Engineer: Eduhar vasquez
Elevation: (ft) 43
Date: 9/21/2022
Submitted By: Eduhar Vasquez
PRIMELINES PERU
CALLE HUAMAMPONA DE AYALA 345
LIMA, 06 15086
PE
Phone: 3058887310
Fax:
Email Address: eduhar@primelines-hvac.com

P.O. Box 410 Schofield, WI 54476 (715) 359-6171 FAX (715) 355-2399 www.greenheck.com

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.1057 Generated by: eduhar@primelines-hvac.com Page 1 of 7
Printed Date: 09/21/2022
Job: SHOPPING LA MOLINA, 240822
Mark: DFD-150
Model: DFD-150

DFD-150 DFD-150: 1 1/2 hour dynamic rated fire damper


APPLICATION & DESIGN
Model DFD-150 is approved for use in walls, floors and partitions with fire resistance ratings less than 3 hours. UL 555 classifies dynamic rated fire
dampers for use in HVAC systems that are operational in the event of fire.
Damper
DAMPER RATINGS
Fire Rating: 1½ hours
Dynamic Closure Rating
Maximum Velocity: 4,000 ft/min vertical mount only,
up to 24 in. x 24 in.;
2,000 ft/min vertical or horizontal mount
on all sizes
MaximumPressure: 4 in. wg Height
PRODUCT DETAILS
Frame: Galvanized Steel
Frame Depth: 3.688
Blade: Galvanized Steel
Closure Device: Fusible Link
Closure Temp: 165 F Width
Velocity: 2,000 ft/min
Sizing: Nominal

OPTIONS & ACCESSORIES • This drawing shows a general damper configuration and is not intended to depict the exact
configuration of all dampers in this submittal.
Transition: A • Damper is furnished approximately 0.250 in. undersize.
Union Label: No Preference • Installation instructions available at www.greenheck.com.

CODES APPROVED
This model meets the requirements for fire dampers established by:
• UL Classfied (U.S. and Canada)
Standard UL 555 (Listing #R13317)
• National Fire Protection Association
NFPA Standard 80,90A & 101
• IBC: International Building Codes
• California State Fire Marshal: CSFM listing # 3225-981:102

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Sections Wide: Sections High: Blade Stack: Mounting:
1-1 1 30.000 in. 14.000 in.
1 1 1.870 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-2 1 10.000 in. 10.000 in.
1 1 1.530 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-3 1 20.000 in. 18.000 in.
1 1 2.550 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-4 1 16.000 in. 16.000 in.
1 1 2.210 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-5 1 20.000 in. 14.000 in.
1 1 1.870 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-6 4 18.000 in. 12.000 in.
1 1 1.700 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-7 2 12.000 in. 12.000 in.
1 1 1.700 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-8 6 30.000 in. 30.000 in.
1 1 3.910 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
1-9 2 17.000 in. 17.000 in.
1 1 2.380 in. Vertical

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.1057 Generated by: eduhar@primelines-hvac.com Page 2 of 7
Printed Date: 09/21/2022
Job: SHOPPING LA MOLINA, 240822
Mark: FSD-211
Model: FSD-211

FSD-211 Combination Fire Smoke Damper


APPLICATION & DESIGN
Model FSD-211 is a combination fire smoke damper with 3V style blades. This model is designed for operation and dynamic closure in emergency fire
smoke situations. It is rated for airflow and leakage in either direction. The FSD-211 may be installed horizontally or vertically (with blades running
horizontally).

DAMPER RATINGS
UL 555 Fire Resistance Rating
Fire Rating: 1 1/2 hours
Dynamic Closure Rating: Actual ratings are size dependent
Velocity: Up to 2,000 ft/min
Pressure: 6 in. wg

UL 555S Leakage Rating


Leakage Class: I
Height
Operational Rating: Actual ratings are size dependent
Velocity: Up to 2,000 ft/min
Pressure: Up to 6 in. wg
Temperature: Up to 350 F depending on actuator
Damper
Width Location
PRODUCT DETAILS "A" 5 in.
Sideplate
Frame Type: Channel Length

Frame Thickness: 16 ga
Closure Device: RRL • This drawing shows a general damper configuration and is not intended to depict the
exact configuration of all dampers in this submittal.
Closure Temperature: 350 F • Width and height furnished approximately 0.250 in. undersize.
Blade Action: Parallel • Dampers with more than one section wide will be furnished with a single OCI device
Blade Seal: Silicone per row when the blade indicator option is selected.
• Installation instructions available at www.greenheck.com.
Axle/Linkage Material: Steel
Axle Bearings: 316 SS
Sizing: Nominal CODES APPROVED
Model FSD-211 meets the requirements for fire
ACTUATOR INFORMATION dampers, smoke dampers and combination fire smoke
dampers established by:
Actuator Type: 230 VAC
National Fire Protection Association:
Operating Mode: Two Position
NFPA Standards 80, 90A, 92, 101, 105
Actuator Operation: Spring Return
IBC (International Building Codes)
Fail Position: Closed
CSFM (California State Fire Marshal)
Time Cycle: Standard
Fire Damper Listing (3225-0981:103)
Operating Temperature: 350 F
Leakage (Smoke) Damper Listing (3230-0981:104)
Velocity: 2,000 ft/min
Underwriters Laboratories:
Pressure: 4 in. wg
UL Classified to U.S. and Canadian safety standards
NEMA Enclosure: 1
Standard 555 & 555S (Listing # R13317)
OPTIONS & ACCESSORIES
Union Label: No Preference

