15.4 Two interior columns for a high-rise concrete structure are spaced 15 ft apart,
and each carries service loads D= 500 kips and L= 514 kips. The columns are to
be 22 in. square in cross section, and will each be reinforced with 12 No. 11 (No.
36) bars centered 3 in. from the column faces, with an equal number of bars at each
face. For the columns, f c =4000 psi and f y = 60,000 psi. The columns will be
supported on a rectangular combined footing with a long side dimension twice that
of the short side. The allowable soil bearing pressure is 8000 psf. The bottom of the
footing will be 6 ft below grade. Design the footing for these columns, using f c
=3000psi and fy=60,000 psi. Specify all reinforcement, including length and
placement of footing bars and dowel steel.
lbf lbf
Nota. Se supone un peso unitaxrio γ ≔ 125 ―― qadm ≔ 8000 ――
promedio de 125 lb/pie3, ya que la ft 3 ft 2
superficie del terreno esta ocupado por bc ≔ 22 in PL ≔ 514 kip
concreto y relleno, tal valor es
hc ≔ 22 in PD ≔ 500 kip
recomendado en el libro.
Lc ≔ 15 ft
Df ≔ 6 ft
kip
qneto ≔ qadm - γ ⋅ Df = 7.25 ――
ft 2
Columnas A y B
B ≔ 12 ft
B = ⎛⎝3.658 ⋅ 10 3 ⎞⎠ mm
L ≔ 2 ⋅ B = 24 ft
Centralizacion de carga
Valores de prueba
x ≔ 1 ft
Restricciones
Diseño de zapata.
Mayoracion de cargas
Diagrama de
momento y cortante.
Cortante 1d
Cortante 1d
9
Suponiendo una altura de hz ≔ 1300 mm db ≔ ―in
800mm fc ≔ 3000 psi 8
fc = 20.684 MPa
d ≔ hz - 75 mm - 1.5 ⋅ db = ⎛⎝1.182 ⋅ 10 3 ⎞⎠ mm
d = 46.541 in
ϕ ≔ 0.75
⎛ kip ⎞
Vud ≔ -781 kip + ⎜d ⋅ 118.6 ―― ⎟ = -321.021 kip
⎝ ft ⎠
2
ϕVc ≔ ϕ ⋅ 0.17 ⋅ ‾‾‾‾‾‾‾
fc ⋅ MPa ⋅ B ⋅ d = 2507.232 kN
Cortante en 2d (Punzonamineto) 2
Apunz ≔ ((d + hc)) = 32.624 ft 2
Columna A y B
Pu ⋅ 2 kip
qu ≔ ――= 9.878 ――
B⋅L ft 2
hc
β ≔ ―= 1 αs ≔ 40 bo ≔ 4 ⋅ ((39.74 in )) = 13.247 ft
bc
⎛ 2 ⎞ ‾‾‾‾‾‾‾
ϕVc1 ≔ 0.75 ⋅ 0.17 ⋅ ⎜1 + ― ⎟ ⋅ fc ⋅ MPa ⋅ bo ⋅ d = 1866.615 kip
⎝ β⎠
⎛ αs ⋅ d ⎞
ϕVc2 ≔ 0.75 ⋅ 0.083 ⋅ ⎜―― ⎟ ⋅ ‾‾‾‾‾‾‾
fc ⋅ MPa ⋅ bo ⋅ d = 3557.698 kip
⎝ bo ⎠
⎛ ⎛ 21 - 28 ⎞⎞
β1 ≔ 0.85 - ⎜0.05 ⋅ ⎜――― ⎟⎟ = 0.9
⎝ ⎝ 7 ⎠⎠
Momento positivo
c ≔ 1 in
SolverRestricciones
⎛ β⋅c⎞
Mn = 0.85 ⋅ fc ⋅ β ⋅ c ⋅ B ⋅ ⎜d - ―― ⎟
⎝ 2 ⎠
c = 0.597 in
((0.85 ⋅ fc ⋅ β ⋅ c ⋅ B))
As ≔ ―――――― = 3.652 in 2
fy
Ag ≔ B ⋅ L
As
ρ ≔ ― = 8.807 ⋅ 10 -5
Ag
π
Ab ≔ ―db 2
4
⎛ As ⎞
nbarras ≔ Ceil ⎜― , 1⎟ = 4
⎝ Ab ⎠
⎛ As ⎞
nbarras ≔ Ceil ⎜― , 1⎟ = 4
⎝ Ab ⎠
B - 2 ⋅ 75 mm - 12 db
Sb ≔ ―――――――= ⎛⎝1.055 ⋅ 10 3 ⎞⎠ mm Cumple separacion minima
nbarras - 1 de 25 mm
Momento positivo
c ≔ 1 in
SolverRestricciones
⎛ β⋅c⎞
Mn = 0.85 ⋅ fc ⋅ β ⋅ c ⋅ B ⋅ ⎜d - ―― ⎟
⎝ 2 ⎠
c = 0.597 in
((0.85 ⋅ fc ⋅ β ⋅ c ⋅ B))
