You are on page 1of 10

740 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 24, NO.

3, SEPTEMBER 2009

Integration of an Energy Capacitor System With a


Variable-Speed Wind Generator
S. M. Muyeen, Member, IEEE, Rion Takahashi, Member, IEEE, Toshiaki Murata,
and Junji Tamura, Senior Member, IEEE

Abstract—This paper presents a system using an energy capac- List of Principal Symbols
itor system (ECS) to smoothen the output power fluctuation of a
variable-speed wind farm. The variable-speed wind turbine driv- WTGS Wind turbine generator system
ing a permanent-magnet synchronous generator is considered to be EDLC Electric double layer capacitor
connected to the ac network through a fully controlled frequency ECS Energy capacitor system
converter. The detailed modeling and control strategy of the fre- VSWT Variable-speed wind turbine
quency converter as well as variable-speed operation of a wind
PMSG Permanent-magnet synchronous generator
turbine generator system are demonstrated. Afterward, a suitable
and economical topology of ECS composed of a current-controlled CC-VSI Current-controlled voltage-source inverter
voltage-source inverter, dc–dc buck/boost converter, and an electric VSC Voltage-source converter
double layer capacitor (EDLC) bank is presented, including their FLC Fuzzy logic controller
control strategies. Exponential moving average is used to generate FLARA Fuzzy-logic-aided reference adjuster
the real input power reference of ECS. Another novel feature of
this paper is the incorporation of a fuzzy-logic-controlled reference
EMA Exponential moving average
signal adjuster in the control of the dc–dc buck/boost converter, in PREF Reference power
which the stored energy of the EDLC bank is utilized in an effi- PW F Wind farm total output (delivered from all wind
cient way. Due to this controller, the energy storage capacity of the generators in a wind farm to a collection point)
EDLC bank can be reduced in size, thus resulting in reduction of PL Line power (supplied to the utility grid)
the overall cost of the ECS unit as well as decrease in irrepressible
operations during high and low energy levels of the EDLC bank.
PE Real power of ECS
Finally, extensive simulation results are presented that validate the WEDLC Stored energy of EDLC bank.
effectiveness of the proposed system to smoothen the output power
fluctuation of the variable-speed wind farm.
I. INTRODUCTION
Index Terms—Current-controlled voltage-source inverter (CC-
VSI), dc–dc buck/boost converter, electric double layer capac- LOBALLY, wind energy has become one of the main-
itor (EDLC), energy capacitor system (ECS), fuzzy logic con-
troller (FLC), permanent-magnet synchronous generator (PMSG),
voltage-source converter (VSC), wind energy.
G stream energy sources and an important player in the
world’s energy markets at the end of 2007. In 2007, 20 000 MW
wind power was installed all over the world, bringing the world-
wide installed capacity to 94 112 MW. This is an increase of
NOMENCLATURE 31% compared with the 2006 market and represents an overall
increase in the global installed capacity of about 27% [1].
Cp Power coefficient.
Though wind power is considered as a prospective energy
Cp opt Optimum value of power coefficient.
source, wind power fluctuation due to randomly varying wind
N Total number of rules.
speed is still a serious problem for power grid companies or
Pw Extracted power from the wind.
transmission system owners (TSOs). Therefore, it is essential
R Turbine blade radius.
to emphasize the research on the smoothening of wind power
Vw Wind speed.
fluctuation. It is possible to smoothen the wind power fluctuation
Wi Degree of conformity
up to a certain range by the blade pitch angle control of the wind
β Blade pitch angle.
turbine [2], [3]. A flywheel energy system is proposed in [4]–[6]
λ Tip speed ratio.
to smoothen the wind power fluctuation. A superconducting
λopt Optimum value of tip speed ratio.
magnetic energy storage (SMES) system for smoothening wind
µ(x) Grade of membership.
power fluctuation is also reported in [7]–[9]. In some reports, a
ρ Air density.
battery energy storage system (BESS) [10] or static synchronous
ωr Rotational speed.
compensator (STATCOM) integrated with BESS [11] has also
been proposed to smoothen wind power fluctuation.
Another relatively new energy storage technology is ECS,
Manuscript received August 3, 2008. Current version published August 21,
2009. This work was supported by the Japan Society for the Promotion of Sci- which is composed of power electronic devices and EDLC
ence (JSPS) under Grant-in-Aid for JSPS Fellows. Paper no. TEC-00301-2008. [12]–[21]. From the environmental viewpoint, it is a relatively
The authors are with the Department of Electrical and Electronic Engi- clean source of energy as it does not contain any toxic ma-
neering, Kitami Institute of Technology, Kitami 090-8507, Japan (e-mail:
muyeen@pullout.elec.kitami-it.ac.jp). terial. EDLC has a simple charging method; after full charge,
Digital Object Identifier 10.1109/TEC.2009.2025323 it stops accepting charge. It can be cycled millions of time,
0885-8969/$26.00 © 2009 IEEE
MUYEEN et al.: INTEGRATION OF AN ENERGY CAPACITOR SYSTEM WITH A VARIABLE-SPEED WIND GENERATOR 741