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-1 8 32.000 in. 32.000 in.
Honeywell MS4609F1210 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-1

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.1057 Generated by: eduhar@primelines-hvac.com Page 3 of 7
Printed Date: 09/21/2022
Job: SHOPPING LA MOLINA, 240822
Mark: FSD-211
Model: FSD-211
ID # TAG QTY Width Height CONFIGURATION
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-2 16 30.000 in. 30.000 in.
Honeywell MS4609F1210 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-1
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-21-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-3 8 37.000 in. 37.000 in.
Honeywell MS4620F1203 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-46
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-21-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-4 4 47.000 in. 47.000 in.
Honeywell MS4620F1203 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-46

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.1057 Generated by: eduhar@primelines-hvac.com Page 4 of 7
Printed Date: 09/21/2022
Job: SHOPPING LA MOLINA, 240822
Mark: FSD-211
Model: FSD-211

AMCA

AMCA Licensed for Air Performance.

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance
ratings only.

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.1057 Generated by: eduhar@primelines-hvac.com Page 5 of 7
Printed Date: 09/21/2022
Job: SHOPPING LA MOLINA, 240822
Mark: BR-30
Model: BR-30

BR-30 No Flange Barometric Relief Damper


APPLICATION & DESIGN
The BR-30 is an eccentrically pivoted backdraft damper for low velocity systems. This model is a vertical mounted damper designed to allow horizontal
airflow and prevent reverse airflow.

DAMPER RATINGS
Max. Pressure: 2 in. wg
Max. Velocity: Up to 2,000 ft/min
Temperature: 180 F

PRODUCT DETAILS
Frame: Galvanized
Frame Thickness: 16
Blade: Aluminum
Blade Seal Material: TPE
Blade Thickness: 0.063 in.
Axle Material: Plated Steel
Axle Bearings: Galvanized Ball
Start Open Pressure: 0.05 in. wg
Linkage Material: Galvanized Steel
Jamb Seal Material: None
Operation: Counterbalanced
Sizing: Nominal

OPTIONS & ACCESSORIES


Clean Wrap: No
Union Label: No Preference • This drawing shows a general damper configuration and is not intended to depict the
exact configuration of all dampers in this submittal.
• Width and Height furnished approximately 0.25 in. under size.
• Installation instructions available at www.greenheck.com.
• Pressure drop data applies to units with minimum start open pressure. Higher start
open pressure will result in different performance.

SUMMARY
SECTIONS SECTIONS SHIP
ID # TAG QTY W (in.) H (in.)
WIDE HIGH SECTIONS
5-1 14 24.000 24.000 1 1 1

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.1057 Generated by: eduhar@primelines-hvac.com Page 6 of 7
Printed Date: 09/21/2022
Job: SHOPPING LA MOLINA, 240822

Damper Drive Arrangements Job Summary -Start-

Drive Arrangement: Drive-MLS-11-1FER-1

Drive Arrangement: Drive-MLS-21-1FER-1

Damper Drive Arrangements Job Summary -End-

D:\1. EDUHAR\eduhar primelines\5. PRIMELINES 2022\3. PROYECTOS\102. SHOPPING LA MOLINA\SHOPPING LA MOLINA, 240822.gfcj
CAPS 4.39.1057 Generated by: eduhar@primelines-hvac.com Page 7 of 7
Model DFD-150
Dynamic Rated Fire Damper
1 ⁄2 Hour Fire Resistance Rating
1

Application
Model DFD-150 is approved for use in walls, floors, and partitions
with fire resistance ratings less than 3 hours. This model carries a
11⁄2 hour UL fire damper label. UL555 classifies dynamic rated fire
damper for use in HVAC systems that are operational in the event
of fire.

Ratings
UL 555 Fire Resistance
Fire Rating: 11⁄2 hours
Velocity
4000 fpm (20.3 m/s) vertical mount only, up to 24 in. x 24 in.
(610mm x 610mm);
2000 fpm (10.2 m/s) vertical or horizontal mount all sizes
Pressure
Maximum: 4 in. wg (1 kPa)

* W & H dimensions furnished approximately 1⁄4 in. (6mm) undersize.

