Professional Documents
Culture Documents
Basics of Power Cables
Basics of Power Cables
(1)It is strictly forbidden to bind the power cord with metal wires (such as lead wires)
(2)Do not use wet hands to touch switches, sockets and electrical equipment with metal shells,
and do not wipe the above-mentioned electrical appliances with a damp cloth.
(3)It is strictly forbidden to place clothing on the motor and various electrical equipment,
do not sit or stand on the motor, and do not hang rain gear on top of the motor or
electrical equipment.
(4) During thunderstorms, do not approach the grounding conductors of high-voltage poles,
iron towers and lightning rods to prevent thunder and lightning from hurting people.
Do not approach high-voltage wires that have fallen on the ground
(5) Motors that are prone to overload, may fail to start due to serious starting or
self-starting conditions, or need to limit the starting time, overload protection should be installed.
(6) The current carrying capacity of the wire is slightly larger than the current of the circuit breaker.
Only in this way can it be ensured that the circuit breaker can provide overload protection
for the wire.
2. Basic knowledge:
﹡ A good power distribution design should be able to ensure that the current flowing through the
circuit conductor cannot exceed its safe current carrying capacity.
There are generally the following two situations when the current flowing in the circuit conductor
exceeds the safe current carrying capacity
(1) Overload:
The power consumption of the load connected to the circuit has exceeded its
safe current carrying capacity.
1. Fuse, is made of low melting point alloy and connected in series. When overload or short circuit
occurs, it can be blown by the heat generated by overcurrent. It is suitable for small current
capacity.
2. Circuit Breaker (CB) is a kind of switch, in addition to manual operation, opening and
closing the circuit, when an overload or short circuit occurs, it can also automatically cut off the
circuit.
1P 50AF 15AT
2P 50AF 15AT
3P 100AF 50AT
圖片來源:富士 F102B,75A,10kA,熱動+電磁式
3. The starting current of the motor is generally about 5 to 8 times the load current.
From the time-current curve TCC, the motor must be started within 3 seconds and run normally,
otherwise the MCCB will trip and disconnect the power supply.
4. Considering that the starting current of Y-Δ step-down voltage is the starting current / √ 3,
the starting time can be extended to about 10 seconds.
3 P For 3∮4W
圖片來源:士林電機
No Fuse Breaker
The non-fuse switch is also referred to as NFB, which is a kind of overcurrent protection circuit breaker.
The main specifications of the router are the number of poles (Pole), frame current (Frame
Current), rated current (Rate Current), breaking capacity (Interrupting Capacity) and so on.
1.Number of poles P:
The number of contact groups of the protection device, that is, the number of lines that
can be opened or closed at the same time. It is usually represented by "P". 1P means a
single set of contacts, and only one wire can be opened and disconnected, and 2P
means two Group contacts, can open and break two wires at the same time, 3P means
three sets of contacts, can open and break three wires at the same time, and so on.
the current ampere that the frame contact of the protection device can withstand, unit A,
abbreviated as AF, frame capacity AF must be greater than the rated current AT. Motor
dedicated AF is above 150.
Theoretically, the IC value only needs to be greater than the maximum asymmetric fault current, but if
the IC is too close to the fault current, the IC value (± 5KA) must be used. For example, if the fault
current is 34.9 KA, the IC value will be 40 KA. Instead of 35 KA
Allowable
Types of insulated wires Remark
temperature ℃
1.PVC wire
60
2.RB wire(指天然橡膠之混合絕緣物)
4.PE wire(POLYETHYLENE) 75
6.人造橡膠電線(BUTYL RUBBER) 80
Cable Size in (Sq. mm) Single Core Two Core Three/Four Core
1 17 13.5 9
2.5 30 24 21
4 40 32 28
6 51 41 36
10 69 57 50
16 91 76 68
25 119 101 89
Cable Size in (Sq. mm) Single Core Two Core Three/Four Core
4 16 13 11
6 20 16 14
10 25 22 19
16 35 31 28
25 43 41 36
35 65 59 52
50 80 71 63
70 91 80 71
﹡Choose the size of the conductor wire diameter, except that it should be able to withstand the rated
current of the motor 1.25 times the flow
﹡When the switch or circuit breaker is installed in damp or outdoors, its protective enclosure should
be of waterproof type.
