You are on page 1of 28

How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

EE Questions / Answers Electrical Formulas & Equations Electrical Wiring Installation How To

 Trending

How to Find The Suitable Size of Cable & Wire for


Electrical Wiring Installation? – Examples in Imperial &
Metric System
 Electrical Technology  112  13 minutes read

How to Determine the Proper Size of Wire & Cable for Electrical Wiring Installation?
The following step by step guide will show you how to find the right size of cable and wire or any other
conductor for electrical wiring installation with solved examples (in both British or English and SI System i.e.
Imperial and Metric System respectively).

Keep in mind that it is very important to select proper wire size while sizing a wire for electrical installations.
An inappropriate size of wire for bigger loads having high current may create chaos which leads to failure of
the electrical equipment, hazardous fire and serious injuries.

Table of Contents 
1. Voltage Drop in Cables
1.1. Example:
2. Tables & Charts for Proper Cable & Wire Sizes
3. How to Find the Voltage Drop in a Cable?
4. How to Determine the Proper Cable & Wire Size for Given Load?
5. Solved Examples of Proper Wire & Cable Size
5.1. Example 1 … (Imperial, British or English System)
5.2. Example 2 … (SI / Metric / Decimal System)
5.3. Example 3
5.4. Example 4
6. NEC Wire Size Table 310.15(B)(16) (formerly Table 310.16) & Chart

Voltage Drop in Cables


We know that all conductors, wires and cables (except superconductors) have some amount of resistance.

This resistance is directly proportional to the length and inversely proportional to the diameter of conductor
i.e.

R ∝ L/a … [Laws of resistance R = ρ (L/a)]

Whenever current flows through a conductor, a voltage drop occurs in that conductor. Generally, voltage drop
may be neglected for small length of conductors but in case of a lower diameter and long length conductors,
we have to take into account the considerable voltage drops for proper wiring installation and future load
management.

According to IEEE rule B-23, at any point between power supply terminal and installation, Voltage drop
should not increase above 2.5% of the provided (supply) voltage.

Related Posts:

How to Find the Proper Size of Circuit Breaker? Breaker Calculator & Examples
How to Find the Voltage & Ampere Rating of Switch, Plug, Outlet & Receptacle
How to calculate the Cable size for LT & HT Motors?

1 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Example:
If the supply voltage is 220V AC, then the value of allowable voltage drop should be;

Allowable Voltage Drop = 220 x (2.5/100) = 5.5V

Similarly, if the supply voltage is 120V AC, the allowable voltage drop should be no more than 3V ( 120V x
2.5%).

In electrical wiring circuits, voltage drops also occur from the distribution board to the different sub circuit and
final sub circuits, but for sub circuits and final sub circuits, the value of voltage drop should be half of that
allowable voltage drops (i.e. 2.75V of 5.5V as calculated above)

Normally, Voltage drop in tables is described in Ampere per meter (A/m) e.g. what would be the voltage
drop in a one meter cable which caries one Ampere current?

There are two methods to define the voltage drop in a cable which we will discus below.

In SI (System international and metric system) voltage drop is described by ampere per meter (A/m).

In FPS (foot pound system) voltage drop is described in length based which is 100 feet.

Update: Now you may also use the following electrical Calculators to find Voltage drop & the wire size
in American wire gauge systems.

1. Electrical Wire & Cable Size Calculator (Copper & Aluminum)


2. Wire & Cable Size Calculator in AWG
3. Voltage Drop in Wire & Cable Calculator

Tables & Charts for Proper Cable & Wire Sizes


Below are the important tables which you should follow for determining the proper size of cable for Electrical
Wiring Installation.

Click image to enlarge

Click image to enlarge

2 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Click image to enlarge

Click image to enlarge

Click image to enlarge

How to Find the Voltage Drop in a Cable?


To find voltage drop in a cable, follow the simple steps given below.

First of all, find the maximum allowable voltage drop.


Now, find the load current.
Now, according to the load current, select a proper cable (which current rating should be nearest to the
calculated load current) from table 1.
From Table 1, find the voltage drop in meter or 100 feet (what system you prefer) according its rated
current.

(Stay cool :) We will follow both methods and systems for finding voltage drops (in meters and 100 feet) in
our solved example for whole electrical installation wiring).

