DEPTH (IN) = COLUMN LENGTH (IN) / MAX COL
RAFTER MIN DEPTH (IN) = SPAN (IN) / MAX RAF
SPAN is building width for clear span frames and distance from column to column for modular frames.
MILL MAINFRAMES:
Mill mainframes use the same initialization process as the welded plate to derive a range of mill section depths to
initialize.
SIDEWALL OVERHANGS:
When an overhang beam is added to the building, the software will set the member type for the overhang to match
the member type of the rafter. If an existing overhang beam is recalculated, it will leave the member type as it was
first set. The initial end of the overhang is at the mainframe column.
Welded Plate – Narrower overhangs, less than 5 foot (1.5 meters), will have 8 inch (203 mm) initial and
final depths.
Wider overhangs will have a final depth of 8 inches (203 mm).
The initial end is tapered as for 1/12 slope.
Mill – Mill overhangs of all widths will default to a range of 7 inches to 24 inches (178 mm to 610 mm).
Also on this tab are fields to control Wind Load unit display. Job Costing will display wind load values in PSF or
KPa up to and including the numbers input on this screen. Wind loads input in excess of these selections will be
interpreted as MPH or KPH.
In the Frame Optimization box, set the default member size initialization to either standard or enhanced member
initialization for built up members. See the Depth Initialization information in the General Section of this manual.
For the Bill of Material reports, use the radio buttons under View to specify if you want the reports to be displayed
and printed in PDF format, or as a text report. The selection you make here will control Reports, Output; Print All;
and Update [report] in Post Editor.
When choosing PDF Reports, use the radio buttons under PDF Report Logos to specify whether you want the
default Loseke logos for each report type, or if you want to create and use a custom logo with your company logo.
Rules for creating the custom logos are specified in the Output section of the Users Guide.
To generate a coil report and enable the ability to edit the coil inventory, you should check the Coil Report box.
While this box is checked, the program will automatically decrement the coil inventory each time a building is run.
It is suggested that you run your building first with the Coil Report unchecked, until you achieve a satisfactory run.
You should then check this box and rerun your building to get an accurate coil report.
Report Critical Loads only should be checked if you wish the default mainframe design report generation to include
controlling loads only. Uncheck it if you prefer the complete report of all loads. Note: When you select the Frame
Design Report from the Output menu, you may override this option.
Generate Frame Design Reports at end of run should be checked if you want the program to generate these
reports without having to select them from the Reports, Output menu. The Frame Summary report will always be
generated if this box is checked. The mainframe report will be Critical Loads or All Loads, depending on the
selection in the Report Critical Loads Only box. Having the program generate these reports by default is
convenient if you want to save or email them without viewing them first.
The Sort Fasteners option permits sorting of panel and trim fasteners in the costing reports. When the option is
selected, panel and trim fasteners (including stitch fasteners and trim lap fasteners) will be reported by surface
(front endwall, left sidewall, left roof, etc.) in subcategories by specific fastener usage. Some fasteners, such as
those for attaching base angle, are not associated with a single surface and are not sorted. When using the Post
Editor, the user has the option of associating a fastener with a surface.
Place Additional Parts in a separate Report Section should be checked if you want any additional parts to be in a
separate section of the bill of material reports. Uncheck the selection if you prefer additional parts to be listed with
other parts of the same inventory type (e.g., additional clips will be listed in the Clips section of the reports).
Report Critical Loads only for Purlins / Eave Struts/ Struts and for Girts should be checked if you wish the default
design report generation to include controlling loads only. Uncheck the selection if you prefer the complete report
of all loads.
There are two selections relating to the hole location report (Special Punching Diagram). The first applies only
when imperial output units is the selection under Structure Setup: the report can be in feet, inches and fractions of
inches, or in decimal inches. (Metric report is always in rounded millimeters.) The second is the selection of the
web orientation: open face or back of web faces the user, and different selections may be made for c-section,
eave strut and z-section.
GENERAL INSTRUCTIONS
FOR
PRINTER SETUP
Displays the name of the default printer and shows the printer connection. You may select a different printer from
the drop-down list and/or change the printer properties by clicking the Properties button. Choose the orientation of
the paper, either portrait or landscape. Specify the paper size and paper source for the printer.
STRUCTURE INPUT
NOTE: IN THESE PAGES OF DOCUMENTATION, WE HAVE SHOWN IMPERIAL UNITS FIRST, FOLLOWED
BY METRIC UNITS.
REMOVE BUILDING
Select this option to permanently remove the building from the structure.
SETUP
For the IBC 2012 and IBC 2015 building codes, and the ASCE 7-10 structural loading specification, load data is
available by state and county. This data comes directly out of the Metal Building Systems Manual, 2012 Edition
and includes snow load, wind load (based on Risk Category), and seismic acceleration factors. When selecting a
state and county, the corresponding load data is retrieved and placed into the non-editable text boxes shown
below, and the checkbox “Apply Load Data when clicking OK” is checked. You have the option to turn this
checkbox on or off. If the box is checked, the corresponding load data is applied from the fields below into the
structure file and the program performs the required recalculations that are necessary based on load changes. As
always, it is the users responsibility to verify and confirm the loading for your area.
Choose Metric or Imperial Output Units. (The input units are controlled by the structure template that you select
when you create a new structure.)
The inventory file associated with this structure is contained in the “Inventory File” box (grayed out).
To input the customer information, choose an existing customer from the left box by double clicking on the
customer’s name. Choose New to add a customer to the customer database. When you click on New, enter the
name, company, address, city, state, zip code, phone number and fax number in the dialog box. These fields will
be included on the Quote Confirmation report. You may also enter Second Phone, email and Contact Person
although these fields will not be included on the Quote Confirmation report. Do not use quotation marks in any of
the input fields. Click on OK to continue. To edit a customer, double click on the customer. When the customer
information appears in the address box, click on Edit and change field(s) on the Edit Customer screen.
You can modify pricing relationships by changing the pricing factors. Factors for panel, trim, structural and
accessories and hardware are multiplied by the material cost and markup shown in the inventory files. The factor
for services is applied to the labor cost and markup in the inventory files. Factors can be increased or decreased
to modify results. Thus, a factor can be changed to .95 to effect a 5% discount, or changed to 1.1 to effect a 10%
increase.
The Special Fee fields can be used to add an additional amount to the bill of material reports. For the Quote
Confirmation report, you can specify the text to be associated with this amount. The specified text is saved with
the current structure file. And you can elect to display or suppress the amount on the Quote Confirmation report.
The amount will always be shown on the Management, Sales and Shipper reports, and will be labeled Special Fee
on these reports.
SCREEN STRUCTURE SETUP – TAB (ASCE 7-95, ASCE 7-98, ASCE 7-02, ASCE 7-05, ASCE 7-10, BOCA,
IBC 2000, IBC 2003, IBC 2006, IBC 2009, IBC 2012, IBC 2015, MBMA, SBC, UBC)
This screen will vary depending on which building code option you have selected on the General Tab. The building
code choices that appear are the ones you specify in your data files. Refer to the Designer’s Guide in the front of
the Design Manual, and to the building code setup documentation (starting on page Design Appendix 11 in the
Design Manual) for detailed information about the various input parameters on these screens.
LOADS
LIVE LOAD TO FRAMES
Specify the live load to be applied to the frame (PSF or KPa).
WIND LOAD
Specify the wind load to be applied to the frame (PSF/MPH or KPa/KPH). When imperial units are
used, the program interprets wind load values over a user-specified value as MPH. For metric
input, the program interprets wind load values over a user-specified value as KPH. See the
Program Setup section of this manual for information about changing these user-controlled
values. For ASCE 7-10, IBC 2012, and IBC 2015, this is the Ultimate Wind Speed or Ultimate
Wind Pressure (strength design intensity).
.
Copyright 1992 Melvin R. Loseke effective Version 8.8.76
All Rights Reserved
Loseke Technologies, Inc. Structure Input… 6
Building Systems Software
CONNECT BUILDINGS
To connect buildings, add the desired number of buildings to be connected to the same structure file (.STR). In
PrecisionPlus, select Structure ➔ Connect Buildings.
Each building will be labeled with a green number (this number will be shown in parentheses after the building
name in the drop-down lists referenced on the following pages). To move a building, left click and drag it to the
desired location. When buildings are connected, you can move the connected set of buildings by left clicking the
anchor building and dragging it to the desired location. Buildings can be rotated counter clockwise 90 degrees by
right clicking on any building.
Endwall column
Peak
Mainframe
Column
Front Endwall
On each building picture, the building number will be placed in the corner between the left sidewall and back
endwall. Gray boxes indicate mainframe columns and expandable endwall columns. Blue lines indicate endwall
columns. The arrows that meet indicate the peak of a gabled building. A dashed line indicates the center of a
single slope or lean-to. An arrow will be placed at the right sidewall of a single slope or a lean-to. On the endwall,
an arrow will indicate the front endwall. Frames are numbered from front to back and include endwalls regardless
of type. Frames are indicated by red lines from one column to another.
A sidewall of one building can be connected to a sidewall of another building or an endwall of one building can be
connected to an endwall of another building. A sidewall of a building cannot be connected to an endwall of another
building.
SIDEWALL CONNECTIONS
Sidewall connections are input as described. Attachments to a symmetrical gabled building require changing the
frame symmetry to non-symmetrical on the General Frame ➔ Frame screen.
Select Building (A) and a Surface. Choose a Frame Line. Then choose Building
(B), Surface and Frame Line. Click on Connect to make the connection. The
program will indicate if the connection is acceptable. To undo the last successful
connection, select Undo, Undo or press Control Z. Building (A) cannot be a
building that is already connected to another building. Select the non-attached
building first. Disconnect will detach all connected buildings.
The exterior bay length will be computed by the program as the sidewall bay
length value minus the setback for an expandable endwall if an expandable
endwall is present.
