DL ≔ 4 kip

LL ≔ 1 kip
fc' ≔ 3000 psi cover ≔ 3 in db ≔ 0.5 in b ≔ 48 in

fy ≔ 60000 psi

γconcrete ≔ 150 pcf

γsoil ≔ 120 pcf

tf ≔ 24 in

tfoundation ≔ 24 in

tsoil ≔ 24 in

qa ≔ 2 ksf

qn ≔ qa - ⎛⎝tfoundation ⋅ γconcrete⎞⎠ - ⎛⎝tsoil ⋅ γsoil⎞⎠ = 1.46 ksf

(DL + LL)
Arequired ≔ ―――― = 3.425 ft 2 ACI 318-14(13.3.1.1)
qn
Afooting ≔ 4 ft 2

Factored Net Pressure:

(1.2 ⋅ DL + 1.6 ⋅ LL)


qnu ≔ ―――――― = 1.6 ksf
Afooting
Signature Homes

Shear Capacity check:

ϕ ≔ 0.75 ACI 318-14 (Table 21.2.1)

λ ≔ 1.0 bw ≔ 12 in
db
d ≔ tf - cover - ―= 20.75 in
2

⎛⎝b - tf⎞⎠ ⋅ 1 ft
Atributary ≔ ――――= 1 ft 2
2

Vu ≔ qnu ⋅ Atributary = 1.6 kip

‾‾‾‾‾
⎛ fc' ⎞
ϕVc ≔ ϕ ⋅ 2 ⋅ λ ⋅ ⎜―― ⎟ ⋅ psi ⋅ bw ⋅ d = 20.457 kip ACI 318-14 (Table 22.5.5.1)
⎝ psi ⎠
Vu< ϕVc OK

Flexural Reinforcement Design