﹡The maximum load of the branch shall be handled in accordance with the following regulations:
1. The load supplied by the branch should not exceed the rated capacity of the branch.
2. If the branch is simultaneously supplied with 1/8 horsepower or more fixed motor driving equipment
and other loads, the load calculation should be calculated as the sum of 1.25 times the maximum
motor load plus other loads
a b contact
When the MC itself is not activated (the excitation coil is not energized or manual pressing is not used),
the contact is open; when the MC is activated (the excitation coil is energized or manually pressed), the
contact is in the open state; it returns to the MC (The excitation coil is de-energized or the press is
released), the contact returns to its original open circuit state.
1. The voltage level of the AC contactor must be the same as that of the load, and the type of
contactor selected must be compatible with the load.
2. It is necessary to consider the length of the line connected to the control circuit of the contactor.
Generally, the recommended operating voltage value of the contactor should be able to work at
85-110% of the rated voltage value.
3. The calculated current of the load must conform to the capacity level of the contactor, that is,
the calculated current is less than or equal to the rated working current of the contactor. The
making current of the contactor is greater than the starting current of the load.
When a thermal relay is used to protect a motor in a long-term working system or an intermittent long-
term working system, it is generally selected according to the rated current of the motor. For example,
the setting value of the thermal relay can be equal to 0.95~1.05 times the rated current of the motor,
or the median value of the setting current of the thermal relay can be equal to the rated current of the
motor, and then adjust.
Function
Thermal relays are generally used in conjunction with contactors for motor control circuits. When the
thermal relays heat up, their normally closed point will disconnect the contactor coil control power
supply, so that the contactor will be de-energized and disconnected, stopping the main circuit power
supply to protect the motor.
Leakage circuit breakers
Leakage circuit breaker is an electrical safety device that can automatically trip off the power supply in
an instant to protect electrical equipment from small electrical leakages to prevent electric shocks,
equipment burns, and fires.
In terms of design, it has a permanent fixed type and a movable type. It is classified according to the
principle of tripping and power failure. It can be divided into voltage type and current type. Generally,
the current type is mainly used, and the current type is automatically tripped. The electric current is
less than 0.03 ampere, the action time is less than 0.1 second, the voltage type tripping off voltage is
less than 30V, and the action time is less than 0.2 second.
Places/equipment recommended to install/use leakage circuit breakers include: small hand machine
tools, laboratory electrical equipment, equipment for operating or handling flammable materials,
swimming pool underwater lighting equipment, fish farming/irrigation electricity, water dispensers,
water heaters , Bathroom sockets, construction site electricity, temporary electricity, floor washing and
waxing machines (purchase extension cords with leakage circuit breaker sockets), etc....
Single phase
Three-phase
Generally, the safe cut-off capacity of copper wire is 5-8A/mm2, and the safe cut-off capacity of
aluminum wire is 3-5A/mm2.
In a single-phase 220V line, the current per 1KW power is about 5A, and in a three-phase load-balanced
three-phase circuit, the current per 1KW power is about 3.3A.
in a three-phase load-380V, three-phase circuit, the current per 1KW power is about 3.3A.
That is to say, in a single-phase circuit, every 1 square millimeter of copper wire can withstand a power
load of 1KW; a three-phase balanced circuit can withstand a power of 2-2.5KW.
But the larger the working current of the cable, the smaller the safe current per square millimeter can
withstand.
Ex.1. Knowing 380V three-phase motor with a capacity of 5kw, find its current.
A: amps=5000/1.732*380*0.9=8.44 amps
﹡Measuring method of grounding resistance of grounding wire
-Twenty meters from the ground wire, a steel drill is inserted into the ground.
-Go forward in a straight line, and then touch the ground twenty miles away.
-E end is connected to the line to be tested, P and C are each connected to a steel braze。
-Level the meter to adjust the zero, and the pointer just points to the red line.
-Slowly shake the handle scheduling board, the pointer red line is adjusted.
-When the galvanometer indicates balance, the acceleration reaches two hundred revolutions.
-The adjustment dial refers to the red line, and write down the resistance to judge.
▲摇表
3-phase 380V, cooling capacity 32kW, power consumption 8.9kW, Power factor 0.8,
A=8900W/(1.732*380*0.8)=16.9A
➟3-phase 380V air conditioner, rated current 16.9A, ampere capacity of wire from
main distribution box to indoor unit