It is the user’s responsibility to prevent conflicts between building connections and overhang locations.
ENDWALL CONNECTIONS
Endwall connections are input as described.
Select Building (A) and an endwall under Surface. Then choose Building (B) and
an endwall under Surface. Then input an offset in feet or meters, matching the
PrecisionPlus input units. See the information under the heading Offset in this
section of the user documentation for information about offset input.
Click on Connect to make the connection. The program will accept all endwall
connections. It is the user’s responsibility to make sure that the offset input and
slope of the buildings is appropriate. To undo the last connection, select Undo,
Undo or press Control Z. Building (A) cannot be a building that is already
connected to another building. Select the non-attached building first. Clicking on
Disconnect will detach all connected buildings.
Endwall connections will result in combined costing reports. None of the other
output reports will be combined. All elements are designed as if they were not
attached at endwall.
OFFSET
If you are connecting a front endwall to a back endwall or a back endwall to a front endwall, the left sidewall of
Building (B) will be the reference wall. Building (A) will then be placed as follows:
Offset of 0 Left sidewall of Building (A) aligned with the reference wall of Building (B)
Negative offset Left sidewall of Building (A) moved to the left of the reference wall of Building (B) by the amount
of the offset input
Positive offset Left sidewall of Building (A) moved to the right of the reference wall of Building (B) by the
amount of the offset input
If you are connecting a front endwall to a front endwall or a back endwall to a back endwall, the left sidewall of
Building (B) will be the reference wall. Building (A) will then be placed as follows:
Offset of 0 Right sidewall of Building (A) aligned with the reference wall of Building (B)
Negative offset Right sidewall of Building (A) moved to the left of the reference wall of Building (B) by the
amount of the offset input
Positive offset Right sidewall of Building (A) moved to the right of the reference wall of Building (B) by the
amount of the offset input
To connect the back endwall of Building 2 to the front endwall of Building 1 and center it:
Select Building 2 as Building (A).
Select Back Endwall for the surface.
Then select Building 1 as Building (B).
Select Front Endwall for the surface.
Input the Offset from left sidewall as 25.
VIEW STRUCTURE
To view connected buildings, make sure that one of the connected buildings is selected. Then, select Structure,
View Structure. If a non-connected building is active when the View Structure command is chosen, you will get a
message stating that “The current building is not part of a connected structure.”
Each building will be labeled with a green number. Structure frames will be labeled with the structure frame
number in a red box. Each structure frame is labeled one time.
The symbols shown on the left are for zooming and rotating the connected structure.
The Frame Member and Joint Locations option will be available after a successful run. It allows you to view
member numbers and joint numbers and their associated locations. The screen will be populated according to the
run option selected.
Centerline geometry will be used to make the line drawing. Member numbers are indicated in bold. Print the frame
member and joint locations sketch by clicking on Print. Member numbers and joint numbers will match the Frame
Geometry output report for that frame.
GENERAL INSTRUCTIONS
FOR
RUNNING THE JOB COSTING PROGRAM
ALLOWABLE INPUT
Input for comments, project description, and address on the Structure Setup screen will be alphanumeric. After
each question has been answered and/or each selection has been clicked, move the cursor to the next question.
On grids, move the cursor to the next field by using the arrow keys. On other screens, use the tab key to move to
the next field. Then the program will allow the next input to be entered. Acceptable input for some of the fields are
listed as choices on the screen when you click on the down arrow. On some questions the answer is typed, but for
others a button is selected. Click on OK when ready to move to the next screen. To display additional choices,
scroll by clicking on the arrows. To quit from a screen without saving the changes, choose Cancel.
Select Run Structure from the Structure menu or click on the Run Structure icon
INSTRUCTIONS
FOR
EACH INPUT SCREEN
NOTE: IN THESE PAGES OF DOCUMENTATION, WE HAVE SHOWN IMPERIAL UNITS FIRST, FOLLOWED
BY METRIC UNITS.
For symmetrical gabled buildings, left sidewall height and left roof slope will be editable. For non-symmetrical
gabled buildings, the right sidewall height, right roof slope and peak location will also be editable. Enter values for
any two of these three items. Select the Choose Value to Recalculate button next to the third value; this value is
uniquely determined by the geometry of the frame and is calculated by the program. The peak location is the
horizontal distance from left sidewall to peak. On mono-slope buildings, the "peak" is used to divide the roof beam
into left and right rafters. For these buildings, "peak" is calculated by the program to be at mid-span for clear span
buildings, or at the interior column closest to mid-span on buildings with frames having interior columns. See the
drawings in the General Frame Input Section of this manual.
Use Foundation Level to input the distance from the ground to the top of the foundation (foundation depth). The
program will use this to calculate the mean roof height for mainframes, endwalls, diagonal bracing, purlins and
girts.
Select the frame to be located at the end of each bay. Click on the column for Frame Located at End of Bay. Each
frame that has been added to the current building will be listed in the drop-down box. (To add a frame to the
building, see the documentation in the General Frame Input Section of this manual.) Note: The last row of this
column will not accept frame input (because this is the back endwall). Input the frame on the Endwalls screen.
For snow loading on the roof, specify if the Heating Conditions are Heated Greenhouse or All Others. The roof
surface can be specified as Smooth or Others for the MBMA building code and as Unobstructed Slippery or All
Others for the ASCE, BOCA, IBC, SBC and UBC building codes.
Specify if floor live load should be included in the building weight for seismic calculations. (IBC/ASCE specifies that
a minimum of 25% of the floor live load should be included in areas used for storage.) If you check this option and
Copyright 1992 Melvin R. Loseke effective Version 8.8.76
All Rights Reserved
Loseke Technologies, Inc. Job Costing Input… 3
Building Systems Software
no floor live load is specified, or the Floor Live Load usage factor is zero, your selection will not impact the
calculations.
If you wish to use Unbalanced Snow Loads for Mainframes, check that selection. Refer to information about
unbalanced snow loads under the heading SCREEN LOAD COMBINATIONS in this section of the manual.
Additional snow loading options for mainframes, purlins and overhangs may be visible depending on the building
code you have selected. For the IBC 2012, IBC 2015, and ASCE 7-10, the minimum balanced snow load will be
applied if that option is checked. Refer to the Design Appendix, Building Default Settings for information about
these options. Refer to calculations for each building code sample for the ground to roof snow load calculation.
Select the enclosure condition: Enclosed, Partially Enclosed or Open. Refer to page Design Appendix 13-1 and
following in the Design Manual for additional information about each building code type and its requirements.
You will not be able to exit the screen until the sum of the spaces on the endwalls is equal to the width of the
building. Note the following about endwall column spacing.
A. Roof diagonal bracing locations are based on the location of the displayed column spaces on the front
endwall.
B. Moving the endwall column spacings to dimensions resulting in columns located between roof purlins
may result in excessive weak axis bending loads for the specified rafter, a condition for which the
program does not automatically check.
C. Endwall spacings should be the same for front and back endwalls. If this is not possible, you should
make a second run specifying only half as many braced bays as will actually be used. This second run
should be used for bracing member sizes.
For the endwall framing, a selection of “cold-formed” allows the program to design endwall framing members
using sections in the C-Sections Inventory File. If none of these members is structurally adequate for the imposed
conditions, the program will automatically use mill shapes. Therefore, an endwall specified as cold-formed may be
designed using mixed member types. If this condition is not desired, select “mill” to force the program to use only
the Mill Sections Inventory File.
Front and back endwall types are selected from the choices displayed when you click on the arrow. Choose from
the following options:
Endwall type EW Corner Col. EW Int. Col.(s) EW Rft. Girts and Panel
Std end frame – fully paneled Y Y Y Y
Std end frame – open to gable Y Y Y Y, in gable only
Std end frame – open to roof Y Y Y N
Exp MF at EW – fully paneled N Y N Y
Exp MF at EW – open to gable N Y N Y, in gable only
Exp MF at EW – open to roof N N N N
No end frame – open to roof N N N N
Half loaded MF at EW – fully paneled N Y N Y
Half loaded MF at EW – open to gable N Y N Y, in gable only
Half loaded MF at EW – open to roof N N N N
Y = Yes, N = No
You may select a different option for each endwall; thus “Std end frame – fully paneled” can be chosen for the
front, and “No frame open to roof” for the back endwall. Example: to estimate a roof unit only, select “Std end
frame – open to roof”, “Exp MF at EW – open to roof”, or “No frame – open to roof”, depending on the frame type
desired at the endwall. Choosing any "Exp MF at EW" or “Half loaded MF at EW” option will display a drop-down
list of frames from which to choose. Each frame that has been added to the current building will be listed.
When “flush” is specified, the girts are designed as simple span and you can choose to use either c- or z-section
types. (“Flush” is not an available option for purlins.) When “exterior” is selected, you determine the design method
by selecting “simple span” or “continuous”. If you choose Simple Span, either type of section can be used;
however if you choose Continuous the program will use a z-section.
Certain locations of wall openings can cause the continuous girt options to be unsafe. Check with your engineer
for specific guidelines. When “continuous” is selected for endwall girts, simple span girts may occur above the left
sidewall height. The program does not check for overstresses for this condition.
On symmetrical gabled buildings, the left sidewall girt type controls design of columns and rafters. Input the
building configuration so that the left sidewall will have the more critical condition. If you are unsure which is the
more critical case, run the building both ways. Selecting different girt types from sidewall to sidewall constitutes an
“offset peak” case, which must be accommodated by specifying the building as non-symmetrical. Similarly
specifying different girt locations creates a non-symmetrical case. (The symmetrical/non-symmetrical option is
selected under Building, Geometry.)
You also have the option to choose your preferred orientation for sidewall girts and roof purlins. Specify the
orientation of the outside flange: upslope or downslope.