i.e., it has a virtually unlimited cycle life. Its standby loss is


also very low. Therefore, ECS can be used effectively for wind
power application. Some reports have already been presented
to show the effectiveness of ECS connected with a fixed-speed
WTGS [20], [21].
This paper proposes to integrate ECS with a wind farm com-
posed of VSWTs driving PMSGs. Permanent-magnet machines
are characterized as having large air gaps, which reduce flux
linkage even in machines with multimagnetic poles [22], [23].
Fig. 1. ECS connected to dc-link of the frequency converter.
As a result, low-rotational-speed generators can be manufac-
tured with relatively small sizes with respect to its power rating.
Moreover, the gearbox can be omitted due to low rotational power fluctuations of a wind farm composed of variable-speed
speed in the PMSG wind generation system, thus resulting in generators.
low cost. In a recent survey, the gearbox is found to be the most
critical component, since its downtime per failure is high in
comparison to other components in a WTGS [24]. In a VSWT- II. BACKGROUND OF THE STUDY
PMSG, the generator is connected to the ac network using, in In [20], ECS is used for smoothening the output power of a
general, the fully controlled frequency converter. This paper pro- fixed-speed wind generator, though the reference power of the
poses a VSC based sinusoidal pulsewidth-modulated (PWM) control system is not determined from a realistic viewpoint and
frequency converter. The frequency converter is composed of real wind speed data are not used throughout the analysis. In
a generator-side ac/dc converter, dc-link capacitor, and grid- our previous study, we developed a complete control system
side dc/ac inverter, where interpolated firing pulses are used as for ECS connected to the terminal of a wind farm composed of
the switching signals for the insulated gate bipolar transistors fixed-speed generators [21]. In general, a fixed capacitor bank is
(IGBTs) of both the converter and inverter. For the maximum connected to the terminal of a fixed-speed wind generator, which
power point tracking (MPPT) operation, rotor speed is used as a cannot maintain constant terminal voltage under randomly vary-
controller input instead of wind speed, because the rotor speed ing wind speed condition. Therefore, the reactive power control
can be measured more precisely and more easily than the wind by ECS would also be very important in addition to the real
speed. The detailed control schemes of a converter/inverter and power control while connected with fixed-speed wind genera-
variable-speed operation of a wind turbine are demonstrated in tors. Considering these concerns, the well-designed cascaded
this paper. On the other hand, the control scheme of ECS is control used successfully in industrial applications is adopted
based on a simple sinusoidal PWM-based CC-VSI and dc–dc in that study for the control of VSC of ECS [21]. However,
buck/boost converter using IGBTs, which is especially appo- in the case of variable-speed operation of WTGS, the terminal
site when ECS is connected to the terminal of a wind farm. To voltage is maintained constant, in general, with the help of a
resolve the foremost problem in wind generator output power frequency converter. Therefore, in this study, a simple CC-VSI
smoothening, the EMA is used for the determination of the is adopted, which also has the bidirectional power flow capabil-
power reference of the dc–dc buck/boost converter of ECS ity, thus replacing the VSC used in the previous attempt [21].
[25]. This reduces the intricacy of the control system due to reduced
Another novel feature of this study is the incorporation of numbers of proportional–integral (PI) controllers and reference
a FLARA in the control of the dc–dc buck/boost converter of frame transformation, and hence, reduces the cost of the overall
ECS. The FLARA works with monitoring the stored energy system.
level of the EDLC bank. When the stored energy of the EDLC The variable-speed WTGS has recently become more popular
bank reaches at the rated level, it cannot store more energy. On than the fixed-speed one. In 2004, the worldwide market share
the contrary, when the energy level of the EDLC bank goes of variable-speed WTGS was more than 60%, and it is growing
below a certain percentage, i.e., 20% of its rated capacity, the more and more [26]. A detailed study is presented in [27], where
EDLC bank cannot discharge anymore. In the aforementioned ECS is connected to the dc link of the frequency converter of
circumstances, it is not possible to absorb or provide real power the VSWT-PMSG, as shown in Fig. 1. This topology reduces
to/from the ECS unit according to the real power reference the cost of the bidirectional converter of the ECS unit and needs
of the dc–dc buck/boost converter. Therefore, in this study, the only a dc–dc buck/boost converter to control the real power,
reference for the dc–dc buck/boost converter is adjusted by using which is quite appropriate for a stand-alone system. However, if
FLARA, which augments the control ability without making this system is applied to a wind farm composed of multiple wind
the ECS unit excessively large, and hence, reduces the overall generators, the ECS unit needs to be installed at each VSWT
cost of the ECS unit. The stored energy of EDLC can be used system and controlled for smoothening each “line power.” If
efficiently in the cases of low- and high-energy conditions of the the total output of a wind farm is to be smoothened, then the
EDLC bank. Real wind speed data are used in the simulation control strategy of each ECS unit will become very complicated.
analyses to obtain a realistic response. Finally, it is concluded Considering this aspect, comparatively cost-effective topology
that the proposed ECS with a CC-VSI and dc–dc buck/boost of ECS composed of a CC-VSI and dc–dc buck/boost converter
converter controlled by FLARA can smoothen well the output is developed, which is installed at the terminal of the wind farm,
742 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 24, NO. 3, SEPTEMBER 2009

