Application of Demand Factor: 1st 3000 VA @ 100%; Remainder 10,800@ 35% d.f. = 3,780 VA ICB
Total net Computed Load: 3000 +3780 + 1840 @ 100% (4)+3,910 @ 100% (3)+6,440 @ 100% (2)= 38,750 VA
Total Full Load Current: 38,750/230= 168.48 A MAIN PROTECTION :

FEEDER SIZE :

LOAD SCHEDULE

C. SERVICE EQUIPMENT:
Maximum Current Rating of Circuit Breaker:
Load from 34.5kV/230V Single-phase Transformer
[ = 333.06A
Anticipation of Future Load:
125% (333.06 A) = 416.33A
SINGLE LINE DIAGRAM Service Equipment Rating:
COMPUTATION Use one 400-ampere trip, 2-pole, 230-volt molded
case circuit breaker
COMPUTATION: D. TRANSFORMER:
A. Total load: 90,123 VA x 85% Demand Factor Rating:
=76,604.55 VA Total Connected Load
B. SERVICE ENTRANCE CONDUCTORS: 76,604.55 VA = 76,604.55 VA
Use 2-250 Use 75 KVA, 230 V secondary neutral brought
Use 1-30 for grounding conductors out (grounded), inherently single-phase transformer
Use 90 RSC

ELECTRICAL
ENGINEERING