Now, calculate the voltage drop for the actual length of the wiring circuit according to its rated current
with the help of following formulas.

(Actual length of circuit x volt drop for 1m) /100 ===> to find Volt drop in per meter.

3 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

(Actual length of circuit x volt drop for 100ft) /100 ===> to find volt drop in 100 feet.

Now multiply this calculated value of volt drop by load factor where;

Load factor = Load Current to be taken by Cable/ Rated Current of Cable given in the table.

This is the value of Volt drop in the cables when load current flows through it.
If the calculated value of voltage drop is less than the value calculated in step (1) (Maximum allowable
voltage drop), than the size of selected cable is proper
If the calculated value of voltage drop is greater than the value calculated in step (1) (Maximum
allowable voltage drop), than calculate voltage drop for the next (greater in size) cable and so on until
the calculated value of voltage drop became less than the maximum allowable voltage drop calculated
in step (1).

Related Posts:

How to Find the Size of Earth Conductor, Earthing Lead & Earth Electrodes?
How to Do Electrical Earthing? – Methods and Types of Earthing & Grounding (Step by Step)
How to Control One Lamp From Two or Three Places?

How to Determine the Proper Cable & Wire Size for Given Load?
Below are solved examples showing how to find the proper Cable Size for Given Load.

For a given load, cable size may be found with the help of different tables but we should keep in mind and
follow the rules about voltage drop.

Determining the size of cable for a given load, take into account the following rules.

For a given load except the known value of current, there should be 20% extra scope of current for
additional, future or emergency needs.

From Energy meter to Distribution board, Voltage drop should be 1.25% and for final sub circuit, voltage drop
should not exceed 2.5% of Supply voltage.

Consider the change in temperature, when needed, use temperature factor (Table 3)

Also, consider the load factor when finding the size of cable

When determining the cable size, consider the wiring system i.e. in an open wiring system, temperature
would be low but in conduit wiring, temperature increases due to the absence of air.

Note: Keep in mind Diversity Factor in Electrical Wring Installation while selecting the proper size of
cable for electrical wiring installation

Related Posts:

How to calculate the value of resistor for LEDs (with different types of LED’s circuits)
How To Locate Faults In Cables? Cable Faults, Types & Causes
Why Coaxial Cables are Highly Insulated?

Solved Examples of Proper Wire & Cable Size


Following are the examples of determining the proper Size of cables for electrical wiring installation which will
make it easy to understand the method of “how to determine the proper size of cable for a given load”.

Example 1 … (Imperial, British or English System)


For Electrical wiring installation in a building, Total load is 4.5kW and total length of cable from energy meter
to sub circuit distribution board is 35 feet. Supply voltages are 220V and temperature is 40°C (104°F). Find
the most suitable size of cable from energy meter to sub circuit if wiring is installed in conduits.

4 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Solution:-

Total Load = 4.5kW = 4.5 x1000W = 4500W


20% additional load = 4500 x (20/100) = 900W
Total Load = 4500W + 900W = 5400W
Total Current = I = P/V = 5400W /220V =24.5A

Now select the size of cable for load current of 24.5A (from Table 1) which is 7/0.036 (28 Amperes). It means
we can use 7/0.036 cable according to table 1.

Now check the selected (7/0.036) cable with temperature factor in Table 3, so the temperature factor is 0.94
(in table 3) at 40°C (104°F) and current carrying capacity of (7/0.036) is 28A, therefore, current carrying
capacity of this cable at 40°C (104°F) would be;

Current rating for 40°C (104°F) = 28 x 0.94 = 26.32 Amp.

Since the calculated value (26.32 Amp) at 40°C (104°F) is less than that of current carrying capacity of
(7/0.036) cable which is 28A, therefore this size of cable (7/0.036) is also suitable with respect to
temperature.

Now find the voltage drop for 100 feet for this (7/0.036) cable from Table 4 which is 7V, But in our case, the
length of cable is 35 feet. Therefore, the voltage drop for 35 feet cable would be;

Actual Voltage drop for 35 feet = (7 x 35/100) x (24.5/28) = 2.1V

And Allowable voltage drop = (2.5 x 220)/100 = 5.5V

Here The Actual Voltage Drop (2.1V) is less than that of maximum allowable voltage drop of 5.5V. Therefore,
the appropriate and most suitable cable size is (7/0.036) for that given load for Electrical Wiring Installation.