If through-fastened was chosen as the lateral stability option, you need to be certain that all data for the building
complies with all AISI S100-12 specifications for through-fastened. Through-fastened is not a valid choice when
any span length exceeds 33 feet. If through-fastened is selected when design is continuous and adjacent span
lengths vary by more than 20%, the simple span through-fastened factor will be applied in those spans.
If lateral braces were chosen for top or bottom flange, you must review the related lateral bracing screen(s). When
the through-fastened option is selected, the eave strut is designed as fully braced at the outside flange and
laterally braced at the inside flange. The number of lateral braces specified under Roof Lateral Bracing will be
used for eave strut design. Check with your engineer and see the Designer’s Guide in the Design Manual for
information about purlin, strut and girt design.
The program displays default answers for diaphragm panel lengths for each sidewall and the roof. Specify the
amount of uninterrupted panel that is available. (Diaphragm panel strength is specified in the Panel Inventory.)
Remember that most standing seam roof systems do not provide any diaphragm action contribution. See page
File Maintenance 1-4 (in the File Maintenance Manual) for information on setting diaphragm panel length defaults.
Torsional bracing selections are used to direct the program to remove all bracing in one sidewall and to attempt to
compensate for this by transmitting all the longitudinally applied forces to the remaining braced sidewall. For
example, if Omit Left Sidewall Bracing is checked, the program will select bracing and strut sizes necessary to
transfer all bracing-related loads to the right sidewall. Torsional bracing cannot be selected on lean-to buildings (a
lean-to building is always processed as a torsionally braced system). See the Designer’s Guide for additional
information about usage of torsional bracing.
Endwall diagonal bracing is based on the user-controlled option (see the File Maintenance section of the user
documentation). If you select a set-up option to use diaphragm panel strength, the program will attempt to use
panel diaphragm to eliminate diagonal bracing members. The program determines the amount of diaphragm panel
length based on the size of the endwall and the input openings on that wall. (Diaphragm panel strength is specified
in the Panel Inventory.) If the option is set to use diaphragm only (i.e., never use bracing members), the program
will report the results and continue. In this case, if diaphragm is not adequate, you will need to provide stability in
some other manner.
If you have selected an option for bracing members (either after trying diaphragm or without trying diaphragm),
bracing members will be designed based on the specified locations. If the bracing members are not adequate, or
no braced spaces are specified, an error will be reported in the building status and in the endwall diagonal bracing
report. Endwall bracing tension members are sized by the program based on the brace locations specified by the
user.
When a new building is created, initialization will be based on the endwall diagonal bracing setup option and, if
bracing is an option, will default to the endwall diagonal bracing stored in the building template. If a building has an
expandable or half loaded mainframe at the endwall, the diagonal bracing will be turned off, because the
mainframe is providing stability to the endwall. Otherwise, default locations are based on geometry of the endwall,
including openings; at least one bracing member will be placed in each direction. An endwall diagonal bracing
recalculation is triggered by changes to building width, height, slope, endwall column spacing, endwall type, loads,
Copyright 1992 Melvin R. Loseke effective Version 8.8.76
All Rights Reserved
Loseke Technologies, Inc. Job Costing Input… 6
Building Systems Software
building code data and location(s) of opening(s). The recalculation can be turned off by the user if desired. Note:
Recalculation does not apply if diaphragm only is the selected option.
Refer to the Designers Guide section on Endwall Stability / Endwall Diagonal Bracing for additional information.
SCREEN PANELS – TABS FRONT ENDWALL, BACK ENDWALL, LEFT SIDEWALL, RIGHT SIDEWALL,
ROOF
On these tabs, specify roof and wall panel configuration, the gauge of the material and finish type, for the exterior
panel, and for liner panel if needed. The panel, fastener and insulation choices specified on the left roof will be
used for the right roof also. Panel configurations displayed are from the Panel Inventory. Panel Color/Finish
choices are displayed based on the Panel Suffixes specified in the Finishes Inventory (see File Maintenance page
2-4 for information on specifying finishes). To have a color designation appended to the panel description on the
shipper report, select a suffix other than None. On a wall tab, select a panel and then click on the Typical button to
set all walls to the current panel choice. Fastener selections specify the sheeting to structural fasteners to be used.
Stitch selections specify the sheeting sidelap fasteners to be used. Note that liner panel information will be used
only if liner panel locations are specified.
It is possible to estimate a building without any roofing (panel, mastic, closure and fasteners). Under panel type
choices, select the option, typically called “NOR” for “no roof”. The program will then produce estimations without
the roof. The “NOR” choice must never be requested as wall panel.
Insulation options displayed are from the Insulation Inventory. The program does not automatically choose longer
fasteners for extremely thick insulation, but allows you to make the selection. On the Roof tab, you have the option
to specify a double layer of insulation. Check the box if you want the program to calculate double the roof area.
If you selected an endwall open to the gable or open to the roof and then select insulation for that endwall, the
amount of insulation will be reduced by the unpaneled area.
If you select “YES” to place wire between insulation and purlins (to provide support for insulation), wire must be
included in the Insulation Inventory.
See page File Maintenance 3-3 in the File Maintenance Manual for drawings of various base support conditions.
There is an option to specify a concrete notch or no concrete notch. This choice affects the wall panel lengths,
whether or not the anchor bolt setting plan displays the concrete notch, and whether or not the sheet recess
drawing (SRD.DWG) is displayed on the anchor bolt details page.
SCREEN TRIM AND RIDGE CONDITION -- TABS FRONT ENDWALL, BACK ENDWALL, LEFT SIDEWALL,
RIGHT SIDEWALL, AND ROOF
This screen asks for information about trim fasteners and trim finish. Fastener choices in the drop-down box are
those in the Hardware Inventory. You may specify up to three different trim fasteners. Typically the first fastener is
used to attach trim to adjacent sheeting; the second fastener is used at trim splices and to attach discrete pieces;
and the third is available as needed for your product line (commonly pop rivets). The selection of the number of
fasteners of each type is based on your input in the Trim Inventory (see the File Maintenance manual for details).
Select a trim finish from the list. The choices available are read from the trim inventory, cross-referencing the
Finishes Inventory. The program does not provide for mixed trim finish, such as color gutter and rake, with the
remainder of the trim in white. Trim Suffix choices are displayed based on the suffixes specified in the Finishes
Inventory (see File Maintenance page 2-6 for information on specifying finishes). To have a color designation
appended to the trim description on the shipper report, select a suffix other than None.
When inputting data for a wall, you can choose Use Base Trim if you want the program to detail panel on this wall
with the base trim specified in the Panel Trim Setup (see the File Maintenance Manual for instruction). Or choose
Omit Base Trim to detail panel on this wall without base trim. If the wall has liner panel, the base trim selection will
apply to exterior wall panel only.
Notes:
If no base trim is associated with the panel, the Base Trim Option on this screen will not impact the output. Base
trim is always removed for openings starting at floor line.
Click Typical to use the same data for all surfaces of the current type (i.e., all walls, or both roof surfaces). Click
OK to exit and save your input, or click Cancel to exit without saving.
Remove a space by selecting it and clicking the Delete button. If you want the opposite endwall or sidewall to
match the girt spacing on the current wall, click Typical. If you want girt locations on all walls to match the current
wall, click Typical All Walls.
If you need different girt spacing on left and right sidewalls, the frame must be specified as non-symmetrical.
Symmetrical frame design is based on girt locations at the left sidewall. For each sidewall girt location, indicate if a
flange brace is to be used by toggling Yes or No. The maximum number of girt spaces on a wall is 20. The sum of
the girt locations must exceed the wall height (the program will internally calculate the exact size of the last space).
SCREEN OVERHANGS
Overhangs may be added to the building. Location is the distance from the front endwall or left sidewall to the
beginning point of the overhang (similar to that for openings). See the OPENING LOCATION drawing in that
section of this manual. Sidewall overhangs must traverse at least two frame lines. Overhang length is the
dimension of the overhang along the side or end of the building. Overhang width is the horizontal projection of the
overhang perpendicular to the sidewall or endwall. Dead load added to endwall overhangs will be applied as
collateral load when designing purlins, strut purlins and eave struts. Dead load added to sidewall overhangs is
applied both to sidewall overhang purlins and as collateral load when designing the mainframe. The Overhang ID
box will be populated by the program and is used to reference the purlin design report for sidewall overhangs.
Roof panel for overhangs is computed and priced by the program. Overhang items such as trim at the building and
soffit are priced per square foot (see pages File Maintenance 2-14 and following in the File Maintenance Manual).
The number of overhang braced locations is used for endwall overhangs when “Use lateral braces” is selected for
the purlin support condition. For overhangs less than 5 feet (1.52 m) wide, the program will assume 1 lateral
brace. For overhangs greater than or equal to 5 feet wide, the program will use the input value (minimum of 1).
SCREEN ACCESSORIES
This screen allows you to input accessories. You can input multiple accessories on a single line. Click on the grid.
Then, click on the wall on which the accessory is to be placed. View the accessories available in the Hardware
Inventory File by clicking on the + sign. This will display a list of choices within that category. Choose the desired
accessory. Input the quantity of this item. Click on the next available line in the grid to repeat these steps for
additional accessories. The maximum number of different entries for each accessory type is 16 (e.g., you can
input up to 16 different types of windows, and may specify the desired quantities of each).
Select the desired part category from the drop-down list and specify the quantity. If the part is a part with length,
you will also specify a length. For c-sections and mill sections, you can indicate if the endwall labor pricing is or is
not to be used. When specifying a non-inventory item, select the desired indicators, description, weight, pricing,
and length (if applicable). You may also input a partmark in the partmark field (if applicable) and it will carry over to
the shipper, or leave it blank if it does not apply. Click the Add button to add the item and it will be shown in the
grid at the bottom of the screen.