Since measurement of the precise wind speed is, in general,


difficult, it is better to calculate the maximum power Pm ax ,
without the measurement of wind speed, as
 3
2 ωr R
Pm ax = 0.5 ρ π R Cp opt (2)
λopt
where ωr denotes the rotor speed of the wind turbine, and λopt
and Cp opt are the optimum value of the tip speed ratio and
power coefficient, respectively.
From (2), it is clear that the maximum generated power
P Ref fc , which is actually the reference power of the frequency
converter, is proportional to the cube of rotational speed. When
the rotational speed exceeds the rated speed of the wind turbine,
Fig. 2. ECS connected to wind farm terminal. the pitch controller, which is presented in [29], is used to keep
the turbine output at the rated value.
For VSWT, the drive train modeling is not so influential due to
the decoupling effect of the power electronic converters between
the generator and the grid system [30]. Therefore, in this study,
the simple one-mass lumped model of WTGS is used.

B. Modeling of the Frequency Converter


In this study, the frequency converter composed of a
generator-side ac/dc converter, dc-link capacitor, and grid-side
dc/ac inverter is used for the direct-drive VSWT-PMSG sys-
tem. The PMSG model available in the package software
PSCAD/EMTDC [31] is used. The control strategy of the fre-
quency converter is demonstrated next.
Fig. 3. Turbine characteristic with MPPT. 1) Sinusoidal PWM Controller: A sinusoidal PWM con-
troller, which is composed of three main circuits (i.e., a high-
frequency carrier circuit, sinusoidal modulating reference sig-
as shown in Fig. 2. Moreover, incorporation of FLARA can nal circuit, and the interpolated firing pulse circuit), is mod-
reduce the overall cost of the ECS unit with increased control eled on the PSCAD/EMTDC software, which generates the
ability. switching signals for the IGBT gates in both the generator-side
converter and grid-side inverter. The interpolated firing pulse
III. COMPONENT MODELING OF THE VARIABLE-SPEED circuit is a simulation technique concerned with generating
SYSTEM firing pulses through the interpolation procedure. This allows
A. Wind Turbine Modeling for exact switching between time steps based on a compari-
son between the sinusoidal reference and the high-frequency
The mathematical relation for the mechanical power extrac- carrier signal [32]. The triangular carrier frequency is chosen
tion from the wind can be expressed as follows [28]: to be 1000 Hz for the converter and 1050 Hz for the inverter,
Pw = 0.5 ρ π R2 Vw3 CP (λ, β) (1) respectively.
2) Synchronization and Transformation: In grid-side in-
where Pw is the extracted power from the wind, ρ is the air verter control, a phase-locked loop (PLL) is used to synchronize
density (in kilograms per cubic meter), R is the blade radius (in the reference frame by locking it to the ac network voltage. On
meters), Vw is the wind speed (in meters per second), and Cp is the other hand, in the generator-side converter control, the ro-
the power coefficient that is a function of both tip speed ratio λ tor angular position calculated from the rotor speed is used for
and blade pitch angle β (in degrees). the synchronization of the reference frame. Angles θt and θr
In the variable-speed WTGS, the generated active power de- are used for the reference frame transformation in the grid-side
pends on the power coefficient Cp , which is related to the pro- inverter and generator-side converter, respectively.
portion of power extracted from the wind. For each instanta- 3) Generator-Side Converter: In generator-side converter
neous wind speed, there is a specific turbine rotational speed control, the cascaded control scheme, as shown in Fig. 4, is
that corresponds to the maximum active power extraction from considered. As the converter is directly connected to the PMSG,
the wind. In this way, the MPPT in the variable-speed WTGS its q-axis current is proportional to the active power. The active
increases the energy generation in all types of wind conditions. power reference of the converter PRef fc is determined in such
The wind turbine characteristic used in this study is shown in a way as to provide the maximum power to the grid. The d-axis
Fig. 3, including the maximum power point trajectory [29]. stator current is proportional to the reactive power. The reactive
MUYEEN et al.: INTEGRATION OF AN ENERGY CAPACITOR SYSTEM WITH A VARIABLE-SPEED WIND GENERATOR 743

Fig. 6. Schematic diagram of ECS.