Related Post: How to Wire Auto & Manual Changeover & Transfer Switch? (1 & 3 Phase)

Example 2 … (SI / Metric / Decimal System)


What type and size of cable suits for given situation

Load = 5.8kW
Volts = 230V AV
Length of Circuit = 35 meter
Temperature = 35°C (95°F)

Solution:-

Load = 5.8kW = 5800W

Voltage = 230V

Current = I = P/V = 5800 / 230 = 25.2A

20% additional load current = (20/100) x 5.2A = 5A

Total Load Current = 25.2A + 5A = 30.2A

Now select the size of cable for load current of 30.2A (from Table 1) which is 7/1.04 (31 Amperes). It means
we can use 7/0.036 cable according to the table 1.

Now check the selected (7/1.04) cable with temperature factor in Table 3, so the temperature factor is 0.97
(in table 3) at 35°C (95°F) and current carrying capacity of (7/1.04) is 31A, therefore, current carrying
capacity of this cable at 40°C (104°F) would be;

Current rating for 35°C (95°F) = 31 x 0.97 = 30 Amp.

Since the calculated value (30 Amp) at 35°C (95°F) is less than that of current carrying capacity of (7/1.04)

5 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

cable which is 31A, therefore this size of cable (7/1.04) is also suitable with respect to temperature.

Now find the voltage drop for per ampere meter for this (7/1.04) cable from (Table 5) which is 7mV, But in our
case, the length of cable is 35 meter. Therefore, the voltage drop for 35 meter cable would be:

Actual Voltage drop for 35meter =

= mV x I x L

= (7/1000) x 30×35 = 7.6V

And Allowable voltage drop = (2.5 x 230)/100 = 5.75V

Here the actual Voltage drop (7.35V) is greater than that of maximum allowable voltage drop of 5.75V.
Therefore, this is not a suitable size of cable for that given load. So we will select the next size of selected
cable (7/1.04) which is 7/1.35 and find the voltage drop again.

According to Table (5) the current rating of 7/1.35 is 40 Amperes and the voltage drop in per ampere meter is
4.1 mV (See table (5)). Therefore, the actual voltage drop for 35 meter cable would be;

Actual Voltage drop for 35 meter =

= mV x I x L

(4.1/1000) x 40×35 = 7.35V = 5.74V

This drop is less than that of maximum allowable voltage drop. So this is the most appropriate and suitable
cable or wire size.

Related Posts:

How to Connect a Portable Generator to the Home Supply – 4 Methods


How to Connect Automatic UPS / Inverter to the Home Supply System?

Example 3
Following Loads are connected in a building:-

Sub-Circuit 1

2 lamps each o 1000W and


4 fans each of 80W
2 TV each of 120W

Sub-Circuit 2

6 Lamps each of 80W and


5 sockets each of 100W
4 lamps each of 800W

If supply voltages are 230 V AC, then calculate circuit current and Cable size for each Sub-Circuit?

Solution:-

Total load of Sub-Circuit 1

= (2 x 1000) + (4 x 80) + (2×120)

= 2000W + 320W + 240W = 2560W

Current for Sub-Circuit 1 = I = P/V = 2560/230 = 11.1A

Total load of Sub-Circuit 2

6 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

= (6 x 80) + (5 x 100) + (4 x 800)

= 480W + 500W + 3200W= 4180W

Current for Sub-Circuit 2 = I = P/V = 4180/230 = 18.1A

Therefore, Cable suggested for sub circuit 1 = 3/.029” (13 Amp) or 1/1.38 mm (13 Amp)

Cable suggested for Sub-Circuit 2 = 7/.029” (21 Amp) or 7/0.85 mm (24 Amp)

Total Current drawn by both Sub-Circuits = 11.1A + 18.1A = 29.27 A

So cable suggested for Main-Circuit = 7/.044″ (34 Amp) or 7/1.04 mm (31 Amp)

Related Posts:

American Wire Gauge “AWG” Chart – Wire Size & Ampacity Table
American Wire Gauge (AWG) Calculator – AWG Size Chart & Table
Standard Wire Gauge “SWG” Calculator – SWG Size Chart & Table

Example 4
A 10H.P (7.46kW) three phase squirrel cage induction motor of continuous rating using Star-Delta starting is
connected through 400V supply by three single core PVC cables run in conduit from 250feet (76.2m) away
from multi-way distribution fuse board. Its full load current is 19A. Average summer temperature in Electrical
installation wiring is 35°C (95°F). Calculate the size of the cable for the motor?