If you want to modify an item shown in the grid, click on it and click either Edit (to modify) or Delete (to remove).
When you select Edit for an item from your inventory, you will see the current pricing of the item from your
inventory and will be given an option to override that pricing. Markups are displayed for your convenience. They
cannot be modified; the program will automatically apply the related markup factor.
Clicking on Delete All will remove all items listed in the grid. When you have added and/or modified all desired
parts, click Ok to save and exit. Or click Cancel to exit without saving.
Additional parts will be reported in the associated section of the bill of material reports, or in their own section,
depending on the option you specify on Program Setup. These parts will be combined with similar items when
appropriate (e.g., the additional parts are bolts of a type already used on the building). Additional parts will never
be combined with items having part marks. The program does not detail the additional parts; you will need to
specify all required parts. For example, if you add a clip, you must also add the associated bolts.
NOTE: To delete parts from the bill of material, create a component order, or create/modify part groups, use the
Post Editor, documented in the Post Editor section of this manual.
SCREEN OPENINGS
Refer to the drawings on the following pages for information about inputting openings. Openings may fit between
columns, or may extend across columns. If an opening extends from one corner to another (full length of the wall),
the jambs are deleted. Users are responsible for avoiding interference between openings.
Start by clicking on the first line on the grid. Select an opening indicator by clicking with the mouse button on the
appropriate indicator. Indicator choices are:
Field Located
Factory Located (include both jambs)
Omit Near Jamb
Omit Far Jamb
Omit Both Jambs
Omit jamb choices are valid only for openings on walls with flush girts. If a corner column is used in place of a
jamb, the user has the responsibility of assuring that the corner column orientation is appropriate for such usage
(see page Plotting 1-7-3 in the Plotting Manual). When you choose to omit one or both jambs, the initial location
must be a column. A column may be used in place of a jamb for only one opening (i.e., a column cannot be used
as a near jamb for one opening and as a far jamb for another). Total width of the opening will be the clear
dimension between the columns and will, therefore, be less than the input width when columns are double c-
sections or mill shapes.
If the option for omit jamb columns is set to 1 in the Framed Opening Details file (see page File Maintenance 3-5
in the File Maintenance Manual), the program will try a single c-section design on omit jamb choices on a mill
endwall. If the single c-section column is not adequate for design, the program will try mill sections. Double c-
sections will not be tried. If a single c-section is used as a column in this case, the program will orient the section
as appropriate for the jamb usage, rather than using the standard endwall usage. Using option 1 will also cause
single c-sections on cold-formed endwalls to be rotated when used for an omit jamb condition.
If you select field located, you may input a quantity greater than one. Choose a wall from the diagram and input a
horizontal location from the reference corner. Field located openings will include two structural jambs of a length 2
feet greater than the header height specified, a header, a sill (if applicable), clips, hardware, and trim for the
opening. Sheeting will not be automatically deducted for field located openings, and girts are not deducted.
If you select a factory located opening, the quantity must be one. Choose a wall from the diagram and input a
horizontal location from the reference corner. Structural jambs, a header, a sill (if applicable), clips, hardware, and
trim are provided. In addition, if an opening extends completely across one or more panels, the program
automatically deducts sheeting for the opening.
You may specify either standard or special cover, or none for each opening.
The Jamb Top option for Factory Located, Omit Near Jamb or Omit Far Jamb openings will default to either Full
Length or Stop at Girt (depending on the option specified in the Framed Opening Details setup file). You may
change to another option by selecting the appropriate row in the grid and clicking the preferred Jamb Top option. If
Stop at Girt is selected and no girt exists above the opening, the program will process as though Full Length were
selected. If the opening is field located or both jambs are omitted, the Jamb Top option will default to N/A (not
applicable) and cannot be changed unless the Indicator is changed. Note: Columns used as jambs will always be
detailed to extend to the top of the wall.
The Liner Panel option applies only when liner panel has been specified in the bay (or endwall space) for this
opening. Select Remove to omit liner panel from the opening area. If you do not want to remove liner panel, select
Leave. If you do not specify an option, the program defaults to removing the liner panel. Note that the liner panel
option does not apply to field located openings.
The program designs endwall columns as braced laterally by the adjoining girts. If an endwall has an opening that
runs the full building width, the program will automatically design the columns as unbraced. Wind loads are applied
to the endwall columns as concentrated loads at the girt locations. Large open wall areas diminish the wind loads
applied to the columns. Such a condition may result in columns that are adequate for vertical loads, but not
adequate for applied wind loads. If an endwall designed as open were later enclosed, the column sizes might be
incorrect. If you anticipate such a case, run the program twice, once with the desired amount of open wall area
and again with a fully enclosed endwall, and use the heavier endwall columns.
If opening input dictates a building with no sidewall girts on either sidewall, the program will use the first section in
the first girt set to determine assumed girt depth. If only one sidewall has girts, the program will assume that both
sidewalls have the same girt depth. These girt depth values are used for design and detailing such as determining
span of frame and placing anchor bolts. Refer to the Designer’s Guide for additional information on girt design
criteria, and usage of non-symmetrical indicators.
OPENING LOCATIONS
BACK ENDWALL
(2)
FRONT ENDWALL
(1)
NOTE: Factory located framed opening, open wall area and overhang location information is defined from building
corners as shown by the arrows.
Use Roof Collateral Dead Load to input any dead loads supported by the purlins, endwall columns and endwall
rafters, such as sprinkler systems (PSF or KPa). This load will be applied only for load combinations without wind
and with a Col. Dead factor greater than 0.00 on the Load Combinations screen.
The Roof Seismic (Longitudinal) Load is initialized based on the seismic information specified under Structure
Setup as well as the building input. It is recalculated whenever the “Seismic Load” recalculation occurs. You may
modify this value as desired (KIPS or KN). This seismic loading must be handled by the roof and sidewall strut and
bracing system.
The common purlin space can be edited on the screen. Change the common purlin space and click on OK to have
the program recalculate the detail purlin spaces for both roof surfaces.
Use the Add or Delete button to adjust the number of purlin spaces. Clicking Add will copy the current purlin space
and insert a copy immediately following the current purlin space. The purlin spaces must total the required width
(FT or M). To input a new purlin space or spaces, input the space value or input the number of spaces @ the
space value and click the down arrow. For example, an input of 4 @ 60.208 will replace the values on four lines
with 60.208 for the space value for a total of 20 feet, assuming a 1 on 12 slope. After you have input your desired
spacing, it is recommended that you use Compute Selected Space to assure the sum of the spaces is adequate to
cover the roof surface. Click on the space that you want to compute and then click Compute Selected Space.
If you have adjusted the spacing on one roof surface and want the other surface to match it, click Typical. If you
would like the purlin spaces on the right roof to match the left roof, type SAME in the first space on the right roof.
If you need different purlin spacing on left and right roofs, the frame must be specified as non-symmetrical.
Symmetrical Gabled frames are designed using the left roof purlin spacing and flange brace locations. A
maximum of 205 purlin spaces will be used when designing a frame. If more spaces are specified, only the first
205 will be used.
When a recalculation of load combinations occurs, the collateral dead load factor for load combinations involving
wind will be set for 0.0; for combinations without wind, the program will assign 1.0 for the collateral dead load
factor. The collateral dead load for mainframes is specified under General Frame Setup. The collateral dead
load for purlins, endwall columns and endwall rafters is specified under Building Loads. In the Design Manual,
refer to page Design Appendix 11 and following for information about changing default building code input.
The right-hand side of the Load Combinations screen provides a summary of data currently associated with the
selected load combination. Click the Edit button to invoke the screen on which you can modify these values. Some
factors are not available for selected elements or combinations. For example, earthquake (seismic) combination
factors impact only mainframe and diagonal bracing design, and floor loads apply only to mainframes.
Deflection limits are specified for elements designed for deflection. Purlins, endwall rafters, endwall columns,
endwall girts, and sidewall girts are designed for deflection. The deflection limit for endwall bracing is used to
control sidesway of endwall columns to which endwall diagonal bracing members are attached. The default
deflection limits are read from the building template. On the Load Combinations input screen, use the drop-down
list to select A, B or C as the desired limit for this structure. To modify the deflection limits, select the load
combination and click Edit. Input your desired values for Deflection Limits A, B and C. You can change the limit for
one load combination and click Typical All Loads to apply the same limit to all combinations for that element (e.g.,
all purlin combinations). Or you can specify a different deflection limit for each combination.
NOTE: The program does not design for deflections for mainframes or for roof and sidewall bracing. Therefore, no
deflection input is available on the screens. Mainframe deflection is reported on the Frame Design report. The
frame input can be adjusted to assure the deflection conforms with the project requirements.
For unbalanced snow loading (skip loading) on mainframes, in Building Setup check the Use Unbalanced Snow
Loads option. If this is not checked, PrecisionPlus will treat the Snow load as a true snow load (i.e., unbalanced
snow factors will not be used). For the related load combination, the Unbalanced Snow Load box on the load
combination screen will default to checked, permitting editing of the calculated factors for Windward and Leeward.
The windward factor is applied to the lighter loaded roof surface, and the leeward to the heavier loaded roof
surface. The program automatically checks for the case where the direction of loading is reversed.
For unbalanced snow loading (skip loading) on purlins, use the Wind and Snow Load fields. For full loading on odd
numbered bays, partial loading on even numbered bays, input a Wind Load factor of –1.000; use the Snow Load
factor to input the skip load factor. For full loading to even numbered bays, partial loading to odd numbered bays,
input a Wind Load factor of –2.000; use the Snow Load factor to specify the skip load factor.
Load combinations for designing mainframe members and connections can be applied and reported in a variety of
ways:
Other mainframe load combinations can be used for reporting without impacting design of any elements:
Separate load combinations may be applied only for design of mainframe connections:
Usage indicators are shown on the design reports. For your reference, here is a list ordered by Usage Indicator:
For mainframes, purlins, and girts, indicate if additional load/loads is/are associated with this load combination.