Fig. 4. Control block diagram of the generator-side converter.

Fig. 7. Detailed model of the EDLC bank.

TABLE I
DETAILED MODEL PARAMETERS OF THE EDLC BANK

1) Modeling of EDLC: The distributed model of the EDLC


bank, as shown in Fig. 7, is considered in the simulation analyses
Fig. 5. Control block diagram of the grid-side inverter. as it can represent the terminal characteristics of the EDLC cell
precisely [20]. In this study, the considered EDLC cell is rated
at 2.7 V, 3000 F. The rated EDLC bank voltage is chosen to
power reference is set to zero to perform unity power factor be 1.3 kV. The rated capacity of the EDLC bank is 2.0 MW,
operation. 0.036 MW·h. It is assumed that 25 EDLC strings are working in
4) Grid-Side Inverter: Control blocks for the grid-side in- parallel where each string is composed of 481 EDLC cells. The
verter are shown in Fig. 5, which is based on the cascaded steps of the EDLC bank parameters determination are available
control scheme. The dc-link voltage can be controlled by the in [25]. The parameters of the EDLC bank are shown in Table I.
d-axis current. The dc-link capacitor value is chosen to be 2) CC-VSI Modeling: The CC-VSI, as marked with the
10 000 µF. The rated dc-link voltage is 2.3 kV. On the other doted line in Fig. 6, has the bidirectional real and reactive power
hand, the reactive power of the grid-side inverter can be con- control ability, avoiding the intricacy of the controller designing.
trolled by the q-axis current. The reactive power reference is set Based on the inverter switching functions, the inverter simula-
in such a way that the terminal voltage on the high-voltage side tion model shown in Fig. 8 has been developed [33], [34]. The
of the transformer (VHVS T ) remains constant at 1.0 per unit desired and actual currents are compared and the error signal is
(p.u.). This voltage difference is chosen as the reactive power determined. Then, the error signal is processed through the sinu-
reference, as shown in Fig. 5. soidal PWM controller to generate interpolated firing pulses of
the IGBT switches of the VSI. Considering the VSI connected
with the ac network through the coupling transformer, it can be
IV. MODELING OF ECS derived easily that real and reactive powers of the VSI are pro-
In this study, ECS composed of a CC-VSI, dc–dc buck/boost portional to the d and q components of its current phasor. If we
converter, and an EDLC bank is considered to be connected to neglect the switching losses and harmonics, then the real power
the terminal of the wind farm. A schematic diagram of ECS is proportional to the dc-link voltage of the VSI. Based on this
is shown in Fig. 6. CC-VSI controls the dc-link voltage and concept, a very simple VSI control strategy has been developed
the reactive power output, whereas the real power output is in this paper, as shown in Fig. 9. The controller maintains the
controlled by the dc–dc buck/boost converter. dc-link voltage as constant and also has the ability to provide
744 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 24, NO. 3, SEPTEMBER 2009

Fig. 10. Multiplication factor determination strategy in FLARA.

Fig. 8. Simulation model of PWM-VSI.

Fig. 11. Fuzzy membership functions of W E D L C .