Solution:-

Motor load = 10H.P = 10 x 746 = 7460W *(1H.P = 746W)


Supply Voltage = 400V (3-Phase)
Length of cable = 250feet (76.2m)
Motor full load Current = 19A
Temperature factor for 35°C (95°F) = 0.97 (From Table 3)

Now select the size of cable for full load motor current of 19A (from Table 4) which is 7/0.36” (23 Amperes)
*(Remember that this is a 3-phase system i.e. 3-core cable) and the voltage drop is 5.3V for 100 Feet. It
means we can use 7/0.036 cable according Table (4).

Now check the selected (7/0.036) cable with temperature factor in table (3), so the temperature factor is 0.97
(in table 3) at 35°C (95°F) and current carrying capacity of (7/0.036”) is 23 Amperes, therefore, current
carrying capacity of this cable at 40°C (104°F) would be:

Current rating for 40°C (104°F) = 23 x 0.97 = 22.31 Amp.

Since the calculated value (22.31 Amp) at 35°C (95°F) is less than that of current carrying capacity of
(7/0.036) cable which is 23A, therefore this size of cable (7/0.036) is also suitable with respect to
temperature.

Load factor = 19/23 = 0.826

Now find the voltage drop for 100feet for this (7/0.036) cable from table (4) which is 5.3V, But in our case, the
length of cable is 250 feet. Therefore, the voltage drop for 250 feet cable would be;

Actual Voltage drop for 250feet = (5.3 x 250/100) x 0.826 = 10.94V

And maximum Allowable voltage drop = (2.5/100) x 400V= 10V

Here the actual Voltage drop (10.94V) is greater than that of maximum allowable voltage drop of 10V.
Therefore, this is a not a suitable size of cable for the given load. So we will select the next size of selected
cable (7/0.036) which is 7/0.044 and find the voltage drop again. According to Table (4) the current rating of

7 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

7/0.044 is 28 Amperes and the volt drop in per 100 feet is 4.1V (see Table 4). Therefore, the actual voltage
drop for 250 feet cable would be;

Actual Voltage drop for 250 feet =

= Volt drop per 100 feet x length of cable x load factor

= (4.1/100) x 250 x 0.826 = 8.46V

And Maximum Allowable voltage drop = (2.5/100) x 400V= 10V

The actual voltage drop is less than that of maximum allowable voltage drop. So this is the most appropriate
and suitable cable size for electrical wiring installation in a given situation.

NEC Wire Size Table 310.15(B)(16) (formerly Table 310.16) & Chart
NEC (National Electrical Code) Table 310.15(B)(16) (formerly Table 310.16) – 310.60 – ARTICLE 310 –
Conductors for General Wiring & Allowable Ampacities of Conductors & Wire Sizes based on AWG
(American Wire Gauge).

310.60 ARTICLE 310 — CONDUCTORS FOR GENERAL WIRING

Table 310.15(B)(16) (formerly Table 310.16) Allowable Ampacities of Insulated Conductors Rated Up to
and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-
Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of
30°C (86°F)*

Temperature Rating of Conductor [See Table 310.104(A).]

60°C 75°C 90°C 60°C 75°C


90°C (194°F)
(140°F) (167°F) (194°F) (140°F) (167°F)

Types
TBS, SA,
SIS, FEP,
FEPB,
MI, RHH,
Types Types TBS, SA,
RHW-2, Size
Size RHW, SIS, THHN, THHW,
THHN, Types RHW, AWG
AWG or THHW,
THHW, THHW, or
Types THW, Types TW, THW-2, THWN-2,
kcmil THW,
TW, UF THWN, UF RHH, RHW-2, kcmil
THW-2, THWN,
XHHW, USE-2, XHH,
THWN-2, XHHW, USE
USE, XHHW, XHHW-2,
USE-2,
ZW ZW-2
XHH,
XHHW,