Select a Load Set from the drop-down list and specify the associated Factor. The number of load sets in the list is
based on the input on the Additional Loads input screen. Therefore, the additional loads must be input before
selections can be made on this section of the Edit Load Combination input screen.
NOTE: Only the factor associated with the load set will be applied to the additional load; the overall combination
factor and load factors for the various elements of the load combination will not be applied to the additional load.
MEMBER LOCATION
General location of the load, as shown in the legend on the input screen:
1 = left column
2 = right column
3 = rafters between left steel line and peak
4 = rafters between right steel line and peak
5 = interior column
6 = left overhang
7 = right overhang
8 = floor beam
For clear span Single Slopes and Lean-Tos, the peak is assumed to be at the center of the rafters. If there are
interior columns, the peak is assumed to be at the interior column closest to the center of the building, measured
from the left sidewall.
INTERIOR COLUMN #
The number of the interior column, numbering from left to right, to which the load will be applied or the number of
the floor beam, numbering from left to right and bottom to top with all floor beams in a single span numbered
before those to its immediate right. Use this field only if MEMBER LOCATION is 5 or 8.
LOCATION
See notes under each load type code.
0= MEMBER CONCENTRATED
LOAD
VERTICAL CONCEN LOAD vertical concentrated load (KIP or KN)
HORIZONTAL CONCEN LOAD horizontal concentrated load (KIP or KN)
ROTATIONAL CONCEN LOAD moment concentrated load (K-FT or KN-M)
LOCATION Location is from the base of the column up, or from the associated
sidewall steel line over, to the beginning of the load.
For overhangs, load is from unsupported end of the overhang
towards the building. For floor beams, location is from left side of the
floor beam to the beginning of the load. (FT or M)
3 = TRAPEZOIDAL LOAD
INIT TRAP LOAD magnitude of initial end of load (K/FT or KN/M)
FINAL TRAP LOAD magnitude of final end of load (K/FT or KN/M)
TRAP LOAD WIDTH width of trapezoidal load (FT or M)
LOCATION Specify the location of the initial end of the trapezoidal load. (FT or M)
Trapezoidal load must fall completely within a member, not on the
end deduct. Therefore, LOCATION + TRAP LOAD WIDTH must not
exceed the location of the end of the member.
Location for right rafter of lean-to and right rafter of single slope is
from the right sidewall.
4 = UNIFORM LOAD
VERTICAL UNIFORM LOAD vertical load (K/FT or KN/M)
HORIZONTAL UNIFORM LOAD horizontal load (K/FT or KN/M)
UNIFORM WIDTH A value of zero will cause loads on rafters to be placed on the
specified side of the peak. A value of zero is input to load all
members of a column. Positive values will cause a load to be placed
starting at LOCATION and extending across the specified width.
Copyright 1992 Melvin R. Loseke effective Version 8.8.76
All Rights Reserved
Loseke Technologies, Inc. Job Costing Input… 17
Building Systems Software
Uniform loads must start and stop at member ends; the program will
start and stop applying the load at the member end nearest to that
specified on the screen. (FT or M)
LOCATION Specify location on the member from the base of the column up, or
from the associated sidewall steel line over, to the beginning of the
load when UNIFORM WIDTH is greater than zero. (FT or M)
For overhangs, load is from unsupported end of the overhang
towards the building. For floor beams, location is from left side of the
floor beam to the beginning of the load when UNIFORM WIDTH is
greater than zero. (FT or M) Not used when UNIFORM WIDTH is
zero.
Refer to the following page for illustrations of placement of uniform load, member concentrated load, and
trapezoidal load on a frame.
STEEL LINE
LOCATION UNIFORM
LOAD
STEEL LINE
HORIZONTAL
CONCEN
LOAD
LOCATION
STEEL LINE
STEEL LINE
Positive direction denotes loads acting from the outside of the building toward the inside (for example, gravity load
on the roof or wind pressure on a surface). Negative direction denotes loads acting from the inside of the building
toward the outside (such as wind suction). All loads are applied in the plane of the web of the purlin or girt; i.e.,
normal (perpendicular) to the supported surface.
LOCATION
Location is from the front endwall for purlins or sidewall girts. Location is from the left sidewall for additional loads
on endwall girts. See specific notes under each load type code.
0 CONCENTRATED LOAD Concentrated loads may be placed at any location other than the
supports.
Normal Concen. Load Concentrated load applied in the plane of the web, normal (perpendicular)
to the supported surface (KIP or KN)
Location For purlins and sidewall girts, input the distance from the front endwall to
the location of the load; when loading front endwall cantilevers, input a
negative location. For endwall girts, input the distance from the left
sidewall to the location of the load. (FT or M)
JOINT LOADS Joint loads are located at the ends of member but not at a support. The
output will describe all non-cantilever joint loads as being located at the
right end of the left member in the bay.
1 INITIAL END JOINT LOAD
2 FINAL END JOINT LOAD
Normal Concen. Load Concentrated load applied in the plane of the web, normal (perpendicular)
to the supported surface (KIP or KN)
Location For purlins and sidewall girts, input the distance from the front endwall to
any location on the member; when loading front endwall cantilevers, input
a negative location. For endwall girts, input the distance from the left
sidewall to any location on the member (FT or M)
3 TRAPEZOIDAL LOAD Trapezoidal loads are valid only for purlins and cannot be applied to girts.
Init. Trap. Load Magnitude of initial end of load (K/FT or KN/M)
Final Trap. Load Magnitude of final end of load (K/FT or KN/M)
Trap. Load Width Width of trapezoidal load (FT or M)
Location Location of initial end of load. Trapezoidal load must fall completely within
a member. Therefore, LOCATION plus WIDTH must not exceed the end
of the member. Input the distance from the front endwall to the initial end
of the load; when loading front endwall cantilevers, input a negative
location. (FT or M)
4 UNIFORM LOAD Uniform loads are placed over the full length of the specified bay (or
endwall space).
Normal Uniform Load Uniform load applied in the plane of the web, normal (perpendicular) to the
supported surface (K/FT or KN/M)
Location Input any location within the bay. The program will load all members within
the bay specified. For purlins and sidewall girts, input the distance from
the front endwall to any location in the bay; when loading front endwall
cantilevers, input a negative location. For endwall girts, input the distance
from the left sidewall to any location in the endwall space. (FT or M)
NOTE: This input does NOT impact the design of floor beams.
RUN STRUCTURE
When you choose Run Structure or , three run options are available. Choose run option Design the Building
Shell and All Frames, Design the Building Shell Only (No Frames) or Design Selected Frame Only.
Design the Building Shell and All Frames will run the entire building(s) including all mainframes that have been
placed in the building(s). If the active building has been combined with any other building in the structure, the
program will run all of the buildings that are attached. Connected buildings will have frames labeled Str Frm 1, 2,
etc.
Design the Building Shell Only (No Frames) will run all of the building(s) except for the mainframes. The
FrameWeight tab becomes available. Input the weight of one frame, or a weight of 0.00 if your customer is not
purchasing the frames from your firm. Choose the Anchor Bolts for Sidewalls and the quantity for the anchor bolt
plot. If the building has interior columns, choose the Anchor Bolts for Interior Columns and the quantity for the
anchor bolt plot. If the active building has been combined with any other building in the structure, the program will
run all of the buildings that are attached. NOTE: Plotting will assume columns are pinned at the base.
Design Selected Frame Only will run the structure frame or building frame selected in the drop-down box Frame.
The Girt/Purlin tab becomes available. Input the desired section depth for the purlin/girt depth. The depths must
match the depths defined in the purlin/girt sets (zero is not a valid depth). These depths are used to determine
frame geometry, compute flange brace lengths, and to determine the correct set for clip/bolt call out. The purlin/girt
condition (flush or exterior) is determined by the input on the Purlin/Girt Support Conditions screen (see the
Screen Purlin/Girt Conditions & Structural Specifications portion of this section of the manual). NOTE: No Costing
or Post Editor reports are available from Design Selected Frame Only.
Choose the desired output option: Complete Building, Panels and Related Accessories, Trim Only, Secondary
Structural, or Accessories. Note that options other than Complete Buildings may or may not produce the exact
combination of items you desire. You will want to select Input Frame Weight as the run option in these cases, then
use the Post Editor and/or Additional Parts to adjust the bill of material reports to your specifications.
To automatically run plotting after a successful run, place a checkmark next to Run plotting when finished.
NOTE: IN THESE PAGES OF DOCUMENTATION, WE HAVE SHOWN IMPERIAL UNITS FIRST, FOLLOWED
BY METRIC UNITS.
FRAME
This screen determines the basic frame configuration. Enter the column type and number of interior columns for
each frame. Change to a different frame by choosing the frame name from the drop-down list. Click on New to add
a new frame based on the current frame. Click on Edit to change the frame name. The frame name can be a short
description of the frame or a sequence number for multiple frames in the building. This name will appear on the
frame reports, following the description. Click on Delete to delete the frame. Note that you can delete all but one of
the frames. However, you do not need to apply any frames to the building (e.g., you could specify a one-bay
building with standard endwalls).
The program also supports uneven column spacings, off-center peaks, and uneven base elevations.
SYMMETRY INDICATOR
Geometry symmetry indicator for Gabled buildings only:
Non-symmetrical Gabled
Symmetrical Gabled
Symmetrical Gabled will allow you to input information only for the left half of the frame. Members on the right half
of the frame will be dependent and wind loads will be applied in only one direction. Changing the span sizes for
non-symmetrical spacings between interior columns will change this indicator to Non-symmetrical Gabled.