conditions, the performance of the ECS in wind farm line power


smoothening deteriorates, and a large energy storage capacity of
the EDLC bank is needed to avoid such a situation, thus result-
ing in the increase of the system cost. Therefore, in this study,
Fig. 9. Control block of the CC-VSI.
a FLARA is incorporated in the control of a dc–dc buck/boost
converter, which adjusts PREF and observes the stored energy
or absorb reactive power to/from the grid. Therefore, the wind level of the EDLC bank, as shown in Fig. 10. When the energy
farm terminal voltage can be maintained constant at the desired level of the EDLC bank goes below 40% or above 90%, PREF
reference level set by TSO, who usually set this value once or a is modified by the factor shown in the figure. Unless specified,
few times a day. This also augments the stability margin during PREF would remain the same (i.e., 1). Hence, the stored energy
a grid disturbance, though this is not the focus of this study. The of the EDLC bank can be used effectively, and controllability of
rated dc-link voltage is 1.3 kV. The ECS is connected to the ECS during high- and low-energy stages also increases. More-
22.0-kV line through a single step-down transformer (22.0 kV/ over, as overcharging and overdischarging rates of the EDLC
0.72 kV) with 0.25 p.u. leakage reactance (base value bank can be decreased, its service life can be increased.
5.0 MV·A). The dc-link capacitor value is 5000 µF. The details of the proposed FLC are described next.
3) Generation of Line Power Reference PREF : The objec- a) Fuzzification: For the design of the proposed FLC, the
tive of this study is to smoothen the line power PL of the wind stored energy of the EDLC bank WEDLC and multiplication
farm. The reference PREF is generated from EMA of the wind factor δ are chosen as the input and output, respectively. The tri-
farm’s total output PW F . The formula for an EMA is [25] angular membership functions for the input fuzzy set are shown
in Fig. 11 in which the linguistic variables are represented by
EMA(C) = [(C − P ) × K] + P (3)
low-level end (LLE), low-level start (LLS), no change center
where C is the current value, P is the previous period’s EMA, (NCC), high-level start (HLS), and high-level end (HLE). The
and K is a weighting factor. grade of input membership functions can be obtained from the
For a period-based EMA, K is equal to 2/(1 + N ), where N is following equation [31]:
the specified number of periods. In this paper, 180-s (60 periods
[w − 2 |x − m|]
each of 3 s) EMA is used to generate the line power reference µ(x) = (4)
PREF . w
4) Fuzzy-Logic-Aided Reference Adjuster: The ECS would where µ(x) is the value of the grade of membership, w is the
supply/absorb the necessary/surplus real power according to the width, m is the coordinate of the point at which the grade of
error signal between PREF and PL by using a dc–dc buck/boost membership is 1, and x is the value of the input variable.
converter, which is demonstrated in our early work [21]. How- b) Fuzzy rule base: The specific feature of the proposed
ever, the EDLC bank cannot store energy when it is fully FLC is its very simple structure having only one input variable
charged. Similarly, it cannot provide necessary real power when and one output variable. The use of single input and single output
its energy level goes below a certain percentage. During such variables makes the fuzzy controller very straightforward. The
MUYEEN et al.: INTEGRATION OF AN ENERGY CAPACITOR SYSTEM WITH A VARIABLE-SPEED WIND GENERATOR 745

TABLE II
FUZZY RULE TABLE

Fig. 13. Model system.

TABLE III
GENERATOR PARAMETERS

Fig. 12. Control block of the dc–dc buck/boost converter.

control rules of the proposed controller are determined from


the viewpoint of feasible system operation and are shown in
Table II.
c) Inference and defuzzification: For inference mecha-
nism of the FLC design, Mamdani’s method [35] is adopted.
According to the Mamdani, the degree of conformity Wi of
each fuzzy rule is as follows:

Wi = µi (x) (5)

where i is the rule number.


The center-of-area method is the most well-known and rather
simple defuzzification method [35], which is used here to de- Fig. 14. Wind speed data.
termine the output crispy value (i.e., the multiplying factor δ).
This is given by the following expression: V. MODEL SYSTEM
N The detailed switching models are considered to simulate
i=1 Wi Ci
δ=  N
(6) the frequency converter of the VSWT-PMSG, and the PWM
i=1 Wi CC-VSI and dc–dc buck/boost converter of ECS for the sake
of precise analysis. Detailed switching models require a large
where N is the total number of rules and Ci is the value of δ in number of state variables and a much smaller step size in com-
the fuzzy rule table. parison to time average models, which makes the simulation
5) Modeling of the DC–DC Buck/Boost Converter: The dc– slower. However, when dealing with a relatively new technol-
dc buck/boost converter marked with the dashed line in Fig. 6 ogy, such as ECS, a switching model is preferred. The aggre-
operates alternately by controlling switches g1 and g2 to be gated wind farm model is used in this study to speed up the
ON or OFF. At first, the reference power calculated using EMA
simulation, where several WTGSs are lumped together to ob-
is adjusted through the FLARA. When the line power PL is tain a large WTGS. The model system used in the simulation
less than the adjusted reference power PREF ADJ , the EDLC study is shown in Fig. 13, where ECS is connected to the wind
discharges, thus working in the boost converter mode and farm connection point K. The parameters of the PMS are shown
vice versa. The error signal between the line power and the ad- in Table III. The system base is 5 MV·A.
justed reference power is processed through a PI controller, and
the dc–dc buck/boost converter duty cycle is produced. Then,
the duty cycle is compared with the sawtooth carrier wave to VI. SIMULATION RESULTS
generate the gate signals for the buck/boost converter, as shown To verify the effectiveness of the proposed system, simula-
in Fig. 12. The frequency of the sawtooth carrier signal is chosen tion analyses have been performed using real wind speed data
to be 250 Hz. obtained in Hokkaido Island, Japan, as shown in Fig. 14. The
746 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 24, NO. 3, SEPTEMBER 2009

Fig. 18. DC-link voltage of the frequency converter of VSWT-PMSG.


Fig. 15. Wind farm output power.

Fig. 19. Line power of wind farm without FLARA-incorporated ECS.


Fig. 16. Rotor speed of PMSG.