XHHW-2,
ZW-2

COPPER ALUMINUM OR COPPER-CLAD ALUMINUM

18** — — 14 — — — —

16** — — 18 — — — —

14** 15 20 25 — — — —

12** 20 25 30 15 20 25 12**

10** 30 35 40 25 30 35 10**

8 40 50 55 35 40 45 8

6 55 65 75 40 50 55 6

8 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

4 70 85 95 55 65 75 4

3 85 100 115 65 75 85 3

2 95 115 130 75 90 100 2

1 110 130 145 85 100 115 1

1/0 125 150 170 100 120 135 1/0

2/0 145 175 195 115 135 150 2/0

3/0 165 200 225 130 155 175 3/0

4/0 195 230 260 150 180 205 4/0

250 215 255 290 170 205 230 250

300 240 285 320 195 230 260 300

350 260 310 350 210 250 280 350

400 280 335 380 225 270 305 400

500 320 380 430 260 310 350 500

600 350 420 475 285 340 385 600

700 385 460 520 315 375 425 700

750 400 475 535 320 385 435 750

800 410 490 555 330 395 445 800

900 435 520 585 355 425 480 900

1000 455 545 615 375 445 500 1000

1250 495 590 665 405 485 545 1250

1500 525 625 705 435 520 585 1500

1750 545 650 735 455 545 615 1750

2000 555 665 750 470 560 630 2000

*Refer to 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other
than 30°C (86°F). Refer to 310.15(B)(3)(a) for more than three current-carrying conductors.
**Refer to 240.4(D) for conductor overcurrent protection limitations.

Here is the NEC table as a chart (image format to downloads as a reference)

Click image to enlarge

9 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Related Posts:

How to Size a Load Center, Panelboards and Distribution Board?


How to Determine the Number of Circuit Breakers in a Panel Board?
How to Determine the Right Size Capacity of a Subpanel?
How to Calculate the Suitable Capacitor Size in Farads & kVAR for Power factor Improvement
How to Convert Capacitor Farads into kVAR & Vice Versa (For Power factor improvement)
How To check a Capacitor with Digital & Analog Multimeter. 8 Methods
How to Check the Value of Burnt Resistor. 3 Handy methods
How To: Electrical & Electronics Tutorials
Basic Electrical Wiring Installation Tutorials

 Tags Cable Size Table 310.15(B)(16) Table 310.16 Wire Size

SHOW ALL COMMENTS

10 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

AC Fundamentals Alternating Current EE Questions / Answers Over Head Lines

Power factor Power System Single Phase AC Circuits

Advantages of Power factor


improvement and Correction
 Electrical Technology  2  1 minute read

Advantages of Power factor improvement and Correction:

Following are the merits and benefits of improvedPower factor;


1. Increase in efficiency of system and devices
2. Low Voltage Drop
3. Reduction in size of a conductor and cable which reduces cost of the
Cooper
4. An Increase in available power
5. Line Losses (Copper Losses) I2R is reduced
6. Appropriate Size of Electrical Machines (Transformer, Generators etc)
7. Eliminate the penalty of low power factor from the Electric Supply
Company
8. Low kWh (Kilo Watt per hour)
9. Saving in the power bill
10. Better usage of power system, lines and generators etc
11. Saving in energy as well as rating and the cost of the electrical devices
and equipment is reduced

You may also read about:

Power Factor

Active, Reactive, Apparent and Complex Power. Simple


explanation with formulas.

Causes of low Power Factor


Disadvantages of Low Power Factor
Power Factor improvement Methods with Their
advantages & Disadvantages

How to Calculate the Suitable Capacitor Size in Farads &


kVAR for Power factor Improvement (Easiest way ever)
How to Convert Capacitor Farads into kVAR and Vice
Versa (For Power factor improvement)