As ≔ ―――――― = 3.652 in 2 Verificacion acero minimo
fy
Ag ≔ B ⋅ L ASmin ≔ 0.0018 ⋅ B ⋅ d = 12.063 in 2
As ≔ ASmin
As
ρ ≔ ― = 2.909 ⋅ 10 -4
Ag
π
Ab ≔ ―db 2 = 0.994 in 2
4
⎛ As ⎞
nbarras ≔ Ceil ⎜― , 1⎟ = 13
⎝ Ab ⎠
B - 2 ⋅ 75 mm - 12 db
Sb ≔ ―――――――= 263.725 mm Cumple separacion minima
nbarras - 1 de 25 mm
Momento negativo
Momento negativo
ϕ ≔ 0.9
MMaxpos
Mn ≔ ―――= ⎛⎝2.378 ⋅ 10 3 ⎞⎠ kip ⋅ ft
ϕ
Valores de prueba
c ≔ 1 in
SolverRestricciones
⎛ β⋅c⎞
Mn = 0.85 ⋅ fc ⋅ β ⋅ c ⋅ B ⋅ ⎜d - ―― ⎟
⎝ 2 ⎠
c = 1.701 in
((0.85 ⋅ fc ⋅ β ⋅ c ⋅ B))
As ≔ ―――――― = 10.408 in 2
fy
Ag ≔ B ⋅ L
As
ρ ≔ ― = 2.51 ⋅ 10 -4
Ag
As ≔ ASmin
π
Ab ≔ ―db 2
4
⎛ As ⎞
nbarras ≔ Ceil ⎜― , 1⎟ = 13
⎝ Ab ⎠
B - 2 ⋅ 75 mm - 12 db
Sb ≔ ―――――――= 263.725 mm Cumple separacion minima
nbarras - 1 de 25 mm
B ≔ hc + d = 68.541 in
Momento positivo
c ≔ 1 in
⎛ β⋅c⎞
Mn = 0.85 ⋅ fc ⋅ β ⋅ c ⋅ B ⋅ ⎜d - ―― ⎟
⎝ 2 ⎠ ASmin ≔ 0.0018 ⋅ B ⋅ d = 5.742 in 2
c = 1.263 in
((0.85 ⋅ fc ⋅ β ⋅ c ⋅ B))
As ≔ ―――――― = 3.679 in 2
fy
Ag ≔ B ⋅ L
As
ρ ≔ ― = 1.864 ⋅ 10 -4
Ag
π
Ab ≔ ―db 2
4
As ≔ ASmin
⎛ As ⎞
nbarras ≔ Ceil ⎜― , 1⎟ = 6
⎝ Ab ⎠
B - 2 ⋅ 75 mm - 12 db
Sb ≔ ―――――――= 249.608 mm Cumple separacion minima
nbarras - 1 de 25 mm
Momento negativo
c ≔ 1 in
SolverRestricciones
⎛ β⋅c⎞
Mn = 0.85 ⋅ fc ⋅ β ⋅ c ⋅ L ⋅ ⎜d - ―― ⎟
⎝ 2 ⎠
c = 0.842 in
((0.85 ⋅ fc ⋅ β ⋅ c ⋅ B))
As ≔ ―――――― = 2.454 in 2
fy
Ag ≔ B ⋅ L
As ≔ ASmin
As
ρ ≔ ― = 2.909 ⋅ 10 -4
Ag
π
Ab ≔ ―db 2
4
⎛ As ⎞
nbarras ≔ Ceil ⎜― , 1⎟ = 6
⎝ Ab ⎠
B - 2 ⋅ 75 mm - 12 db
Sb ≔ ―――――――= 249.608 mm Cumple separacion minima
nbarras - 1 de 25 mm
lbf
pd ≔ 135 kip pl ≔ 125 kip qadm ≔ 3000 ―― f'c ≔ 3000 psi
ft 2
lbf
fy ≔ 60000 psi df ≔ 3 ft γs ≔ 125 ―― rec ≔ 3 in
ft 3
bc ≔ 11 in hc ≔ bc = 11 in
Primeramente se usa las cargas de servicio sin mayorar para poder hallar el area, se tomo
el peso unitario del suelo hasta la base de la zapata como de 125.
lbf pl + pd
qe ≔ qadm - ⎛⎝df ⋅ γs⎞⎠ = ⎛⎝2.625 ⋅ 10 3 ⎞⎠ ―― A ≔ ――― = 99.048 ft 2
ft 2 qe
L ≔ ‾‾
A = 9.952 ft B ≔ L = 9.952 ft Se pasan a unidades
constructivas
L ≔ 10 ft
B ≔ L = 10 ft
A ≔ B ⋅ L = 100 ft 2
Se asume un d=25in
d1 ≔ 25 in x ≔ 11 in + 25 in = 3 ft
vu2
d ≔ ―――――――――― = 9.491 in <d=25in OK
⎛ 40 ⋅ d ⎞
‾‾‾‾‾‾
0.75 ⋅ ⎜――+ 2⎟ ⋅ f'c ⋅ psi ⋅ bo
⎝ bo ⎠
L bc
f ≔ ―- ―= 4.542 ft
2 2
⎛f⎞
⎟ = ⎛⎝4.48 ⋅ 10 ⎞⎠ kip ⋅ in
3
Mu ≔ f ⋅ B ⋅ qu ⋅ ⎜―
2
⎝ ⎠
Mu
As ≔ ―――――― = 4.255 in 2
⎛ bc ⎞
0.9 ⋅ fy ⋅ ⎜d1 - ―⎟
⎝ 2⎠
3 ⋅ ‾‾‾‾‾‾
f'c ⋅ psi 200 psi
Asmin1 ≔ ――――⋅ B ⋅ d1 = 8.216 in 2 Asmin2 ≔ ――― ⋅ B ⋅ d1 = 10 in 2
fy fy
Asmin2
#b ≔ ――― = 10 10 barras #9 en cada dirección
1 in 2
B - 2 ⋅ rec - #b ⋅ 1.128 in
s ≔ ――――――――= 11.413 in
#b - 1
Diseño Zapata cuadrada.