Fig. 17. Power reference of PMSG-side converter using MPPT. Fig. 20. Line power of wind farm with FLARA-incorporated ECS.

time step and simulation time have been chosen to be 0.00002 EDLC bank without and with adopting FLARA are shown in
and 600 s, respectively. It is important to note here that the Figs. 21 and 22, respectively. Responses of the dc-link voltage
parameters of the PI controller for all simulation cases are de- of ECS and terminal voltage of the wind farm (i.e., terminal
termined by the trial-and-error approach in order to obtain the voltage at the high voltage side of the transformer located after
best performance. The simulations have been performed by us- the grid-side inverter) without and with adopting the reference
ing PSCAD/EMTDC [31]. adjuster are shown in Figs. 23 and 24, respectively. FLARA
Responses of the wind farm output power (i.e., real power output is shown in Fig. 25. The real and reactive powers of ECS
output from the grid-side inverter of VSWT-PMSG), rotor speed are shown together in Fig. 26.
of PMSG, power reference of PMSG-side converter calculated The response of the EDLC current during charge and dis-
using MPPT, and dc-link voltage of the frequency converter are charge is shown in Fig. 27. To realize the EDLC characteristic
shown in Figs. 15, 16, 17, and 18, respectively. Responses of precisely, it is considered in the simulation that the energy dis-
wind farm output power controlled by ECS without and with charge is not possible when the terminal voltage of EDLC goes
adopting FLARA are shown in Figs. 19 and 20, respectively. below 20% of its rating. If the energy discharge is not possible
Responses of the stored energy and terminal voltage of the during the low EDLC voltage, the unwanted voltage spike can
MUYEEN et al.: INTEGRATION OF AN ENERGY CAPACITOR SYSTEM WITH A VARIABLE-SPEED WIND GENERATOR 747

Fig. 25. Output of FLARA (i.e., multiplying factor).


Fig. 21. Stored energy of the EDLC bank.

Fig. 22. Terminal voltage of the EDLC bank. Fig. 26. Real and reactive powers of ECS incorporating FLARA.

Fig. 23. DC-link voltage of ECS. Fig. 27. Current of the EDLC bank incorporating FLARA.

Fig. 24. Terminal voltage of the wind farm. Fig. 28. Frequency spectrum of the line power.
748 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 24, NO. 3, SEPTEMBER 2009

