Professional Documents
Culture Documents
Abstract
The thermal rating of power transformers has hitherto been based on the average temperature rise of
the windings as determined from the increase in resistance, because that has been the best practical
measurement. Unfortunately, for a given and guaranteed temperature rise by resistance, the hottest-spot
temperature can vary over quite a wide range depending on individual design characteristics. The introduc-
tion of the multiflow principle allows the hottest-spot temperature to be determined from measurements
made during a single temperature-rise test. Using this method, it is suggested that the temperature rise
by resistance should be abandoned as a standard guarantee, and replaced by the hottest-spot temperature,
this being the fundamental basis of the true thermal rating. The designer will then have wider latitude
in choosing his parameters, and freedom to exploit more intensive cooling systems such as increased oil
circulation and directed flow. The resulting reductions in both winding- and oil-heat-exchanger capacities
are substantial. As a broad comparison with existing practice, the principle of multiflow in forced-oil-
cooled transformers permits an increase in the average winding-temperature rise from the present
international guaranteed limit of 65°C to 75°C, or more, without any increase in the hottest-spot
temperature.
List of symbols into the bottom of the transformer tank, and from the top
9C — top-oil-temperature rise in heat exchanger of the tank back to the heat exchanger.
9W = top-oil-temperature rise in windings The hottest-spot temperature is not directly measurable,
9, = top-oil-temperature rise in tank
9mw = mean oil-temperature rise in windings top ec
9mc = mean oil-temperature rise in heat exchanger
9h = bottom-oil-temperature rise in heat exchanger
9r — temperature rise of windings by resistance
9h = hottest-spot-temperature rise in windings
Table 1
30-
TEMPERATURE-RISE TEST ON 1 0 0 M V A FORCED-OIL-COOLED
TRANSFORMER
1Measured values « 2O
a a.
= 42 0 Vmw\ = 40- 5 E
= 38•3 = 45- 3
ob- IO-
From eqn. 9, Oyvl == 42 • 7 and 0H>2 = 52- 3
From eqn. 8, = 39-2 for a = 0-9 and w = 0- 45
o,=
Temperature rises are in degrees Centigrade IO 2O 3O 4O 50 6O
time from shutdown, min
In this particular case, four oil streams are considered: Fig. 3
(i) the upward flow through the high-voltage windings, with Temperature changes after shutdown
a Rise by resistance (measured)
a hottest-oil temperature rise at the top of the winding b Rise by resistance 6mi« corrected for fall in 6,,,c
of42-7degC c Mean oil-temperature rise 8)nc in cooler
1
the intersection with the ordinate, shown in Fig. 4, and the
other is the actual asymptotic value.
iX
This can be determined, after about 15min, as
°mw = "r + Vf
where Qf is the fall in the mean oil temperature 6mc after
shutdown.
Fig. 3 shows that dmw obtained in this way is constant for
an hour or more after shutdown, so that, if any doubt arises,
many readings can be taken.
(7)
w = 05a (8)
0-24 0-61
5 Forced-oil-cooled transformers
The comparatively feeble convective flow in natural Temperature rises are in degrees Centigrade
cooling can be greatly increased by forced-oil circulation,
usually by submerged pumps.8 (Convective circulation can cooling were included, with loads giving oil-temperature rises
then be ignored.) The cooling conditions and the proportion ranging from 18 to 35-4degC. It is seen that w ranged from
w of oil circulation actually flowing through the windings 0-21 to 0-29 for normal flow and from 0-52 to 0-73 for
are now completely determined by the hydraulic circuit, and directed flow.
are thus under the control of the designer. Because w cannot be measured directly, and because it
Since, for a given power dissipation, the rise in temperature • The corresponding IEC symbols are OFAN and OFAF
PROC. /EE, Vol. 116, No. 9, SEPTEMBER 1969 1567
involves a small difference between relatively high tempera- wide range of ratings and voltages. It will be seen later to
tures, it is very sensitive to very small errors in the tem- justify, by itself, a suggested increase of 5degC in the standard
perature measurements. It is suggested, therefore, only as a guarantee of 65degC rise by resistance.
theoretical basis for deriving the temperature relationships, Apart from the benefit of directed flow of circulating more
and is not intended for use in design or test formulas. oil through the windings, reducing Dw and the hottest winding-
If H > > 0 - 5 is considered a practical requirement, i.e. if oil temperature 6W, there is the very important effect of
at least half the circulated oil is being directed through the reducing the winding gradients. These gradients consist of
windings, from eqn. 8, 6mw < 0C. (a) the temperature drop through the conductor insulation
Fig. 7 shows a histogram of heat-run measurements for and (b) the surface drop between the insulation and the oil.