See complete marking on


Construction product.
Construction Standard Optional UL 555S Classification
R13317
Frame Material Galvanized steel* -
Frame Depth 3 ⁄16 in. (94mm)
11
-
Blade Material Galvanized steel* -
Closure Spring Stainless steel -
Model DFD-150 meets the requirements for fire
212°F or 286°F dampers established by:
Fusible Link 165°F (74°C)
(100°C or 141°C)
• National Fire Protection Association
Mounting Vertical Horizontal
NFPA Standards, 80, 90A, and 101
* in gauges required by UL listing R13317
• International Building Codes (IBC)
• CSFM California State Fire Marshal
Fire Listing (#3225-0981:0102)

W*
W*
Stainless Steel Fusible Link (replaceable)
Closure Spring Stainless Steel Fusible Link (replaceable)
Closure Spring

H*
H*

“K” side
“K” side

Horizontal Mount
Horizontal Mount

3 11/16 in. Vertical Mount


(94mm) 3 11/16 in. Vertical Mount
(94mm)

DFD-150 January 2022


Options and Accessories
• Breakaway connections
• Clean wrap
• Closed indicator switch
• Flanges
• Grille tabs
• Retaining angles
• Security bars
• Sealed transitions and sleeve
• Transitions: B, B2, C, CO, CR, R

Document Links
Installation Instructions Life Safety Damper Catalog

Damper Product Selection Guide Specifications

Damper Warranty

DFD-150 January 2022


Factory Sleeve Option
All fire damper installations require the use of sleeves, angles and methods described in the installation instructions. Sleeves can be
field fabricated or factory furnished as a completed damper/sleeve assembly.
Sleeves are galvanized steel and are available in 20 through 10 ga. (1mm - 3.5mm) thicknesses and lengths up to 36 in. (914mm).
“K” dimension specifies location of damper within the sleeve. Minimum is 4 in. (102mm), maximum is “L” less 4 in. (102mm), which
allows for mounting angle installation, and duct connection at each end of the sleeve. If “K” dimension is not specified, it will be
provided as one half of “L” dimension (damper centered in sleeve).
Note: If using access doors, the door should be installed on the “K” side of the damper.

Sleeve

Damper
H*

K
Damper CL Damper Frame
Location W*
L
Overall Sleeve Length

Sealed Option
When sealed option is selected, B transition will need to be field sealed in the area where duct to sleeve connection is made.

Type B with sleeve

Seal this area.

DFD-150 January 2022


Type A, B, & B2
Dampers larger than maximum single section sizes are supplied in 2 or more sections of equal size. Multi-section dampers are factory
assembled ready for installation.

Size Limitations
Inches Type A Type B & B2 P
(mm) Minimum Maximum* Minimum Maximum*
Single H*
H *
4x4 36 x 36 4x3 36 x 31
Section
(102 x102) (914 x 914) (102 x 76) (914 x 787)
Vertical
VERTICAL MOUNT
72 x 48 72 x 45 HORZONTAL MOUNT
(1829 x 1219), (1829 x 1143),
Multi
60 x 60 60 x 56 1 1/2
Varies
1 1/2
Section** NA NA in.

3 in.
W* in.
W *
(1524 x 1524) or (1524 x 1422) or
Vertical
120 x 30 O* 120 x 26
H*
(3048 x 762) (3048 x 660) Type A

16 in.
10 in.
Single
4x4 30 x 30 4x3 30 x 26
Section
(102 x 102) (762 x 762) (102 x 76) (762 x 660)
Horizontal
Multi

3 in.
NA 48 x 36 48 x 33
Section** NA
W* (1219 x 914) (1219 x 838) Damper
Horizontal Location
K Dim.
Sleeve
* Sizes are based on 165°F closure temperature and 2000 fpm. Consult
Length
factory for maximum size for different temperatures and velocities. Varies
** Consult factory for number of sections. Type B2
Multi-Section Limitations - Type A
Maximum Single Section
Dimensions
Maximum damper height is 48 in. (1219mm) when combination width is
Maximum Single Section Dimensions 72 in. (1829mm) or less.

36 in. (914mm) max.


31 in.(787mm)
Max.
48 in. (1219mm)
max.

36 in.
(914mm)
36 in. (914mm) max. max.

Maximum
Type A Single Single
SectionSection
Dimensions 72 in.
(1829mm) max.

Multi Section Limitations - Type B/B2


Maximum damper height is 45 in. (1143mm) when combination
width is 72 in. (1829mm) or less.

31 in.(787mm)
Max.
Multi-Section Limitations
Maximum damper height is 48 in. (1219mm) when combination width is 48 in. (1219mm) or less.

45 in. (1143mm)
36 in. Max.
(914mm)
max.

Type B Single Section

48 in.
72 in.
(1219mm) (1829mm)
max. Max.