STEEL YIELDS
Specify steel yields (KSI or MPa) and ultimate strength (KSI or MPa) for flanges, webs, pipe columns, and mill
sections for exterior columns, interior columns, and rafters. Rafter steel yields and ultimate strengths will be used
for overhang and floor beam members. Click OK on this screen as well as on the General Frame, Frame screen
to save the values to the structure.
MEMBER TYPE
Specify the member type for exterior columns, interior columns, and rafters. Detailing/plotting does not support
round pipe and rectangular tube members for sidewall columns, rafters and overhangs. Such frame configurations
can be designed, but no connection design, plotting or costing will be available. Connection design and plotting are
not available for other specific member types and connection types at certain locations. Refer to pages Plotting 8-
8-1 through 8-8-5 in the Plotting Manual for additional information.
Welded Plate (1)
Pipe (2)
Mill (3)
User Defined (9) = generic member type for analysis only; specify section depth and program computes
moment of inertia and cross-sectional area
Rectangular Tube (21)
Connection design and detailing is available for type 2 members only when these members are used as interior
columns with pinned connections.
FRAME LOADS
COLLATERAL DEAD LOAD
Specify any dead loads supported by the frame, such as sprinkler systems, that are not included
in the frame dead load (PSF or KPa).
FRAME DEAD LOAD
Weight of purlins, panel, frame and other permanent dead load (such as permanent built-up roof)
(PSF or KPa).
SPAN SIZES
This grid will only appear if one or more interior columns are specified. The sum of the span sizes must equal the
width of the building. Distance is from sidewall to center of adjacent interior column or distance between interior
columns. Spans are input from left to right (FT or M).
SETUP
The Frame Setup screen for the current building code will be displayed. Values for Seismic and Wind will be
initialized based on the building code setup. Select the Frame you wish to edit and input the desired values. The
following table includes references to the building code publications.
FLOOR BEAMS
FRAME
Choose frame name. Input floor beam data for that frame. Then change to the next frame to input floor beam data
for the next frame. Frames are defined on the General Frame Screen Frame.
NOTE: For symmetrical frames, input will be for left sidewall to peak and will be mirrored for the right sidewall.
SPAN NUMBER
Select the span where the floor beam will be located. If you choose to input a floor beam in a span to the right of
the center of a symmetrical gabled building, you must change the frame type to non-symmetrical gabled on the
General Frame Frame screen.
NUMBER OF MEMBERS
Number of members in the floor beam. Members of floor beams are input from left to right.
LEFT CONNECTION
Support condition at the left (initial) end of the floor beam. Valid selections are:
Welded
Pinned
Moment
ELEVATION
Input the distance from the ground to the top extremity of the floor (i.e, top of the floor joist) (FT or M).
MEMBER TYPE
Specify the member type for the floor beam.
Welded Plate (1)
Mill (3)
User Defined (9) = generic member type for analysis only
Rectangular Tube (21)
DEAD
Dead load of the floor applied to the floor beam in PSF or KPa. The dead load of the floor beam itself is estimated
by the program and added to the floor dead load to obtain a total. An example of floor dead load might be concrete
flooring to be installed on top of the floor beams.
LIVE
Amount of floor live load in PSF or KPa.
COLLATERAL DEAD
Amount of collateral dead load to be applied to the floor in PSF or KPa. Examples of floor collateral dead load
might be heating systems or partitions.
JOIST TYPE
Select flush or exterior joists. This determines how floor beam elevation will be calculated.
JOIST DEPTH
Depth of the joist above the floor beam if joist is exterior mounted. For exterior mounted c-section or z-section
joists, use the depth of the section. For open web joists, input the seat depth of the joist (in or mm).
NOTE: The depth of the rectangular tubes must be equal to or greater than the width of the tube.
LENGTH
Member length(s) (FT or M). One member length must be set to zero.
CONNECTION TYPE
Connection type at final end of the member. Valid selections are:
Welded
Pinned
Moment
NUMBER OF SEGMENTS
Number of segments in the member. The program may change flange and web thicknesses at each segment in
the member. Maximum number of segments is 4. For Mill, Pipe or Rectangular Tube, there will be only one
segment. Segment input is not used for generic (type 9) members.
SEGMENT LENGTHS
Length of segments in the member (FT or M). One segment length must be set to zero. Fields for segment
lengths will be added for the number of segments specified.
FLOOR JOISTS
If the joist does not brace the bottom flange, A = Span X (Percentage for Flange Bracing at Column) (see Setting
Purlin Space & Flange Brace Location Parameters in the File Maintenance Manual). If the joist is located within a
distance A of the column, flange brace every 5 to 6 feet (1.5 to 2 meters). Otherwise brace approximately every 10
feet (3 meters).
If the joist does not brace the bottom flange, flange brace approximately every 10 feet (3 meters).
OVERHANG BEAMS
FRAME
Choose frame name. Input overhang beam data for that frame. Then change to the next frame to input overhang
beam data for the next frame. Frames are defined under General Frame Frame.
MEMBER TYPE
Specify the member type for the overhang beam
Welded Plate (1)
Mill (3)
Rectangular Tube (21) – not currently supported by plotting
NOTE: The depth of the rectangular tubes must be equal to or greater than the width of the tube.
INITIAL CONNECTION
Support condition at the (initial) end of the overhang beam.
Welded
Moment, Vertical (flush connection)
Specify flange brace locations by toggling Yes or No for the locations on each roof surface on for each frame. The
right roof input is used only for gabled buildings. If the building type is gabled, symmetrical, you may specify flange
brace locations for one roof surface and click Typical to utilize the same locations on the other roof surface. Note
that the purlin spaces cannot be modified on this screen. Modify the purlin spaces on the Building, Purlin Spaces
screen, as documented in that section of this manual. If you need different flange brace locations on the left and
right surfaces of a gabled frame, input the frame as non-symmetrical. Symmetrical Gabled frames will use the left
roof flange brace locations for frame design.
If the program detects a conflict between a flange brace location and a connection plate, a message will be given
in the building status when plots are generated. If a warning message is displayed, plots can be viewed to find the
conflicting flange brace. At the peak of a gabled building, the program will plot the flange brace attachment
regardless of the conflict. At other connections, the conflicting flange brace attachment will not be plotted. If an
error message is displayed, no plots will be available. In the case of either a warning or an error, review input for
frame geometry in relation to purlin spaces. Adjust the frame geometry, purlin spaces or purlin flange brace
locations to resolve the conflict and rerun the building.
FRAME
Choose frame name. Input left exterior column data for that frame. Then change to the next frame to input left
exterior column for the next frame. Frames are defined on the General Frame Screen Frame.
NUMBER OF MEMBERS
Number of members in the left exterior column.
BASE SUPPORT
Support condition at the base of the column
Pinned
Fixed
Roller - support is on roller and can move left to right – not currently supported by connection design and
plotting
ELEVATION
Input the base elevation (FT or M). This number may be positive or negative.
NOTE: The depth of the rectangular tubes must be equal to or greater than the width of the tube.
LENGTH
Member length(s) (FT or M). One member length must be set to zero.
CONNECTION TYPE
Connection type at final end of the member or at top of column.
Welded
Pinned
Moment, Vertical
Moment, Perpendicular
Moment, Horizontal
NUMBER OF SEGMENTS
Number of segments in the member. The program may change flange and web thicknesses at each segment in
the member. Maximum number of segments is 4. For Mill, Pipe, or Rectangular Tube, there will be only one
segment.
SEGMENT LENGTHS
Length of segments in the member (FT or M). One segment length must be set to zero. Fields for segment
lengths will be added for the number of segments specified.
BASE ELEVATION
Input the base elevation (FT or M). This number may be positive or negative.
TOP ELEVATION
Location of top connection. Choices are Rafter or the elevation of a floor level for that span (FT or M).
NOTES: For interior columns, the program does not detail moment connections.
For this release, the frame will initialize as if the interior column extends to the rafter. Review and adjust
member depths accordingly.
When floor beams are input, interior columns will be automatically split into design members and recombined into
detail members (as input) for plotting.
NOTE: The depth of the rectangular tubes must be equal to or greater than the width of the tube.
LENGTH
Member length(s) (FT or M). One member length must be set to zero.
CONNECTION TYPE
Connection type at the final end of the member.
Welded
Moment, Vertical
Moment, Perpendicular
NUMBER OF SEGMENTS
Number of segments in the member. The program may change flange and web thicknesses at each segment in
the member. Maximum number of segments is 4. For Mill, Pipe or Rectangular Tube, there will be only one
segment.
SEGMENT LENGTHS
Length of segments in the member (FT or M). One segment length must be set to zero. Fields for segment
lengths will be added for the number of segments specified.
the next interior rafter by clicking on the right arrow of the top scroll bar indicator. Input in order from left to right
across the building. All rafters must be the same member type.
NOTE: If selecting rectangular tubes, the orientation is controlled by the left exterior rafter.
For mono-slopes with interior columns, the peak will fall at an interior column closest to the center of the frame.
The location of the peak will be used to divide the roof beam into left and right rafters.
NOTE: Direction of arrows denotes direction of input. Direction of output is reported in the Frame Geometry report.
OUTPUT REPORTS
Output can be selected from the Reports menu or by clicking on the icon. The reports will be overwritten by
the next run of a building or combined buildings. When you have chosen a report, a print preview will appear. To
print the report in compressed print, change to a small font size. You may also want to change from portrait to
landscape (by selecting Printer Setup from the File menu). See the Printer Setup section of this manual.
The following reports require small size fonts or Landscape printer setup: Frame Geometry, General Geometry,
Purlin Design, Eave Strut Design, LSW (Left Sidewall) Girt Design, RSW (Right Sidewall) Girt Design, FEW (Front
Endwall) Girt Design, BEW (Back Endwall) Girt Design and Section Sizes report. The Print All option will
automatically reduce the font size for these reports.
The Quote Confirmation, Management, Sales, Shipper and Coil reports are available in Windows format. To print
these reports, click on the print icon at the top of the report.