SHOW ALL COMMENTS

11 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

EE Questions / Answers How To Over Head Lines Power factor

Power System Single Phase AC Circuits Three Phase AC Circuits

Causes of low Power Factor


 Electrical Technology  5  1 minute read

Causes of low Power Factor


The main cause of low Power factor is Inductive Load. As in pure
inductive circuit, Current lags 90° from Voltage, this large difference of
phase angle between current and voltage causes zero power factor.
Basically, all those circuit having Capacitance and inductance (except
resonance circuit (or Tune Circuit) where inductive reactance =
capacitive reactance (XL = Xc), so the circuit becomes a resistive
circuit), power factor would be exist over there because Capacitance
and inductance causes in difference of phase angle (θ) between current
and voltage.
there are a lot of disadvantages of low Pf and we must improve Pf .
Following are the causes of low Power factor:
1. Single phase and three phase induction Motors(Usually, Induction
motor works
at poor power factor i.e. at:
Full load, Pf = 0.8 -0.9
Small load, Pf = 0.2 -0.3
No Load, Pf may come to Zero (0).
2. Varying Load in Power System(As we know that load on power
system is varying. During low load period, supply voltage is increased
which increase the magnetizing current which cause the decreased
power factor)
3. Industrial heating furnaces
4. Electrical discharge lamps (High intensity discharge lighting) Arc
lamps (operate
a very low power factor)
5. Transformers
6. Harmonic Currents
You may also read about:

12 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Power Factor
Active, Reactive, Apparent and Complex Power. Simple
explanation with formulas.
Disadvantages of Low Power Factor
Power Factor improvement Methods with Their
advantages & Disadvantages
Advantages of Power factor improvement and
Correction  
How to Calculate the Suitable Capacitor Size in Farads
& kVAR for Power factor Improvement (Easiest way
ever)

EE Questions / Answers How To Over Head Lines Power factor

Power System Single Phase AC Circuits Three Phase AC Circuits

Power Factor improvement


Methods with Their advantages &
Disadvantages
 Electrical Technology  12  5 minutes read

Methods for Power Factor Improvement


The following devices and equipment are used for power factor
correction in an electrical system.

1. Static Capacitor
2. Synchronous Condenser
3. Phase Advancer

1. Static Capacitor
We know that most of the industries and power system loads are
inductive that take lagging current which decreases the system
power factor (See disadvantages of low power factor) . For power
factor improvement purposes, static capacitors are connected in
parallel with those devices which work on low power factor.

These static capacitors provide leading current which neutralizes


(totally or approximately) the lagging inductive component of load
current (i.e. leading component neutralizes or eliminates the lagging
component of load current) thus power factor of the load circuit is

13 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

component of load current) thus power factor of the load circuit is


improved.

These capacitors are installed in vicinity of large inductive loads e.g.


induction motors and transformers etc., and improve the load circuit
power factor to improve the system or device efficiency.

Suppose, here is a single phase inductive load which is taking


lagging current (I) and the load power factor is Cosθ as shown in
fig-1.

In fig-2, a capacitor (C) has been connected in parallel with load.


Now a current (IC) is flowing through capacitor which lead 90° from
the supply voltage ( Note that Capacitor provides leading Current i.e.,
In a pure capacitive circuit, Current leading 90° from the supply
Voltage, in other words, Voltage are 90° lagging from Current). The
load current is (I). The vector combination of (I) and (IC) is (I’) which is
lagging from voltage at θ2 as shown in fig 3.

It can be seen from fig 3 that angle of θ2 < θ1 i.e. angle of θ2 is less
than from angle of θ2. Therefore Cosθ2 is less than from Cosθ1
(Cosθ2 > Cosθ1). Hence the load power factor is improved by
capacitor.

Also note that after the power factor improvement, the circuit current
would be less than from the low power factor circuit current. Also,
before and after the power factor improvement, the active component
of current would be the same in that circuit because the capacitor

14 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

The age of static capacitor bank is less (8 – 10 years)


With changing load, we have to ON or OFF the capacitor bank,
which causes switching surges on the system
If the rated voltage increases, then it causes damage it
Once the capacitors spoiled, then repairing is costly

2. Synchronous Condenser
When a Synchronous motor operates at No-load and is over-excited
then it’s called a synchronous condenser. Whenever a Synchronous
motor is over-excited then it provides leading current and works like a
capacitor.

In a synchronous motor, a separate DC source is used for the


excitation of the field winding. Therefore the input supply only
provides current to energize the stator i.e. the current provided is in-
phase with the supply voltage. So the power factor remains unity.

The power factor can be adjusted by varying the DC excitation.


Increasing the DC excitation, the power factor varies from lagging to
unity and leading power factor. When the DC excitation increases,
the field windings are over-magnetized. The input supply provides a
current component to the stator to compensate for this over-
magnetization. This current leads to the supply voltage causing a
leading power factor or generating reactive power.

