Sept. 21 – V 2.

2 A Sofrel Sensors CNPR/CPR, CNPI, CNPA


Level and pressure measurement

1. Presentation
CNPR
Connectable: Measurement of drinking water pressure
(pipes, etc.)
- CNPR range: 0 to 16 bar
- ¼ inch cylindrical gas connection
DIN 3852 with watertight connector
tightened using ∅ 27mm key
- Measurement of clean water pressure
- Accuracy: +/- 0.35% FSO (according to IEC 60770)
- Inbuilt surge protection
- Watertightness: IP68
- Surge resistance: 60 bar
- Optimised power consumption: -30%
CPR
Connectable: Drinking water pressure measurement
(pipes, etc.)
- CPR range: 10 or 20 bar
- ¼ inch cylindrical gas connection
DIN 3852 with watertight connector
tightened using ∅ 24mm key
- Measurement accuracy: 0.5% FSO (according to IEC 60770)
- Inbuilt surge protection
- Watertightness: IP68
- Surge resistance: 60 bar
- Optimised power consumption: -30%

CNPI
Submersible: Measures level of clean water
(reservoirs, drill holes, etc.)
- Stainless steel case
- Remotely powered 4-20 mA two-wire link
- Range: 6m, or 9m (or made to measure)
- Accuracy: +/- 0.35% FSO (according to IEC 60770)
- Inbuilt surge protection
- ACS Certification
- Highly sensitive steel sensor: any contact with other objects or
even your finger may cause damage. Do not under any
circumstances remove the black cover.
CNPA
Submersible: Measures sewage levels
- Stainless steel case
- Remotely powered 4-20 mA two-wire link
- Range: 3m, or 6m (or made to measure)
- Accuracy: +/- 0.35% FSO (according to IEC 60770)
- Inbuilt surge protection
- Suitable for wastewater or sewage
(ceramic sensor, cleaning)
- Optimised power consumption
- The sensor is delivered with a black cover; when used with
sewage, this cover must be removed before use.

Level and pressure measurement


2. RTUs S500 / S4 Connections
All Sofrel sensors come with inbuilt surge protection. However, of the distance between the
Remote Terminal Unit and the sensor exceeds 200m, then a 4-20mA surge protector
must be fitted to prevent damage to the sensor.

AI board

Protects remote terminal unit


from surges

Shielded cable

Sensor protection for


distances > 200m

Installing the CNPA sensor in a pipe


(specifically for Lift Stations)

Anchoring clamp
to attach the cable
(∅ 5.5mm to 10.5mm)
Surge tube
∅ between 100mm
and 125mm
Lift Station

The tube must not Sofrel CNP


rest on the bottom of
the Station. CNPA Sensor Sensor

Any sensor that was used with waste water and needs to be
shipped must include a cleaning and disinfection certificate,
otherwise the package will remain unopened.

Level and pressure measurement


3. Data Loggers Connections

LS/LT

CPR/CNPR

Watertight connection between sensor and LS/LT Data Logger

CNPR / CPR CNPI / CNPA

 Use 2PE-5C kit:  Use 4PE-8C kit:


Capillary outside connector
LS/LT Cable CNP in non-immersed areas
LS/LT Cable

Capillary inside CNP


connector

The end of the capillary must be protected by the The end of the capillary should never be immersed. The height
watertight connection. Pressure measurement is an of water is measured relative to the atmospheric pressure.
absolute pressure measurement.

Level and pressure measurement