Launching the Quote Confirmation report will bring up the window below. The screen will be populated with the
last building run, the Price, and Weight of the building. If you would like for the price and/or weight to show
differently on the report, input the changes in this screen. If there are multiple buildings in the structure, the
information for the last building run will populate the Quote Confirmation report window.
Selecting Frame Design will bring up the window below. Select the frame and click on OK to view the report for
that frame. If multiple frames are present on the building, they will be listed. If you have a combined building,
structure frames will be listed. If you want to report critical loads only for the Frame Design report, check the
appropriate box. Click Generate All and View Selected to generate reports for all frames in the building and open
the report for the selected frame. This option is available only on buildings having more than one frame. After
exiting from a report, the program will return you to this screen. Select another frame report to view or click on
Cancel to close.
The Frame Summary report works in a similar manner (except that the Critical Loads Only choice does not apply).
When multiple frames and/or structure frames have been designed, selecting Frame Geometry or Connection
Design report will bring up a screen on which you select the frame from the list and click on OK to view the report
for that frame. After exiting from a report, the program will return you to this screen. Select another frame report to
view or click on Cancel to close. If there is only one frame in the building, the Frame Geometry report or the
Connection Design report with open directly.
Launching the Girt Design reports, Section Sizes report, or General Geometry report will bring up the window
below if there is more than one building in the structure and they are connected. Select the building and click OK
to view the report for that building. After exiting from the report, the program will return you to this screen. Select
another building report to view or click Cancel to close. If there is only one building in the structure, the report will
run and the window below will not be seen.
Launching the Purlin Design report will bring up the window below. Select the building and building surface.
Building surface includes the roof and any sidewall overhangs, identified by the overhang ID number. Click OK to
view the report for that building surface.
Regions for the eave strut as well as the roof purlins and struts are reported on the design reports and the roof
framing plan. Region 1 is always the left eave strut and region 2 is always the right eave strut (not used on lean-to
buildings). Roof purlin and strut regions start with region 3 at the left side.
The roof framing plan also reports the associated condition designation (purlin/strut connection) for each location,
unless the user has specified that these are to be omitted (see the Purlin and Strut Design Options section of the
File Maintenance Manual).
EDITING REPORTS
To edit the reports listed below, open any editor that will work with ASCII files. Alternately, you may use WordPad
or another word processor to edit the reports. See your Windows manual for more information on these programs.
The file names for the reports that can be selected from the Reports Output menu are listed below. The
Management, Sales and Shipper reports chosen from the menu can be edited by using the Post Editor. The
Quote Confirmation report is NOT automatically updated when changes are made in Post Editor.
When choosing the option option Design the Building Shell and All Frames or Design the Building Shell Only (No
Frames), the Management, Sales, and Shipper reports are output in text format for editing purposes.
Management, Sales, Shipper and Vendor PDF Reports will be combined for connected building runs.
For the following reports, YYY is the purlin line, ZZ is the region number, and XX is the building number.
General Geometry INPUT.XX
Purlin Design PSTYYYZZ.XX – Strut Purlin
PTPYYYZZ.XX – Typical Purlin
Eave Strut ESTRGZZ.XX
Struts STYYYRZZ.XX
FEW (Front Endwall) Girt Design FGIRT.XX
BEW (Back Endwall) Girt Design BGIRT.XX
LSW (Left Sidewall) Girt Design LSGIRT.XX
RSW (Right Sidewall) Girt Design RSGIRT.XX
Roof and Sidewall Diagonal Bracing DIAGBRAC.XX
Endwall Diagonal Bracing EWDIABRC.XX
Copyright 1992 Melvin R. Loseke effective Version 8.8.76
All Rights Reserved
Loseke Technologies, Inc. Output… 4
Building Systems Software
In addition, the following extended design reports are generated and can be printed or viewed with any editor that
will work with ASCII files. Use small font or Landscape printer setup to print these reports.
The following report is generated in the working directory and can be viewed or printed with any editor that will
work with CSV (comma separated values) files, such as Excel.
Special Punching Diagram SPD.CSV
IMPERIAL METRIC
FT M
IN MM
2 2 3
IN MM divided by one thousand (10 )
3 3 3
IN MM divided by one thousand (10 )
4 4 6
IN MM divided by one million (10 )
6 6 8
IN MM divided by one hundred million (10 )
PSF KPa
MPH KPH
KIPS KN
K-FT KN-M
K/FT KN/M
LB KG
LB/FT KG/M
2 2
LBS/100 FT KG/100 M
2 2
LBS/1000 FT KG /1000 M
To change the order of the report sections on the costing reports (Management, Sales and Shipper) choose from
the File menu Setup Files Setup Report Section Editor. The following screen will appear.
Click on a section and then use the Up and Down buttons to move each section of the report higher or lower in
the order of the sections. When finished, click on Exit. The Management, Sales and Shipper reports generated
from the Reports, Output menu and the Post Editor program will be in the order specified here. The building must
be run again to reflect the report order changes.
Creating custom report sections allows specific parts to be placed in the inventory in a custom section on the
report. The following screen will appear when selecting the Custom Sections button.
To create a new report section, select the New button. Enter a New Section Title then press the OK button. Click
Close and the new report section will show in the Report Section Editor list.
To edit the report section, select the Edit button. Edit the title, then press the OK button.
To delete a section, select a Custom Section from the list and press the Delete button.
NOTE: The removed section may still be referenced by inventory items in the deleted section. This will cause
the inventory items to appear in the <error 01> section of the (Management, Sales, and Shipper) report.
Specify which inventory items are to be placed in the custom report section. The inventory editor for Mill
Shapes, C-Sections, Z-Sections, Clips, Hardware, Insulation, Trim, and Panel contains a Report Section field.
The value of 0 indicates the default section of the report setup by Loseke Technologies, Inc.
Select a value in the Report Section column and press any key except for the <ENTER> key. The following
dialog box will be displayed.
Choose the desired Report Section for the selected inventory item.
To change all values in an inventory file, select a cell in the Report Section column, right click and enter the
desired value.
NOTE: Before deleting a Report Section, remove all references to it in the various inventories. Then select the
section from the Custom Report Sections screen and click <Delete>.
If the Custom Logo choice is checked on Program Setup, Reports, you have the ability to create custom logos for
the Cover Page, Quote Confirmation, and Bill of Materials (Management, Shipper, Sales) Reports.
Below are the required file names, required size, and file type for each custom logo:
Report Bitmap File Name Bitmap Width (pixels) Bitmap Height (pixels) File Type
Quote Confirmation QCR.BMP 380 pixels 190 pixels Bitmap (BMP)
Bill of Material * BMR.BMP 350 pixels 350 pixels Bitmap (BMP)
Cover Page ** CVR.BMP 200 pixels 400 pixels Bitmap (BMP)
Report Editor
The Report Editor will be used for viewing and printing non-Windows reports if this editor (TextEdit.EXE) is
specified in Program Setup. See the Program Setup section of this manual. When selecting options within the
various menus, you may use the tab key to move from one button or box to the next.
Viewing a File
Once you have successfully opened a file, you will see the main screen. There are four menu options: File, Edit,
View, and Help. There are several taskbar buttons underneath as well. On the bottom is a status bar, and to the
right is a scroll bar for quickly viewing the document. In the upper right corner are the Minimize, Maximize, and
Close buttons.
File Menu
You can access the File menu in one of two ways: Click on File in the menu or press Alt-F (hold down the Alt key
while pressing the F key)
Close: This will close the view, without saving any changes. Once a report is closed a new report can only be
opened by exiting and reentering Report Editor. Select this option by pressing Alt-F then C. Or click on the
icon from the toolbar.
Save: To save your document, press Alt-F then S or press Ctrl-S from the Main Screen. Or select the icon on
the toolbar.
Save As: To save your report under a new name, click this option under the File menu or press Alt-F then A.
Type the new file name in the File Name field and click Save (or press Alt-S). If you do not wish to save your file
at this time, click Cancel.
Page Setup: This option provides various viewing options such as font size, portrait/landscape layout, and page
breaks. Click on this option under the File Menu or press Alt-F then U.
Choose which report you wish to change. Click on the arrow to bring up a list of available reports. Click on the
desired report. Use the scroll bar for more options. Select portrait or landscape page orientation. Change the size
of the letters by modifying Font Size.
The report editor will insert page breaks in long reports. You may set a page break at any point in the report by
cutting and pasting the ************ page break ************ line. If the option is not selected, no page breaks will
be inserted, and none will be available to cut and paste.
The buttons on the bottom are used to save the options. If you have only changed options for one report, click on
Save Current (Alt-S). This will save the options for the current report. If you have made changes to multiple
report options, click on Save All (Alt-A). If you do not wish to save any changes click Cancel. To see the
changes in the current report you must exit Report Editor and re-enter.
Print: To obtain a hard copy of the report, click on Print in the File Menu or by press Alt-F then P, or Shift-P from
the Main Screen. Or click on the icon from the toolbar.
The first field on the screen is used to select your printer. Click on the arrow and then click on the desired printer.
The Print range box defaults to All (print the entire document) unless text is selected on the Main Screen,
causing it to default to Selection. Specify the number of copies in the Number of copies field. Press Print to
print, or Cancel to cancel. The portrait/landscape setting you specified under Page Setup will be used.
Edit Menu
The Edit Menu, like the File Menu, can be accessed either by clicking on it in the menu bar, or by pressing Alt-E.
The options on this menu are: Undo, Cut, Copy, and Paste.
Undo: Undoes the last change you made to the document. It can be chosen by one of three ways:
1. Click on it in the Edit menu.
2. Pressing Alt-E, then U.
3. Pressing Ctrl-Z from the Main Screen.
To undo an Undo you can select Undo again.