The latter depends on the velocity of the oil flow over the
2O- surface of the insulation, 9 as shown qualitatively in Fig. 8.
By designing the series and parallel flow paths through the
winding to give appropriate velocities of oil flow over the
insulation surfaces, gradient reductions of one-third or more
are practicable. This, in turn, reduces the number of oil
\3 directed flow 110 results
ducts and cooling surfaces necessary for meeting the
U nondirected flow 8 results guaranteed 65degC rise by resistance. It also considerably
reduces the hottest-spot temperature—a reduction which,
though genuine, has been of no technical or commercial
benefit to either manufacturer or user because it has not
hitherto been measurable. The proposals in Section 6 remove
this handicap.
2- (0
= 1-10,.+ O-450C - 0 - 5 5 0 , ,
Fig. 8 (a) 1 -O5(0C — 6b) for forced-oil cooling with normal flow
Surface-temperature gradient in windings (b) O-27(0C — 6b) for forced-oil cooling with directed flow
1568 PROC. IEE, Vol. 116, No. 9, SEPTEMBER 1969
Table 7 Table 8
STAGES OF COOLING RELATIVE COOLING CAPACITY REQUIRED
Temperature rises are in degrees Centigrade to 66%. Stages (ii) and (iii) are not in themselves new (as
the references show), but have been limited in realisation
Taking standard values of (6C —6b from Table 7, these hitherto by the guaranteed rise by resistance of 65degC.
increases become 8-4degC and 1 -08degC, respectively. This can now be raised to 75degC for no increase in the
Jt is important to realise that these higher hottest-spot hottest-spot temperature.
temperatures are not new. They have been there all along but The economic effect may be judged broadly from these
have not been appreciated; the overload tables are therefore figures but will depend on individual circumstances.
not affected.
Instead of reducing the cooling capacity, the power rating
of the transformer could be increased to utilise it. These
7 Practical application and other possibilities have been discussed in Section 7 of
Reference 10, with the important difference that, in this case,
As explained in Section 5, the national standard
specifications for naturally cooled transformers are thermally there is no increase in the hottest-spot temperature, and the
efficient, in that the standard hottest-spot temperatures are transformer is therefore never overloaded.
utilised. This is not so for forced-oil cooling. The whole of this Section must be regarded as a broad
In this Section, an attempt is made to give a broad picture exposition of the versatility of the multiflow principle, and
of the effect of the various degrees of controlled forced-oil the values given in the tables as particular examples among
cooling, including directed flow. a wide range of alternatives at the disposal of the designer.
For this purpose, the IEC recommendations 76 are taken
as a basis, and the following stages of cooling considered: 8 Conclusions
(a) IEC recommendations 76 (a) The present universal standard rating of a trans-
(b) increased oil flow former, based on the temperature rise 6,. of the windings as
(c) directed flow measured by the increase in resistance, is unsatisfactory, since,
id) multiflow thermal rating based on hottest-spot temperature for a given 6n the hottest-spot temperature dh (which is the
fundamental basis of transformer thermal rating) can vary
as in Section 6.
over a range of lOdegC or more, depending on individual
The results are assembled in Table 7. designs.
A value of a = 0-80 is assumed to cover the no-load loss (b) The present position is that the standard rating of a
and stray losses in the tank, core and structural work. The transformer is determined by a single indirect measurement
oil flow in the windings is assumed to be w — 0-24 for normal (the temperature rise by resistance), whereas the national
flow and w = 0-5 for directed flow. overload guides, which deal with more onerous conditions,
The first column of Table 7 gives the IEC basis. The are based more logically on the hottest-spot temperature, even
temperature rise by resistance of 65degC is taken directly though this had to be assumed, and, from conclusion (a),
from the IEC recommendations. Values of 6C = 40 and assumed wrongly in many cases.
