Professional Documents
Culture Documents
Power Transformer Cooling System Optimization
Power Transformer Cooling System Optimization
Mean oil
Top oil
Temperature
98 1.00 80 Winding
Oil
100 1.25 75 Load
102 1.58 70
104 2.00
65
106 2.51
60
108 3.17
18 0
19 0
20 0
21 0
22 0
23 0
0: 0
11 0
12 0
13 0
14 0
15 0
16 0
17 0
0
00
00
00
00
00
00
00
00
00
00
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
1:
2:
3:
4:
5:
6:
7:
8:
9:
110 4.00
17
10
% Load
Table 1. Insulation aging rate
Figure 3. Phase S daily thermal characteristic
THERMAL MONITORING ON TRANSFORMER
500/150 KV 500 MVA phase T
95
Temperature
80 Winding
Oil
11 0
12 0
13 0
14 0
15 0
16 0
17 0
0
00
00
00
00
00
00
00
00
00
10 0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
0
1:
2:
3:
4:
5:
6:
7:
8:
9:
17
% Load
Maximum winding temperature is reached 95°C when Figure 4. Phase T daily thermal characteristic
load 90% it’s nominal. High winding and oil
temperature is caused by high cooling system setting. TEST RESULTS
Existing transformer cooling system setting is shown Dissolved Gasses Analysis (DGA)
below:
On Off IBT 2 IBT 2
Gases R S T Gases R S T
Fan 90°C 80°C CO 1289 167 1145 CO 684 69 708
Oil Pump CO2 9395 2709 7563 CO2 7256 2153 6405
95°C 82°C Ratio 7,29 6,61 Ratio 10,61 9,05
IBT 2 IBT 2
Daily load and temperature of transformer is shown Gases R S T Gases R S T
below: CO
CO2
970
10657
126
3623
1102
9579
CO
CO2
385
6732
63
4561
443
5983
Ratio 10,99 8,69 Ratio 17,49 13,51
phase R
Pump ON Pump OFF
IBT 2 IBT 2
100
Gases R S T Gases R S T
95 Fan ON CO 530 104 898 CO 510 88 440
CO2 9336 3267 8603 CO2 3998 2766 3539
90 Ratio 17,61509 9,580178 Ratio 7,84 8,04
85 Table 2. CO & CO2 concentration
Temperature
Winding
80 Oil
Load
75 Based on periodic DGA test results, it is indicated that
70 CO concentration is exceed normal value for
65 transformer phase R and phase T. Ratio CO2 and CO
60 also confirms that cellulose insulation deteriorated much
more due to thermal stress.
11 0
12 0
13 0
14 0
15 0
16 0
17 0
0
18 0
19 0
20 0
21 0
22 0
23 0
0
00
00
00
00
00
00
00
00
00
10 0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
:0
0
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
17
% Load
Figure 2. Phase R daily thermal characteristic On one hand, based on CO concentration of transformer
phase S, we may see that the cellulose insulation has not
deteriorated yet. Hence, fan operation would have
effective enough decreasing temperature.
58
On the other hand, CO concentration of transformer On
phase R and T has indicated cellulose deterioration. On Setting Resetting
phase R, high ratio of CO2 and CO would cause fan Fan 90°C 70°C
operation has not effective yet decreasing temperature. Oil Pump 95°C 80°C
The temperature still increase until reach the pump Table 4. Cooling system resetting
operation setting and then it start to decrease.
Thermal characteristic
Ratio of CO2 and CO on phase T lower than phase R,
100
fan operation would decrease temperature but we may
80
see that the derivation of the temperature is not as good % Beban
60
as phase S. Setting
40 Resetting
Delta
20
Furan Test
0
17
19
21
23
11
13
15
17
Kandungan
NO TRAFO 2 – Furfural (2FAL) Comment
Ppb
Figure 6. Thermal characteristic after resetting
End of expected life
1 IBT 2 R 6477 Estimated percentage of remaining life 6 %
Overheating caused high concentration 2FAL
Normal Ageing rate Based on thermal characteristic on Fig. 6, transformer
2 IBT 2 S <10
Estimated percentage of remaining life 100 %
End of expected life
temperature has decreased in average 20°C.
3 IBT 2 T 5494 Estimated percentage of remaining life 13 %
Overheating caused high concentration 2FAL
Above figure was made from data taken from 2 IBT
Table 3. Furan test – lifetime estimation
works in parallel, so the data compared is in the same
percentage load. 1 IBT still use existing cooling setting
This test is done to obtain the level of cellulose
(setting), while the other used the new one (resetting).
degradation by estimating the lifetime, based on
previous DGA result. It confirm that phase R has the
CONCLUSION
worst cellulose degradation condition. Its estimated life
time only 6% means that the cellulose would be more
High temperature operation would accelerate
susceptible to mechanical and electrical force, much
transformer aging rate, since it would deteriorate the
more
cellulose condition.
9000 120
The transformer is designed for 30 years normal
8000
100 operation. In normal aging rate, this transformer should
7000
have calculated percentage of remaining life about 53%
6000 80
in 2008. Estimated percentage of remaining life
2F A P (p p b )
Phase S 60 Phase S
4000 Phase T Phase T
3000 40
2000
Resetting the transformer cooling system would
1000
20 minimize thermal stress. Hence, it is expected to
0 0
prolong the transformer lifetime.
Oct-07 Dec-07 Feb-08 Oct-07 Dec-07 Feb-08
Periodic test results shows only phase R and phase T [1] S.D.Myers, “A Guide to Transformer Maintenance”,
indicates cellulose deteriorated, by increment of 2FAL 1981.
concentration. Hence, the estimated percentage of [2] Dugan, Roger C, “Electrical Power Systems
remaining life would decrease as shown on Fig. 5. Quality“, Second Edition, McGraw-Hill, 2002.
[3] CIGRÉ working group WG a2.18, “Life
TRANSFORMER OPERATION CONSIDERATION Management techniques for transformer”, January
2003.
PLN’s management policy state that the transformer [4] IEC 60599, “Mineral oil-impregnated electrical
should still operates because of the load demand and equipment in service - Guide to the interpretation of
since we don’t have any suitable spare. Hence, PLN dissolved and free gases analysis”, 1999.
decide to operate this transformer by reducing thermal [5] IEC 60354, “Loading guide for oil-immersed power
stress. We hope it can prolong the transformer life time. transformer”, 1991.
To implement it, we decide to optimize the transformer
external cooling system by resetting it.
59