Zone Sizing Summary for Air system

Project Name: Textile Factort-Lahore01 06/11/2012


Prepared by: Meinhardt-Pakistan 08:09PM

Air System Information


Air System Name Air system Number of zones 1
Equipment Class UNDEF Floor Area 30169.0 ft²
Air System Type SZCAV Location Lahore, Pakistan

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM Sum of space airflow rates Calculation Months Jan to Dec
Space CFM Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft²) CFM/ft²
Zone 1 1108.8 62471 62471 Jul 1700 378.1 30169.0 2.07

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Zone # 1 1 391.1 Jul 1700 21853 135.9 10350.0 2.11
Zone#2 1 221.8 Jul 1700 12390 92.2 4740.0 2.61
Zone#3 1 63.3 Jul 1600 3536 30.9 2102.0 1.68
Zone#5 1 180.3 Jun 1600 10074 46.3 3680.0 2.74
Zone#6 1 241.5 Jul 1600 13492 72.8 7225.0 1.87
Zone#4 1 20.2 Jan 1700 1126 0.0 2072.0 0.54

Hourly Analysis Program v.4.3 Page 1 of 1