An inductive load consumes reactive power causing a lagging power

15 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

AC Fundamentals Alternating Current Basic Concepts

Basic Electrical Fundamentals DC Circuits EE Questions / Answers

Electric Circuit Analysis Electrical Formulas & Equations Resistors

It is expensive (mainte
Ohm’s Law: Simple Explanation
with Statement and Formulas
 Electrical Technology  6  3 minutes read

What is Ohm’s Law? Explanation, Formula and Solved


Example
main shaft
Ohm’s Lawof the motor

The relationship between Current through and Voltage across a

16 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

conductor was first discovered by a German scientist George Simon


Ohm. This relationship is called Ohm’s Law which can be stated as;

The Current “I” flowing through a conductor is


directly proportional to the potential difference
i.e. Voltage “V” across its ends provided the
physical conditions (i.e. temperature, strain,
etc) do not change.

In other words;


In any electric circuit, the Current “I” is
directly proportional to the applied
Voltage “V” and inversely proportional to
the total circuit Resistance “R” if the
physical condition of the circuit remain
unchanged i.e. (Temperature of the
circuit does not change)

Mathematically,

I ∝ V … or … V ÷ I => Where R = Constant

Where “R” is a Constant of proportionality and is called Resistance of


the Conductor.

Current = Potential Difference ÷ Resistance

I=V÷R

Related Posts:

Lenz’s Law of Electromagnetic Induction


What is Faraday’s Law? Laws of Electromagnetic Induction
What is Coulomb’s Law? Laws of Electrostatics With Example

Formulas & Equations of Ohm’s Law

17 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Current = Voltage ÷ Resistance

Amps = Volts ÷ Ohms (Ω)

3.

R=V÷I

Resistance = Voltage ÷ Current

Ohms (Ω) = Volts ÷ Amps

Where:

V = Voltage in Volts
I = Current in Amperes
R = Resistance in Ohms (Ω)

Better funny explanation of Ohm’s Law

Click image to enlarge

18 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Coulomb’s Laws of Magnetic Force – Formula & Solved

Basic Concepts Electric Circuit Analysis Electrical Formulas & Equations

5000+ Electrical and Electronic


Engineering Formulas & Equations
 Electrical Technology  4  1 minute read

voltage and resistance


List of All Electrical and Electronics Engineering
Formulas

19 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Formulas
Note: Click on the desired box button below to see the related
electrical and electronics engineering formulas and equation with
details.

Basic Electrical Engineering Formulas & Equations

Basic Electrical Quantities Formulas

Ohm’s, Kirchhoff’s & Coulomb’s Laws – Formulas

Voltage & Current Divider Rules (VDR & CDR)


Equations

Power Formulas in DC & AC Single & Three-Phase


Circuits

Resistance, Conductance, Impedance & Admittance


Formulas

Resistance, Capacitance & Inductance in


Series/Parallel Formulas

20 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Formulas

DC Generator Formulas and Equations

Losses in Electrical Machines – Formulas & Equations

Induction Motor & Linear Induction Motors Formulas &


Equations

Synchronous, Stepper & AC Motors Formulas &


Equations

Synchronous Generator & Alternator Formulas &


Equations

Transformer Formulas and Equations

Equations & Formulas For RLC Circuits (Series &


Parallel)

Time Constant τ “Tau”


Electrical & Electronics Notes and Articles How To

21 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Electrical & Electronics Notes and Articles How To

“How to” Electrical & Electronics


Engineering Tutorials
 Electrical Technology  1  4 minutes read

Basic “How to” Electrical & Electronics Engineering


Tutorials

How to Test a Capacitor by Digital & Analog Multimeter – 6


Methods.
How to Test a Diode using Digital & Analog Multimeter – 4
Ways.
How to Check a Transistor by Multimeter (DMM+AVO) – NPN &
PNP – 4 Ways.
How To Perform a Continuity Test for Electrical Components
with Multimeter?
How to calculate the value of resistor for LED’s (with different
types of LED’s circuits)
How to find the Value of 2, 3, 4, 5 & 6 Band Resistors – Resistor
Color Code Calculation.
How to calculate or Find the value of SMD Resistors
How to Calculate/Find the Rating of Transformer in kVA (Single
Phase and Three Phase)?
How To Calculate Your Electricity Bill. Easy and simple
Explanation.
How to test a battery with Test meter?
How To Wire Switches In Series?