Multi Section Limitations - Type B/B2


DFD-150 January 2022
Maximum damper height is 45 in. (1143mm) when combination
width is 72 in. (1829mm) or less.
Type A, B, & B2
Type B & B2 Overall
Damper Dimensions
Vertical Mount

H* O* H* O*
3 (76) 5 (127) 30 (762) 34 (864)
O*
4 (102) 6 (152) 31 (787) 36 (914) H*

5 (127) 7 (178) 32 (813) 37 (940)


6 (152) 8 (203) 33 (838) 37 (940)
7 (178) 9 (229) 34 (864) 37 (940)
8 (203) 10 (254) 35 (889) 38 (965) W*

9 (229) 11 (279) 36 (914) 39 (991) Type B2


Type B
10 (254) 12 (305) 37 (940) 40 (1016)
11 (279) 13 (330) 38 (965) 41 (1041)
Horizontal Mount
12 (305) 14 (356) 39 (991) 42 (1067)
13 (330) 15 (381) 40 (1016) 43 (1092) H* O* H* O*
14 (356) 16 (406) 41 (1041) 44 (1118) 3 (76) 5 (127) 19 (483) 22 (559)
15 (381) 18 (457) 42 (1067) 45 (1143) 4 (102) 6 (152) 20 (508) 23 (584)
16 (406) 19 (483) 43 (1092) 46 (1168) 5 (127) 7 (178) 21 (533) 24 (610)
17 (432) 20 (508) 44 (1118) 47 (1194) 6 (152) 8 (203) 22 (559) 26 (660)
18 (457) 21 (533) 45 (1143) 48 (1219) 7 (178) 9 (229) 23 (584) 27 (686)
19 (483) 22 (559) 46 (1168) 50 (1270) 8 (203) 10 (254) 24 (610) 28 (711)
20 (508) 23 (584) 47 (1194) 51 (1295) 9 (229) 11 (279) 25 (635) 29 (737)
21 (533) 24 (610) 48 (1219) 52 (1321) 10 (254) 12 (305) 26 (660) 30 (762)
22 (559) 26 (660) 49 (1245) 53 (1346) 11 (279) 13 (330) 27 (686) 31 (787)
23 (584) 27 (686) 50 (1270) 54 (1372) 12 (305) 14 (356) 28 (711) 31 (787)
24 (610) 28 (711) 51 (1295) 55 (1397) 13 (330) 15 (381) 29 (737) 32 (813)
25 (635) 29 (737) 52 (1321) 56 (1422) 14 (356) 16 (406) 30 (762) 33 (838)
26 (660) 30 (762) 53 (1346) 57 (1448) 15 (381) 18 (457) 31 (787) 34 (864)
27 (686) 31 (787) 54 (1372) 58 (1473) 16 (406) 19 (483) 32 (813) 35 (889)
28 (711) 32 (813) 55 (1397) 59 (1499) 17 (432) 20 (508) 33 (838) 36 (914)
29 (737) 33 (838) 56 (1422) 60 (1524) 18 (457) 21 (533) -

* Dimension is inches (mm). These dimensions are furnished approximately 1⁄4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart. The top section is a Type B/B2 and the bottom section are Type A.

DFD-150 January 2022


Type C, CO, CR, & R
Dampers larger than maximum single section sizes are supplied in 2 or more sections of equal size. Note: All multiple section dampers
with transitions, will include a factory installed sleeve.
Type CR Type CO & C Type R+
Inches (mm)
Minimum Maximum* Minimum Maximum* Minimum Maximum*
Single Section
3 (76) 30 (762) 3 x 3 (76 x 76) 34 x 30 (864 x 762) 3 (76) 34 (864)
Vertical

70 x 44 (1778 x 1118),
Multi Section 55
NA NA 58 x 55 (1473 x 1397) or NA 58 (1473)
Vertical** (1397)
118 x 25 (2997 x 635)

Single Section
3 (76) 25 (635) 3 x 3 (76 x 76) 28 x 25 (711 x 635) 3 (76) 28 (711)
Horizontal
Multi Section
NA 32 (813) NA 46 x 32 (1163 x 787) NA 34 (864)
Horizontal**
+
With 2 in. (51mm) offset. Sizes adjust with an 1 in. (25mm) offset.
* Sizes are based on 165°F closure temperature and 2000 fpm. Consult factory for maximum size for different temperatures and velocities.
** Consult factory for number of sections.

Maximum Single Section Dimensions


Overall Damper Dimensions

Type C Type CO D*+2

Type CR

30in.
30 in. O*
(762mm)
max. (762mm)
max.

34 in. 34 in. D*
(864mm) (864mm)
max. max.
W*+2

Type CO
Type CR Type R O*

H*

W*
W*+2

34 in.
Type C
(889mm)
30 in. max.
(762mm) O*
max. Type R transition is centered on
damper frame. (Dimension are with H*
2 in. (51mm) offset.)

W*
C, CO, CR transitions are positioned 1 in. (25mm)
from bottom of sleeve.

