DUCT SLEEVE AND

WALL FLASHING WITH


SEALANT ALL AROUND

METAL CLADDING

DUCT WITH INSULATION

300MM

DUCT RISER

NOTES:
1. FOR ROOF CONSTRUCTION AND FLASHING & COUNTERFLASHING
DETAIL, REFER TO ARCHITECTURAL DRAWING.

DUCT PENETRATION THROUGH ROOF

4 SUPPLY & EXHAUST DUCT BRANCHING. 5 DUCT THRU WALL. 6 DUCT PENETRATION THROUGH ROOF
SCHEDUILE&DETAILS
N.T.S. SCHEDUILE&DETAILS
N.T.S. SCHEDUILE&DETAILS
N.T.S. 7 AIR DUCT INSULATION DETAIL( INDOOR , OUTDOOR(M30)
SCHEDUILE&DETAILS
N.T.S.

SINGLE INLET FAN DOUBLE INLET FAN


E NOTE "3"

E C

E E C

F
NOTES 1+2 NOTES 1+2
PLAN VIEW PLAN VIEW PLAN VIEW

E
TYPICAL FLExIBLE
CONNECTION

E NOTE "3"
ELEVATION VIEW ELEVATION VIEW ELEVATION VIEW

DIMENSIONS:
C=DIAMETER OF FAN INLET E=45° MAxIMUM 30° PREFERRED
D=1 1/4 x C F=36" MINIMUM FOR ACCESS DOOR

INLET CONNECTIONS
GOOD GOOD FAIR
BEST
B NOTE 4
NOTE 5
R1
A
A

A B
A

TRANSFORMATION 1" IN 7" PREFERED.


1" IN 4" PERMITTED NOTE 6 & 7.
B B
DIMENSIONS:
A=1 1/2 x B TO 2 1/2 x B
B= FAN DISCHARGE OPENING.
LARGEST DIMENSION.
DISCHARGE CONNECTIONS
NOTES:
1- FAN SHOULD BE CENTERED IN CASING TO PROVIDE GOOD FLOW CONDITIONS.
2- ALL EQUIPMENT SHOULD BE CENTERED FOR BEST PERFORMANCE.
3- ANGLE "E" IS USED TO DETERMINE "F" DISTANCE BETWEEN EQUIPMENT AND FAN.
4- R1=6" MINIMUM.
5- USE SQUARE VANED ELBOW FOR BEST RESULTS, WITH TAKE-OFF IN OPPOSITE ,
DIRECTION TO FAN ROTATION.
6- SLOPE OF 1" IN 4" RECOMMENDED FOR LOW VELOCITY.
7- SLOPE 1" IN 7" RECOMMENDED FOR HIGH VELOCITY.

7 WALL MOUNTED EXHAUST AXIAL FAN


3 IN-LINE TYPE FAN INSTALLATION
1 FAN INLET AND DISCHARGE CONNECTIONS SCHEDUILE&DETAILS
N.T.S.
SCHEDUILE&DETAILS
N.T.S. SCHEDUILE&DETAILS
N.T.S.

7 ROOF TOP EXTRACT FAN. WITH OFFSET ON ROOF. 7 DETAILS OF FIRE AND SMOKE DAMPER. 8 VERTICAL SMOKE/FIRE DAMPER FOR DUCTS
SCHEDUILE&DETAILS SCHEDUILE&DETAILS
N.T.S.
N.T.S. SCHEDUILE&DETAILS
N.T.S.

10 INSTALLATION DETAIL FOR PACKAGE A/C UNIT 11 EQUIPMENT BASE DETAIL


SCHEDUILE&DETAILS
N.T.S. SCHEDUILE&DETAILS
N.T.S.