Cut, Copy and Paste are used to manipulate large portions of the document. First select a portion of text:
1. Click at the beginning of the text, and, holding down the left mouse button drag until you reach the end
of the desired text OR
2. Click (or use the arrow keys) to the beginning of the text and press and hold down the Shift key while
using the arrow keys to place the cursor at the end of the desired text.
If you did not select what you wished, click on the beginning of the desired text and try again. The original
selected text will be unselected.
Once your text has been selected you may either Cut it to the Clipboard, or Copy it to the Clipboard.
To Cut it, use one of the following:
1. Click on it in the Edit Menu
2. Press Alt-E then T.
3. Press Ctrl-X.
4. Choose the icon from the toolbar.
Copy is used in the same way. It does not remove text from the document; it places a copy of the text on the
Clipboard. It is selected by one of the following methods:
1. From the Edit Menu.
2. Alt-E then C.
3. Ctrl-C.
4. Choose the icon from the toolbar.
Paste is used to move the text from the Clipboard to the document. Choose it by one of these methods:
1. From the Edit menu
2. Alt-E then P.
3. Ctrl-V
4. Choose the icon from the toolbar.
View Menu
The View Menu may be selected by clicking on it in the Main Menu or by pressing Alt-V. It has two options:
Toolbar and Status Bar. Both of these are used to toggle the Toolbar or Status Bar on and off.
Help Menu
The Help Menu may be chosen by either clicking on it or by pressing Alt-H. It has one option, About Report
Editor, which in turn has two options, OK and System Info. If you choose OK you will be returned to the Main
Screen. System Info can be used by those with Microsoft Office®. For more information on Microsoft Office®
System Info, please refer to the documentation for that application.
Viewable Documents
This editor does not allow the user to change font styles. By default it attempts to use a Courier style. If, however,
no courier style can be found, the user is prompted to choose a font based on a list of fonts offered.
Post Editor
This program provides the capability to handle unusual building features by modifying the items in the bill of
material reports including Management, Shipper and Sales. You may add or deduct items or groups of items (part
groups). You may also use this program to create component orders.
If you use the Post Editor to modify items which are part marked, the shipper report and plots will not reflect these
modifications.
Menu Choices
The Edit menu allows you to create or edit Part Groups by selecting Part Groups.
The Reports menu allows you to view/print the part groups which have been defined using the Post Editor and
those which have been applied to the most recently run building.
General Input
To display the contents of the current bill of materials reports, click on the check box next to Show All Building
Parts. This check box will not be available if you have not run the building. Specify if you want the parts and / or
Part Group to be applied to the structure, a building in the structure, or to all buildings by selecting the appropriate
choice from the drop-down list. If you select all buildings, the program will give a combined costing report when the
appropriate button is selected.
To create a component order, do not select Show All Building Parts. Under Building Name, choose Apply to
Structure. Add the desired items for the order and then click on a report to view or print.
Buttons
Note: Modified reports for a building will also be available through the Reports, Output menu.
Copyright 1992 Melvin R. Loseke effective Version 8.8.75
All Rights Reserved
Loseke Technologies, Inc. Post Editor... 2
Building Systems Software
The Edit Part Groups screen allows you to add and edit Part Groups. From the Post Editor screen, select Edit,
Part Groups. To exit this screen, click Done.
To create a Part Group, click New. A Part Group named New Part Group will be created. The name of the Part
Group will be highlighted to allow you to type in the name of your choosing. It is recommended that you give the
Part Group a descriptive name to assist you in selecting it for application to a building. Assign a unique number
that is at least 9100 and no more than 9999 to the part group. Click <OK> after typing your desired Part Group
name and number.
Add parts to a Part Group by the following steps:
• Double click on the desired inventory type from the list on the left side of the screen
• Select the desired part from the inventory and drag it to the highlighted Part Group on the right side of the
screen
• Drop the part into the Part Group to bring up the Part Properties screen
• Enter your specifications on the Part Properties screen
• Click OK
The Part Properties input includes an option to Adjust length to Part Group Length. If you check that option, the
value input to Length on the Part Properties screen will be not be used for the current item. If you do not check
that option, the Length you input on the Part Properties screen will be used for the current item.
The Part Properties screen also includes the option to Increment [ ] Number of Times at Intervals of [ ]. This
option is valid only for variable length parts such as coldform sections and panel. If you specify a length of 12 feet,
and increment number of 5 and a length of 1, the Part Group will contain parts of 12, 13, 14, 15 and 16 feet.
The program will not allow specification of data which is not relevant to the part type. For example, inputting a
length for a discrete piece (such as a fastener) is not allowed. If the part is inventoried in specific lengths (such as
corner trim), a list of available lengths will be shown and you can select from the list.
Single click on the name of the Part Group to expand (display contents) or collapse (display only Part Group
name).
To copy a Part Group, select the Part Group from the list and click Copy. A Part Group named New Part Group will
be created. The name of the Part Group will be highlighted to allow you to type in the name of your choosing. The
next available part group number will be assigned, but you can change it to a unique part group number of your
choosing, between 9100 and 9999. The parts in the new Part Group exactly match those of the copied Part Group.
Click <OK> to save the new Part Group. Or click <Cancel> to quit without saving.
To change the name and/or number of an existing Part Group, double click on the part group name. Make the
desired changes and click <OK>. Type the desired name and press <Enter>.
To edit the contents and specifications for parts within an existing Part Group, select the Part Group name by
double clicking on it. This will invoke a list of items in the Part Group, with the associated quantities, lengths and
finishes. Select the item you wish to modify and click Edit. This will invoke the Part Properties input screen. See
the above section on Creating a Part Group for detailed information on this screen.
To delete an item from the part group, click on the item and then click the Delete Button.
NOTE: IF A PART GROUP HAS BEEN APPLIED TO A BUILDING OR STRUCTURE, EDITING THE PART
GROUP WILL NOT IMPACT THE ITEMS ALREADY APPLIED TO THE BUILDING OR STRUCTURE.
Select Part Groups from the list of Inventory Parts. A list of available Part Groups will be displayed. Select the
desired Part Group. Apply the Part Group by using the Apply Parts Button or by dragging the Part Group to the
right side of the screen (in the area under Applied Parts). This will invoke the Part Properties screen. Under
Quantity, specify the quantity of this Part Group to apply. Under Length, specify the length to be used when
applying the Part Group. Note that the Part Group length will be used only for parts in the Part Group with variable
lengths which have been specified as Adjust length to Part Group Length. Select a Surface on which to apply the
Part Group. If desired, input the Increment [ ] Number of Times at Intervals of [ ] information. See the section on
Creating Part Groups for information about the usage of Length and Increment for items within the Part Group.
Select the desired inventory category from the list of Inventory Parts. The contents of your inventory will be
displayed. Select the item you wish to apply. Apply the item by using the Apply Parts Button or by dragging the
item to the right side of the screen (in the area under Applied Parts). This will invoke the Part Properties screen.
Select a Surface on which to apply the part. See the section on Creating Part Groups for information about the
usage of Length and Increment for items within the Part Group.
Select the Non-Inventory Items from the list of Inventory Parts. Apply a non-inventory item by clicking on the Apply
Parts Button. This will invoke the Update Non-Inventory Item screen. Input the quantity and description (maximum
8 characters). For the weight, select an indicator and input the weight in lbs./indicator. Input the length of one item.
For the labor and material prices, select an indicator and input the price in dollars/indicator. In the quantity field
either a quantity or an area may be input. Each of the indicators must remain consistent with the unit input in the
quantity field. The table below shows various results for weights and quantities using various indicator options.
Parallel computations apply to price indicatory calculations. Choose Save to save changes and apply the item.
Choose Cancel to return to Post Editor without saving or applying the item.
The Bill of Material and/or the relevant Part Groups and Applied Parts will be displayed. Click on the + sign to the
left of the item you wish to modify. The + sign will change to a - sign and a list of parts within that item will be
displayed. Highlight the item you wish to modify and click on Edit. This will invoke the Part Properties input or
Update Non-inventory Item screen. See the section on Creating Part Groups for information about Part Properties
input or the section on Applying Non-Inventory Items for information about that screen input. Highlight an item and
click on Delete to remove the entry.
The Defined Part Groups report lists all the defined part groups sorted by part group number. The contents of
each part group is sorted by part number.
The Applied Part Groups report lists all part groups applied to the building(s). It is generated each time a building
is run. This report can also be viewed by selecting Reports Output Applied Part Groups, from the
PrecisionPlus menu.
ICONS
Generate Drawings Generate and view the plots from the last run
Structure Setup Set the Defaults for the Current Structure (Building Code, Pricing and
Customer Information
Connect Buildings Define the Locations of the Buildings Relative to Each Other
Purlin/Girt Support Define the Purlin/Girt Support Conditions for the Current Building
Conditions
Roof and Sidewall Define the Roof and Sidewall Lateral Bracing for the Current Building
Lateral Bracing
Endwall Girt Lateral Define the Endwall Girt Lateral Bracing for the Current Building
Bracing
Wind Bracing Define the Wind Bracing Data for the Current Building
Trim and Ridge Define the Trim and Ridge Condition for the Current Building
Condition
Girt Locations Define the Girt Locations for the Current Building
Purlin Spaces Define the Purlin Spaces for the Current Building
Load Combinations Define the Load Combinations for the Current Building
Frame Member and Display the Frame Member and Joint Locations
Joint Locations
Floor Joists Input for floor joists. This screen cannot be accessed until a floor
beam has been defined
Purlin Flange Brace Define the Purlin Flange Locations for the Current Building
Locations
Building Setup Define building code related data for the Current Building
Frame Setup Define building code related data for the Mainframe(s) in the Current
Building
Endwall Diagonal Define the Endwall Diagonal Bracing Data for the Current Building
Bracing
Liner Panels Input Liner Panel locations and elevations for the Current Building