DFD-150 January 2022


Type C, CO, CR & R
DFD-150
Dynamic Fire Damper

Vertical Mount Horizontal Mount

H* or D* O* H* or D* O* H* or D* O* H* or D* O* H* or D* O*
3 (76) 6 (152) 21 (533) 26 (660) 39 (991) 45 (1143) 3 (76) 6 (152) 18 (457) 22 (559)
4 (102) 7 (178) 22 (559) 27 (686) 40 (1016) 46 (1168) 4 (102) 7 (178) 19 (483) 23 (584)
5 (127) 8 (203) 23 (584) 28 (711) 41 (1041) 47 (1194) 5 (127) 8 (203) 20 (508) 24 (610)
6 (152) 9 (229) 24 (610) 29 (737) 42 (1067) 48 (1219) 6 (152) 9 (229) 21 (533) 26 (660)
7 (178) 10 (254) 25 (635) 30 (762) 43 (1092) 49 (1245) 7 (178) 10 (254) 22 (559) 27 (686)
8 (203) 11 (279) 26 (660) 31 (787) 44 (1118) 50 (1270) 8 (203) 11 (279) 23 (584) 28 (711)
9 (229) 12 (305) 27 (686) 32 (813) 45 (1143) 50 (1270) 9 (229) 12 (305) 24 (610) 29 (737)
10 (254) 13 (330) 28 (711) 33 (838) 46 (1168) 51 (1295) 10 (254) 13 (330) 25 (635) 30 (762)
11 (279) 14 (356) 29 (737) 34 (864) 47 (1194) 52 (1321) 11 (279) 14 (356) 26 (660) 31 (787)
12 (305) 15 (381) 30 (762) 36 (914) 48 (1219) 53 (1346) 12 (305) 15 (381) 27 (686) 31 (787)
13 (330) 16 (406) 31 (787) 37 (940) 49 (1245) 54 (1372) 13 (330) 16 (406) 28 (711) 32 (813)
14 (356) 18 (457) 32 (813) 37 (940) 50 (1270) 55 (1397) 14 (356) 18 (457) 29 (737) 33 (838)
15 (381) 19 (483) 33 (838) 39 (991) 51 (1295) 56 (1422) 15 (381) 19 (483) 30 (762) 34 (864)
16 (406) 20 (508) 34 (864) 40 (1016) 52 (1321) 57 (1448) 16 (406) 20 (508) 31 (787) 35 (889)
17 (432) 21 (533) 35 (889) 41 (1041) 53 (1346) 58 (1473) 17 (432) 21 (533) 32 (813) 36 (914)
18 (457) 22 (559) 36 (914) 42 (1067) 54 (1372) 59 (1499)
19 (483) 23 (584) 37 (940 43 (1092) 55 (1397) 60 (1524)
20 (508) 24 (610) 38 (965) 44 (1118) -

* Dimension is inches (mm). These dimensions are furnished approximately 1/4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart.

Copyright © 2022 Greenheck Fan Corporation


DFD-150, R26, January 2022
Greenheck Fan Corporation reserves the right to make
product changes without notice.
FSD-211
Combination Fire Smoke Damper

Application
Model FSD-211 is a combination fire smoke damper with 3V
style blades. This model is designed for operation and dynamic
closure in emergency fire smoke situations. It is rated for airflow
and leakage in either direction. The FSD-211 may be installed
vertically (with blades running horizontal) or horizontally.

Ratings
UL 555 Fire Resistance Rating
Fire Rating: 11⁄2 hours
Dynamic Closure Rating: Actual ratings are size dependent
Velocity: Up to 2000 fpm (10.2 m/s)
Pressure: Up to 6 in. wg (1.5 kPa)
UL 555S Leakage Rating
Leakage Class: I
Operational Rating: Actual ratings are size dependent Width and Height dimensions furnished approximately 1⁄4 in. (6mm)
undersize. Add sleeve thickness for overall sleeved damper dimension.
Velocity: Up to 2000 fpm (10.2 m/s)
Pressure: Up to 6 in. wg (1.5 kPa)
See complete marking on
Temperature: Up to 350°F (177°C) - depending product.
upon the actuator
UL 555 and UL 555S
Construction Classification R13317