be expected, as can be seen from Figs. 21–24. In the case of using STATCOM/ESS,” in Proc. IEEE PowerTech. 2007 Conf., Lausanne,
without FLARA, the EDLC voltage drops to 20% of its rating Switzerland, Jul., pp. 1232–1237, Paper 258.
[12] M. Okamura, “A basic study on power storage capacitor system,” (in
as more energy is needed to discharge. On the other hand, the Japanese), IEEJ Trans. Power Energy, vol. 115-B, pp. 504–510, 1995.
FLARA-incorporated ECS can efficiently use the stored energy [13] R. L. Spyker and R. M. Nelms, “Optimization of double-layer capacitor
of the EDLC bank during its high- and low-energy stages, thus arrays,” IEEE Trans. Ind. Appl., vol. 36, no. 1, pp. 194–198, Jan./Feb.
2000.
overcoming the situations of full charge and overdischarge of [14] Y. Nozaki, K. Akiyama, H. Kawaguchi, and K. Kurokawa, “An improved
the EDLC bank, and can augment the performance of the over- method for controlling an EDLC-battery hybrid stand-alone photovoltaic
all system, without deteriorating the line power smoothness, as power system,” in Proc. Appl. Power Electron. Conf. Expo. (APEC 2000),
vol. 2, pp. 781–786.
shown in Fig. 28. [15] Y. Jia, R. Shibata, N. Yamamura, and M. Ishida, “A control method of
prolonging the service life of battery in stand-alone renewable energy
system using electric double layer capacitor (EDLC),” in Proc. Power
VII. CONCLUSION Electron. Drives Syst. (PEDS 2005), vol. 1, pp. 228–233.
[16] S. Sugimoto, I. Kouda, and Y. Murai, “Energy storage system utiliz-
In this paper, an ECS has been proposed to smoothen the line ing large capacity electric double-layer capacitors for peak-cut of power
power fluctuation of a wind farm composed of variable-speed demand,” (in Japanese), IEEJ Trans., vol. 118-D, pp. 1377–1385,
permanent-magnet generators. First, the operation and control 1998.
[17] T. Muto, “Development technology of the instantaneous voltage sag
strategies of a VSWT driving a PMSG and frequency converters compensator apply large-capacity electric double-layer capacitor,” (in
have been presented. Then, the cost-effective topology of ECS, Japanese), Electron Technol., vol. 44, no. 11, pp. 52–58, 2000.
which is composed of a CC-VSI, dc–dc buck/boost converter, [18] G. Ariyoshi, K. Murata, K. Harada, and K. Yamasaki, “Load levelling
using EDLCs under PLL control,” IEICE Trans. Fund., vol. E83-A,
and an EDLC bank, and is suitable for the integration with no. 6, pp. 1014–1022, 2000.
a PMSG wind farm, has been proposed. The detailed control [19] L. Zubieta and R. Bonert, “Characterization of double-layer capacitors for
strategy of the ECS has also been demonstrated. A fuzzy-logic- power electronics applications,” IEEE Trans. Ind. Appl., vol. 36, no. 1,
pp. 199–205, Jan. 2000.
controlled reference adjuster is proposed in the control of the [20] T. Kinjo, T. Senjyu, N. Urasaki, and H. Fujita, “Output levelling of renew-
dc–dc buck/boost converter, which can reduce the cost of ECS able energy by electric double-layer capacitor applied for energy storage
but still keep the size of the energy storage system small, as well system,” IEEE Trans. Energy Convers., vol. 21, no. 1, pp. 221–227,
2006.
as enhance the control ability of the overall system. Finally, it [21] S. M. Muyeen, S. Shishido, M. H. Ali, R. Takahashi, T. Murata, and
has been reported that the proposed ECS can smoothen well the J. Tamura, “Application of energy capacitor system (ECS) to wind power
power fluctuation of the variable-speed wind farm. generation,” Wind Energy, vol. 11, no. 4, pp. 335–350, Jul./Aug. 2008.
[22] P. Vas, Electrical Machines and Drives—A Space Vector Theory Approach.
New York: Oxford Univ. Press, 1992.
REFERENCES [23] T. J. E. Miller, Brushless Permanent-Magnet and Reluctance Motor
Drives. New York: Oxford Univ. Press, 1989.
[1] The Global Wind Energy Council, GWEC Latest News. (2008, Feb.). US, [24] J. Ribrant and L. M. Bertling, “Survey of failures in wind power systems
China & Spain lead world wind power market in 2007 [Online]. Available: with focus on Swedish wind power plants during 1997–2005,” IEEE
http://www.gwec.net/ Trans. Energy Convers., vol. 22, no. 1, pp. 167–173, Mar. 2007.
[2] T. Senjyu, R. Sakamoto, N. Urasaki, T. Funabashi, H. Fujita, and H. Sekine, [25] S. M. Muyeen, T. Murata, and J. Tamura, Stability Augmentation of a Grid-
“Output power leveling of wind turbine generator for all operating regions Connected Wind Farm. London, U.K.: Springer-Verlag, Oct. 2008.
by pitch angle control,” IEEE Trans. Energy Convers., vol. 21, no. 2, [26] F. V. Hulle, “Large scale integration of wind energy in the European power
pp. 467–475, Jun. 2006. supply analysis, issue and recommendations,” Eur. Wind Energy Assoc.
[3] S. M. Muyeen, M. H. Ali, R. Takahashi, T. Murata, and J. Tamura, “Wind (EWEA), Brussels, Belgium, Tech. Rep., Dec. 2005.
generator output power smoothing by using pitch controller,” Int. Rev. [27] K. Ushiwata, S. Shishido, R. Takahashi, T. Murata, J. Tamura,
Electr. Eng., vol. 2, no. 3, pp. 310–321, Jun. 2007. M. Sugimasa, A. Komura, M. Futami, M. Ichinose, and K. Ide, “Smooth-
[4] F. Hardan, J. A. M Bleijs, R. Jones, P. Bromley, and A. J. Ruddell, “Appli- ing control of wind generator output fluctuation by using electric double
cation of a power-controlled flywheel drive for wind power conditioning in layer capacitor,” in Proc. Int. Conf. Electr. Mach. Systems (ICEMS 2007),
a wind/diesel power system,” in Proc. 9th Int. Conf. Electr. Mach. Drives, Seoul, Korea, Oct., pp. 308–313.
1999, pp. 65–70, Paper 468. [28] S. Heier, Grid Integration of Wind Energy Conversion System.
[5] R. Takahashi, Wu. Li, T. Murata, and J. Tamura, “An application of fly- Chicester, U.K: Wiley, 1998.
wheel energy storage system for wind energy conversion,” in Proc. Int. [29] S. M. Muyeen, R. Takahashi, T. Murata, J. Tamura, and M. H. Ali, “Tran-
Conf. Power Electron. Drives Syst. (PEDS 2005), Nov., pp. 932–937. sient stability analysis of permanent magnet variable speed synchronous
[6] R. Cardenas, R. Pena, G. Asher, and J. Clare, “Power smoothing in wind wind generator,” in Proc. Int. Conf. Electr. Mach. Syst. (ICEMS 2007),
generation systems using a sensorless vector controlled induction machine Seoul, Korea, Oct., pp. 288–293.
driving a flywheel,” IEEE Trans. Energy Convers., vol. 19, no. 1, pp. 206– [30] J. G. Slootweg, S. W. H. De Hann, H. Polinder, and W. L. Kling, “General
216, Mar. 2004. model for representing variable speed wind turbines in power system
[7] S. Nomura, Y. Ohata, T. Hagita, H. Tsutsui, S. Tsuji-Iio, and R. Shimada, dynamic simulations,” IEEE Trans. Power Syst., vol. 18, no. 1, pp. 144–
“Wind farms linked by SMES systems,” IEEE Trans. Appl. Supercond., 151, Feb. 2003.
vol. 15, no. 2, pp. 1951–1954, Jun. 2005. [31] PSCAD/EMTDC Manual, Manitoba HVDC Research Center, Winnipeg
[8] F. Zhou, G. Joos, C. Abbey, L. Jiao, and B. T. Ooi, “Use of large capacity MB, Canada, Apr. 2005.
SMES to improve the power quality and stability of wind farms,” in Proc. [32] A. M. Gole, I. T. Fernando, G. D. Irwin, and O. B. Nayak, “Modeling of
IEEE Power Eng. Soc. Gen. Meeting, Jun., 2004, vol. 2, pp. 2025–2030. power electronic apparatus: Additional interpolation issues,” in Proc. Int.
[9] M. H. Ali, T. Murata, and J. Tamura, “Minimization of fluctuations of line Conf. Power Syst. Transients (IPST), Seattle, WA, Jun.1997, pp. 23–28.
power and terminal voltage of wind generator by fuzzy logic-controlled [33] L. Salazar and G. Joos, “PSPICE simulation of three-phase inverters by
SMES,” Int. Rev. Electr. Eng., vol. 1, no. 4, pp. 559–566, Oct. 2006. means of switching functions,” IEEE Trans. Power Electron., vol. 9, no. 1,
[10] M. EL Mokadem, C. Nichita, P. Reghem, and B. Dakyo, “Wind diesel pp. 35–42, Jan. 1994.
system for DC bus coupling with battery and flywheel storage,” presented [34] Z. Chen and E. Spooner, “Grid power quality with variable speed wind
at the XVII Int. Conf. Electr. Mach. (ICEM 2006), Chania, Greece, Paper turbines,” IEEE Trans. Energy Convers., vol. 16, no. 2, pp. 148–154, Jun.
ID 699. 2001.
[11] S. M. Muyeen, M. H. Ali, R. Takahashi, T. Murata, and J. Tamura, “Wind [35] D. Driankov, H. Hellendoorn, and M. Reinfrank, An Introduction to Fuzzy
generator output power smoothing and terminal voltage regulation by Control. Berlin, Germany: Springer-Verlag, 1993.
MUYEEN et al.: INTEGRATION OF AN ENERGY CAPACITOR SYSTEM WITH A VARIABLE-SPEED WIND GENERATOR 749