Dc — 8 are considered in the draft IEC loading guide as (c) Using the multiflow principle described in the paper, the
representative of standard practice. These values lead, in the hottest-spot temperature can be determined from measure-
orthodox single-flow diagram of Fig. 1, to a hottest-spot ments made in a single temperature-rise test.
temperature of 80-3° C. (d) The temperature rise of the windings by resistance should
In accordance with the principle in this paper that the therefore be abandoned as a standard guarantee, and replaced
thermal rating should be based on the hottest-spot tem- by the hottest-spot temperature.
perature, and not on the rise by resistance, stage id) is calcu- (<?) The designer is then free of the artificial restriction of the
lated assuming the same hottest-spot temperature 6h of rise by resistance and has wider latitude in the design. It is not
8O-3°C, letting the temperature rise by resistance fall where necessary to distinguish between normal and directed flow.
it will. It can never, of course, exceed the hottest-spot (/) The substantial reductions in oil- and winding-cooler
temperature. capacities are shown in Table 8 of Section 7.
The second and third columns of Table 7 show the effect (g) As a broad comparison with existing practice, the principle
of increasing the oil flow through the heat exchanger, so that of multiflow in forced-oil-cooled transformers permits an
the difference Dc between the inlet and outlet temperatures increase in the average winding-temperature rise from the
is reduced from 8 to 4degC. This is quite a practical reduction. present international guaranteed limit of 65degC to 75degC,
Alternative designs are here possible (as are, of course, or more, without any increase in either the hottest-spot
intermediate combinations). In the second column, the cooler temperature or the hottest-oil temperature.
is unchanged, but higher winding gradients are permissible (h) This substantial increase has been released, not created,
and the cooling ducts in and between the windings are by the multiflow principle. The existing standard temperature
correspondingly reduced. In the third column, the winding limits have hitherto prevented its utilisation by both the
gradients are the same, but, in consequence, higher oil tem- manufacturer and the user.
peratures are possible and the heat exchanger is smaller.
The fourth column shows the effect of directed flow, and 9 Acknowledgments
the last column is for the 'multiflow' thermal rating.
In all these alternatives, the hottest-oil temperature is no Thanks are due to Ferranti Ltd. for permission to
greater than that for the standard IEC design. publish the paper.
The practical economic effect can be shown by comparing
the cooling capacity required of what are virtually the heat 10 References
exchangers between the windings and the oil and between the 1 NORRIS, E. T. : 'The thermal rating of transformers', J. IEE, I928,
oil and the surroundings. The former is inversely propor- 66, pp. 841-854
2 BS 171: 1959. 'Power Transformers'
tional to g and the latter to 6mc. Table 8 shows this compari- 3 'Power Transformers', IEC publication 76
son. The full application of multiflow reduces both the 4 Draft IEC loading guide for oil-immersed power transformers,
document 14
required oil-cooling capacity and the winding-cooling capacity 5 TAYLOR, E. D., BERGER, B., and WESTERN, B. E. : 'An experimental
PROC. 1EE, Vol. IH5, No. 9, SEPTEMBER 1969 1569
approach to the cooling of transformer coils by natural convection', (2)
Proc. IEE, 1958, 105 A, pp. 141-152
6 'Rules for transformers and reactors', VDE 0532/8-64, clause 536
7 'Guide to loading of transformers', British standard code of (17)
practice CP 1010: 1959
8 NORRIS, E. T.: 'Safe loading of oil-immersed transformers', Trans: (is)
Amer. Inst. Elect. Engrs., 1929, 48, p. 1206
9 PALUEV, K. K., and BURNHAM, L. H.: 'Cooling power transformers
by forced circulation of the cooling medium', AlEE paper 43-56 (19)
10 NORRIS, E. T.: 'Loading of power transformers', Proc. IEE, 1967,
114, (2), pp. 228-232
(8)
11 Appendix
Multiflow formulas
( 20 )
All winding temperatures must be determined separately
for each winding. From eqns. 2 and 17,
Tank and core Winding I Winding 2 Cooler
(20
= ^> (15)
From eqns. 17 and 18,
D «*<£
w
(16)
w P