Standard Optional
Frame Material Galvanized steel - Model FSD-211 meets the requirements for fire dampers,
Frame Material smoke dampers and combination fire smoke dampers
16 ga. (1.5mm) -
Thickness established by:
5 in. x 1in. National Fire Protection Association
Frame Type (127mm x 25mm) - NFPA Standards 80, 90A, 92, 101 & 105
hat channel IBC International Building Codes
Blade Material Galvanized steel - CSFM California State Fire Marshal
Blade Material Fire Damper Listing (#3225-0981:0103)
16 ga. (1.5mm) -
Thickness Leakage (Smoke) Damper Listing (#3230-0981:0104)
Blade Type 3V -
Blade Action Parallel -
Plated steel out of
Linkage airstream, concealed - Maximum Size
in jamb Minimum
WxH Single Multiple Section
Axle Bearings 316SS - Size
Section Horizontal Vertical
Axle Material Plated steel -
4 in. wg (1 kPa) pressure
Blade Seals Silicone -
32 x 50 or
Jamb Seals Stainless Steel - Inches 6x6 144 x 96 128 x 100
36 x 48
RRL/OCI,
Closure Device RRL 813 x 1270 or
TOR mm 152 x 152 3658 x 2438 3251 x 2540
914 x 1219
212°F (100°C),
6 in. wg (1.5 kPa) pressure
Closure 250°F (121°C),
165°F (74°C)
Temperature 286°F (141°C)*, Inches 6x6 36 x 48 144 x 96 128 x 96
350°F (177°C)
mm 152 x 152 914 x 1219 3658 x 2438 3251 x 2438

* only available with fusible link

FSD-211 May 2022


Options
• Breakaway connections
• Clean wrap
• Greenheck test switches (GTS)
• Grille tabs
• Momentary switches
• Retaining angles
• RRL/OCI
• Security bars
• Sealed transitions and sleeve
• Smoke detectors
• TOR
• Transitions: C, O, R

Document Links
Installation Instructions Life Safety Damper Catalog

Damper Product Selection Guide Alternate Installation Solutions for Life Safety Dampers

Damper Warranty
Specifications

FSD-211 May 2022


Pressure Drop
AMCA Figure 5.2
5D

D 4 (W) (H)
3.14

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.04 500 0.02 500 0.01 500 0.01 500 0.03
1000 0.14 1000 0.07 1000 0.04 1000 0.06 1000 0.10
1500 0.31 1500 0.16 1500 0.09 1500 0.13 1500 0.23
2000 0.55 2000 0.29 2000 0.16 2000 0.23 2000 0.41
2500 0.86 2500 0.45 2500 0.25 2500 0.36 2500 0.63
3000 1.24 3000 0.65 3000 0.36 3000 0.52 3000 0.91
3500 1.69 3500 0.89 3500 0.49 3500 0.70 3500 1.24
4000 2.20 4000 1.16 4000 0.64 4000 0.92 4000 1.62

AMCA Figure 5.3

5D 6D

5D 6D

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg)5D Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.02 500 0.01 500 0.01 500 0.01 500 0.02
1000 0.09 1000 0.04 1000 0.03 1000 0.04 1000 0.07
1500 0.20 1500 0.09 D 4 (W)
1500(H) 0.06 1500 0.10 1500 0.16
2000 5D
0.36 2000 0.16 3.14
2000 0.11 2000 0.17 2000 0.29
2500 0.56 2500 0.25 2500 0.17 2500 0.27 2500 0.45
3000 0.81 3000 0.35 3000 0.24 3000 0.39 3000 0.64
3500 1.10 3500 0.48D 4 (W) (H) 3500 0.33 3500 0.53 3500 0.88
4000 1.44 4000 0.63 3.14 4000 0.42 4000 0.70 4000 1.14

AMCA Figure 5.5

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.06 500 0.03 500 0.03 500 0.03 500 0.04
1000 0.22 1000 0.14 1000 0.12 1000 0.13 1000 0.17
1500 0.50 1500 0.31 1500 0.26 1500 0.30 1500 0.38
2000 0.89 2000 0.54 2000 0.46 2000 0.53 2000 0.67
2500 1.39 2500 0.85 2500 0.73 2500 0.83 2500 1.04
3000 2.00 3000 1.22 3000 1.05 3000 1.19 3000 1.50
3500 2.72 3500 1.66 3500 1.42 3500 1.62 3500 2.05
4000 3.55 4000 2.17 4000 1.86 4000 2.11 4000 2.67

Greenheck Fan Corporation certifies that the model FSD-


211 shown herein is licensed to bear the AMCA Seal.
The ratings shown are based on tests and procedures
performed in accordance with AMCA Publication 511
and comply with the requirements of the AMCA Certified
Ratings Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.

FSD-211 May 2022


Space Envelopes
Externally mounted actuators always require space outside of T*
the damper sleeve. The “S” dimension illustrates the clearance T*
S
required for various available actuators.
On dampers less than 18 in. (457mm) high, actuators may also
require clearances above and/or below the sleeve. “B” and “T”
dimensions are worst case clearance requirements for some
dampers less than 18 in. (457 mm) high. All dampers 18 in.
(457mm) or more in height, do not require these worst case
clearances. If space availability above or below the damper
sleeve is limited, each damper size should be individually
evaluated.