S. M. Muyeen (M’08) was born in Khulna, Toshiaki Murata completed the Electrical Engi-
Bangladesh, on September 8, 1975. He received neering Curriculum of the Teacher Training School
the B.Sc. Eng. degree from Rajshahi University from Hokkaido University, Sapporo, Japan, and re-
of Engineering and Technology (RUET), Rajshahi, ceived the Dr. Eng. degree from Hokkaido University,
Bangladesh, in 2000, and the M.Sc. Eng. and Dr. Sapporo, Japan, in 1991.
Eng. degrees from Kitami Institute of Technology, Since 1969, he has been a Research Assistant at
Kitami, Japan, in 2005 and 2008, respectively, all in Kitami Institute of Technology, Kitami, Japan, where
electrical and electronic engineering. he is currently an Associate Professor.
He is currently the Japan Society for the Promotion
of Science Postdoctoral Fellow at Kitami Institute
of Technology. His current research interests include
power system, electrical machine, flexible ac transmission system, energy stor-
age system, wind generator stabilization, and multimass drive train of wind
turbine.

Rion Takahashi (M’07) received the B.Sc. Eng. and Junji Tamura (M’87–SM’92) received the B.Sc.
Dr. Eng. degrees in electrical and electronic engi- Eng. degree from Muroran Institute of Technology,
neering from Kitami Institute of Technology, Kitami, Muroran, Japan, in 1979, and the M.Sc. Eng. and
Japan, in 1998 and 2006, respectively. Dr. Eng. degrees from Hokkaido University, Sapporo,
He is currently a Research Assistant with the De- Japan, in 1981 and 1984, respectively, all in electrical
partment of Electrical and Electronic Engineering, engineering.
Kitami Institute of Technology. His current research In 1984, he became a Lecturer at Kitami Insti-
interests include analysis of power system transient, tute of Technology, Kitami, Japan, where he became
flexible ac transmission system, and wind energy con- an Associate Professor in 1986, and is currently a
version system. Professor.

You might also like