22 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

How To Wire a 3-Phase kWh meter from the Supply to The Main
Distribution Board?
How to Wire Solar Panel to 220 V inverter, 12V battery ,12V,DC
Load and 220V AC Load
How much Watts Solar Panel We need for our Home Electrical
appliances?
How To Wire Two 24V Solar Panels in Parallel with Two, 12V
Batteries in Series with Automatic UPS System
How to Size and Find the Numbers of Ceiling Fan in a Room?
How to Calculate the Number of Fluorescent Lamps in a Final
Sub Circuit?
How to Calculate the Number of Incandescent Lamps in a Final
Sub Circuit?
How to install a ceiling Fan with a Dimmer Switch (Part 1)?
How to connect/install a Capacitor with a Ceiling Fan (Part 2)
How to make LED String/Strip Circuit Diagram Using PCR-406 (
Very Easy )
How to operate DC LED Night Lamp on 230 V AC Main?
How to Design & Simulate Electrical/Electronics Projects &

15 Must Have Android A


Electrical Wiring Installation How To

 Trending

Electrical Wiring Installation


Diagrams & Tutorials

23 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Diagrams & Tutorials


 Electrical Technology  49  Less than a minute

Basic Electrical Wiring Installation Diagrams & Step by


Step Guides

Basic Electrical Home Wiring Diagrams &


Tutorials

 Different Types of Electrical Wiring Systems and Methods of


Electrical Wiring Installation
 Electrical Wiring Color Codes for AC & DC – NEC & IEC
 How To Wire Switches In Series?
 How To Wire Switches in Parallel?
 How To wire Lamps in Series?
 How To Wire Lamps in Parallel?
 Which Bulb Glows Brighter When Connected in Series and
Parallel & Why?
 How to Control a Lamp by a Single Way or One-way Switch?
How to Read MCB Nam
 How to control each lamp by separately switch in parallel
How Electric Phase or L
lighting circuit?
How to find Diversity Fa
 Staircase Wiring Circuit Diagram – How to Control a Lamp
from 2 Places by 2-Way Switches?
 Batteries
2 Way Switch – How to Control One Lamp From Two or Three
Places?
 (Three
How toMethods)
control one lamp from six different places by using two,
2-way
How switches
to do and
Earthing & four
G intermediate switches?
What
 How to is
doIntermediate
Series, Paraswitch, its construction, working and

24 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

Main Distribution Board?


 How to Size and Find the Numbers of Ceiling Fan in a Room?
 How to Calculate the Number of Fluorescent Lamps in a Final
Sub Circuit?
 How to Calculate the Number of Incandescent Lamps in a
Final Sub Circuit?
 What is the objection to have lamps in a house-lighting circuit
connected in series?
 How to Wire a Ceiling Fan? Dimmer Switch and Remote
Control Wiring – 5 Ways
 How to Replace a Ceiling Fan Capacitor? – 3 Ways.
 The Star-Delta (Y-Δ) 3-phase Motor Starting Method by
Automatic star-delta starter with Timer.
 Room Air Cooler Electrical Wiring Diagram # 1
 Room Air Cooler Wiring Diagram # 2. (With Capacitor marking
and Installation)
 Star and Delta Connected Lighting Loads – Electrical Wiring
Installation
 How to Size a Generator? Portable, Backup & Standby for
Home & Commercial Applications
 How to Connect a Portable Generator to Home Supply System
(Three Methods)
 Basic Electrical Engineering Tools and Their Uses
 Testing Electrical and Electronics Components and Devices
with Multimeter
 10+ Design & Simulation Tools for Electrical/Electronics
Engineers Online

25 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

 How to Find the Number of Lights on a Single Circuit Breaker?


 How to Find the Number of Outlets on a Single Circuit
Breaker?
 How to Size a Load Center, Panelboards and Distribution
Board?

IEC – UK & EU

 How to Wire Single-Phase, 230V Consumer Unit with RCD?


IEC, UK & EU
 How to Wire 230V Dual Split Load Consumer Unit? –
RCD+MCB

26 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

27 of 28 31/10/22, 09:56
How to Find The Suitable Size of Cable & Wire for Elec... https://www.electricaltechnology.org/2013/10/how-to-d...

28 of 28 31/10/22, 09:56

You might also like