B*

B*

B* T* S
With With Piggyback
Actuator Type/Model
RRL, RRL/OCI, or RRL, RRL/OCI, or
No Yes
TOR TOR
120 Volt AC
FSLF120 (-S) Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
FSNF120 (-S) Belimo 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
FSTF120 (-S) Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
MS4104 Series Honeywell 1
⁄2 in. (13mm) 8 ⁄2 in (216mm)
1
6 in. (152mm) NA
MS4X09 Series Honeywell 1
⁄2 in. (13mm) 8 ⁄2 in (216mm)
1
6 in. (152mm) NA
MS4120 Series Honeywell 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
24 Volt AC
FSAF24 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) NA
FSTF24 (-S) Belimo 7 ⁄16 in (195mm)
11 1
⁄2 in. (13mm) 6 in. (152mm) NA
FSLF24-S Belimo 7 ⁄16 in (195mm)
11
0 6 in. (152mm) NA
FSNF24 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
MS8104 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS8120 Series Honeywell 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229m)
230 Volt AC
FSLF230-S Belimo 7 ⁄16 in (195mm)
11
0 6 in. (152mm) NA
FSNF230-S Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
FSTF230-S Belimo 711⁄16 in (195mm) 1
⁄2 in. (13mm) 6 in. (152mm) NA
MS4604 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS4X09 Series Honeywell 1
⁄2 in. (13mm) 8 ⁄2 in (216mm)
1
6 in. (152mm) NA
MS4620 Series Honeywell 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in.

FSD-211 May 2022


Contained Actuator Option
Dampers can be ordered with a “contained actuator option”. This option will result in the actuator being oriented such that it extends
no more than 11⁄2 inches above or below the sleeve. Note that some damper configurations that are 11 inches high or less will have the
RRL, RRL/OCI, or TOR mounted on the side opposite the actuator when the contained actuator option is selected.

Sleeve Length
Damper
Location

RRL, RRL/OCI, or TOR


opposite actuator

Components contained
within 1½ in. of sleeve
top and bottom

Actuator Parallel

1½ in.

RRL, RRL/OCI, or TOR

Sleeve and Sideplate Dimensions


The drawings below and corresponding table show the position of the FSD-211 damper when mounted in a factory sleeve. The
standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation of
retaining angles and duct connections.
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be positioned at
other locations within a range of 6 in. (152mm) to 16 in. (406mm) for the "A" dimension.

Sleeve 1½ in. (38mm)


maximum blade
clearance
"A" Dimension
in. (mm)
3¾ in.
Sleeve Std Sleeve Max Sideplate
(95mm)
All Dampers (RRL) 73⁄16 (183) 16 (406) 63⁄16 (157)
When H is 11 in. (279mm) or less
12 (305) 16 (406) 12 (305)
5³/8 in.
with RRL, RRL/OCI, or TOR
(137mm)
NOTE: Entire damper frame is not required to be installed
11/2within
in. max. the wall. The damper
Varies due to
height blades, when closed should be contained within the wall.

5 in. 3 3/4 in.


A (127mm)

Sleeve Length

Sleeve 6 in.

Varies
5 3/8 in.

5 in.
A 5 in.
A
Sideplate
Length** Sideplate Sleeve Length

FSD-211 May 2022


FSD-211
Transitioned Damper Dimensions Combination Fire Smoke Damper
When a combination fire smoke damper is being used in conjunction with round or oval ductwork, the FSD-211 can be supplied
in a factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct dimensions.
Drawings below show overall damper size.

D* + 2 in. (51mm) +T s
W* + 2 in. (51mm)+Ts
W* + 2 in. (51mm)+Ts

D* + 2 in. (51mm)+Ts
H* + 2 in. (51mm)+T s H* + 2 in. (51mm)+Ts
2 1/8 in. H*
2 1/8 in. H* (54mm)
2 1/8 in. (54mm)
(54mm)
Lorem ipsum

W*
W*
16 in. D* 16 in. 16 in.
(406mm) (406mm) (406mm)
Minimum Minimum Minimum

TYPE R TYPE O TYPE C


50 in.
(1270mm)
*These dimensions are furnished approximately ¼ in.50(6mm)
in. undersize, except round and oval dimensions which are approximately 1⁄8 in.(3mm) undersize. 50 in.
(1270mm) (1270mm)
Ts = (2)(Sleeve Thickness)

32 in. (813mm)
Multiple Section Dampers 32 in. (813mm)
64 in. (1626mm)
32 in. (813mm)

Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The
following figures show maximum damper section size and assembly configurations for multi-section dampers.

Lorem ipsum

50 in. 100 in.


(1270mm) (2540mm)
50 in.
(1270mm)

50 in. 96 in. (2435mm)


32 in. (813mm) (1270mm)
64 in. (1626mm)
. (813mm) 32 in. (813mm)
128 in. (2540mm)

32 in. (813mm)

Two Section 4 sections wide


2 sections high

Copyright ® 2022 Greenheck Fan Corporation


FSD-211, R18, May 2022
100 in. Greenheck Fan Corporation reserves the right to make
(2540mm) product changes without notice
Drive Arrangement Definition
On multi-blade dampers (except vertical blade and Face & Bypass), they are given a drive arrangement code
that helps describe the construction of the damper. The following breaks down what each number and letter
represents.

22-2FEL- 2
1 2 3 4 5 6 7
1 Number of sections wide

2 Number of sections high


Jackshaft

Damper Height
3 Number of actuators or manual quadrants

4 Who supplies the actuators or manual quadrants


F - Factory
Actuator or
C - Customer Supplied (field mounted) Manual Quadrant
5 Actuator or manual quadrant mounting
E - External
I - Internal
B - Both internal and external

6 Actuator or manual quadrant location


L - Left hand drive
R - Right hand drive
B - Both right and left Damper Width

7 Number of jackshafts

Vertical blade and face & bypass dampers are given a configuration ID number that helps describe the
construction of the damper. See the following examples:

Model Drive Arrangement


Prefix
AMD-23, 33, 42 AMD
AMD-42V VB
DFD-210, 230; DFDAF-310;
MLS
DFDAF-330; SEDFD-210
FBH & FBV FB
FSD, OFSD, CFSD, SMD, SEFSD,
SSFSD, SESMD, SSSMD series MLS
(except vertical blade models)
FSD-311V, SMD-301V VB
GFSD series GFSD
ICD series CC
IMO series MLS
MBD-15 & VCD series (except CC
vertical blade models)
VCD-xxV (vertical blade models) VB
BR-30 Series
Barometric Relief Dampers
Vertical Mount - Horizontal Airflow

Application
The BR-30 series is an eccentrically pivoted backdraft damper for
low velocity systems. BR-30 series is a vertical mounted damper
and designed to allow horizontal airflow and prevent reverse
airflow. The blade is formed aluminum which increases sensitivity
and reduces blade mounted counterbalance weights. On-blade
counterweights are provided to fine tune start-to-open and full
open blade operation. Ball bearings minimize friction.
Recommended Applications
• Gravity hood intake and exhaust
• Stairwell pressurization
• Room pressurization
• Ductwork outlets
Poor Applications
• Propeller fan outlets (high velocity)
• Centrifugal fan outlets (high velocity)
• Building pressurization (sensitive to wind)
• Pressure relief exceeding 0.3 in. wg (0.075 kPa) *W & H dimensions furnished approximately 1⁄4 in. (6mm) undersize.

Ratings
1.5 in. 1.5 in.
Back Pressure
2.0 in. wg (0.5 kPa)
Start-to-Open Pressure
0.05 in. wg (.01 kPa)
4 3/8 in.
Velocity MAX

2,000 fpm (10.2 m/s) 1 in.


MAX
Temperature Airflow
180°F (82°C)

Construction
Standard Optional
304SS,
Frame Material Galvanized Steel
Aluminum
5 in.
Frame Thickness 16 ga. (1.5mm) -
No Flange (BR-30) - BR-30 BR-31 BR-32
Frame Type Flange on Discharge (BR-31) - No Flange Flange on Flange on
Flange on Intake (BR-32) - Discharge Intake
Blade Material Aluminum -
Blade Seal TPE None
Size Limitations
Blade Thickness 0.063 in. (1.6mm) -
Maximum Size
Minimum
Axle Plated Steel 316SS WxH
Size Single Section Multiple Sections
Axle Bearings Galvanized Ball Acetal w/SS Ball
Inches 8x6 48 x 74 96 x 148
Linkage Material Galvanized Steel -
mm 203 x 152 1220 x 1880 2438 x 3759
Jamb Seal None EPDM
Blade mounted with -
Counterbalance adjustable weights
Baked Enamel, Feature
Paint Finishes None Hi Pro Polyester, • Selectable start open from .05 to .30 in. wg
Industrial Epoxy (0.012 kPa - 0.075 kPa).

BR-30 Series May 2022


BR-30 Series
Performance Data Barometric Relief Dampers

Performance data results from testing a 12 in. x 12 in. and 36 in. x 36 in. (305mm x 305mm and 914mm x 914mm) in accordance with
AMCA Standard 500-D using Figure 5.3 (fully ducted), 5.2 (ducted exhausting into an open area), and 5.5 (plenum mounted). All data
has been corrected to represent standard air density at 0.075 lb/ft3 (1.201 kg/m3).
Pressure drop data shown is based on minimum start open pressure. Higher start open pressure will result in different pressure drop.

Damper Size Damper Size


12 in. x 12 in. 36 in. x 36 in.
(305mm x 305mm) (914mm x 914mm)
2.0 2.0

5.5 5.5
1.0 1.0
.9 .9
.8 .8
5.2 5.2
.7 .7
.6 .6
.5 .5
5.3 5.3
Pressure Drop (in. wg)

Pressure Drop (in. wg)


.4 .4

.3 .3

.2 .2

.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05

.04 .04

.03 .03
100 200 300 400 500 600 800 1000 2000 3000 100 200 300 400 500 600 800 1000 2000 3000
700 900 700 900

Velocity Velocity
(fpm) (fpm)

Document Links