Souad Chebbi
Laboratory of Technologies
of Information and Communication &
Electrical Engineering (LaTICE)
ENSIT, University of Tunis, Tunisia
souad.chebbi@yahoo.com
Abstract— This paper presented UPFC and SVC control for capacitor banks can improve voltage stability, but they are
effective power system stability. The purpose of this work is to unable to provide good performance during rapid changes in
study the contribution of FACTS devices to damp the fluctuation reactive power [4].
of voltage under fault condition. The simulation results are Despite proven technologies and practices for power
applied to the IEEE 14-bus test system, and show that including
system security enhancement, this problem remains a sensitive
UPFC and SVC improves the accuracy of voltage stability of
power system. The case study is performed using the well-known
issue, and more efforts are then required to guarantee the
software EUROSTAG. stability of the system. Flexible AC transmission system
(FACTS) devices are among the solutions considered for
Keywords— EUROSTAG, UPFC, SVC, voltage stability.
dealing with power system stability problems. There are
I. INTRODUCTION various forms of FACTS devices. Based on power
electronics, the FACTS are used to increase the controllability
P ower systems were generally operated under stressed
conditions, closer to their stability limits. This is due to the
increasing power demand and, at the same time, the economic
and the power transfer capacity of the network, they are
characterized by a very short response time and offer a better
flexibility of regulation and control [5, 6].
constraints imposed on the electricity production. Moreover,
In [7], the authors proposed the UPFC and the IPFC
the power flow transmitted by the transmission lines must be
(Interline Power Flow Controller), in order to sustain the
limited for stability reasons. Therefore, in the event of an voltage stability of power systems. In [8], they outlined the
unforeseen fault, the power flow can exceed the limits causing importance of the integration of different FACTS such as
system collapse [1]. UPFC and SVC in improving power system stability.
Voltage stability is one of the main concerns of the Likewise, the UPFC as a controllable shunt compensation
network managers and is also considered as one of the most provides an effective power flow control and a good voltage
complex studies. It concerns the ability of the system to control [9].
maintain all its buses voltage within the permissible limits, In this paper, we will specify the contingencies that create a
after being disturbed. In fact, voltage fluctuations have caused fault and their effect on the voltage stability of the power
major incidents (blackouts) that have occurred all over the system. In addition, a corrective control using Facts devices
world [2]. The long interruptions of the electricity service for improving the voltage stability of a test system is
cause the shutdown of the communication systems, the performed using the pioneering EUROSTAG software
distribution of water, the transport, etc. In addition, even the package [10].
short-term electricity cuts, can significantly affect industrial
processes [3].
The voltage collapse is highly related to the lack of II. CONTRIBUTION OF FACTS DEVICES ON THE
reactive power. Therefore, it is essential to always satisfy the IMPROVEMENT OF POWER SYSTEM STABILITY
demand for reactive energy. However, the reactive power FACTS devices have been employed for improving the
transit causes voltage drops. Thus, it is necessary to proceed power system stability, flexible power flow control and
with the reactive power compensation. Conventional means as increasing transmission system reliability and availability.
Authorized licensed use limited to: CINVESTAV. Downloaded on October 18,2022 at 22:10:27 UTC from IEEE Xplore. Restrictions apply.
2020 4th International Conference on Advanced Systems and Emergent Technologies (IC_ASET)
Therefore, they have a stronger capability of power transfer, manner, increasing therefore the power flow control
avoiding cascading outages and damping oscillations [11, 12]. flexibility.
Vse V2
FACTS
V1
Serie
Serie Shunt Hybrid Shunt
Transformer Transformer
TCSR
TCR TSC Fig.3. Model of UPFC
14
13
12
11
10
6
C 9
G1 8
7
C L 1 C
5
4
258
Authorized licensed use limited to: CINVESTAV. Downloaded on October 18,2022 at 22:10:27 UTC from IEEE Xplore. Restrictions apply.
2020 4th International Conference on Advanced Systems and Emergent Technologies (IC_ASET)
phase fault at bus 14 and the total even load increase by 25%,
without any modification to the network configuration. We
will connect SVC at bus 9 and UPFC between the two buses 1
and 2. Power dimension of SVC is ± 60 MVAR. UPFC sized
to ± 200 MVAR.
Here are the results characterizing the evolution of
electrical network during transient state with and without the
addition of FACTS.
1) First Scenario: Three-phase fault at bus 14:
Consider the disturbance with a bolted three-phase fault
during 100ms at bus 14. A direct short circuit in the system
may cause the voltage drop that can continue until reaching
the minimum permissible. On fault clearance, voltage returns
to its initial value after a few well damped oscillations. Fig. 5
depicts the temporal evolution of voltage at bus 2. Despite the
presence of SVC, the voltage at bus 2 has a slight
improvement which is due to its location. However, with
UPFC the evolution of voltage magnitude is well damped.
259
Authorized licensed use limited to: CINVESTAV. Downloaded on October 18,2022 at 22:10:27 UTC from IEEE Xplore. Restrictions apply.
2020 4th International Conference on Advanced Systems and Emergent Technologies (IC_ASET)
REFERENCES
[1] P.Kundur, “Power system stability and control,” McGraw-Hill,Inc
1993.
[2] K. Alcheikh-Hamoud, “Modeling of large interconnected power
Fig.8. Voltage magnitude at bus 14 with and without FACTS systems: application to the safety analysis in a competitive
environment,” Phd. Engineering Sciences. Institut National
Polytechnique de Grenoble - INPG, 2010.
2) Second Scenario: 25%-Load increase on the system: [3] Meddeb, A., Jmii, H. and Chebbi, S. ‘Operation state classification of
Based on the results obtained from the short circuit at bus 14, power system using fuzzy logic techniques’, Int. J. Process Systems
we simulate the 25% even increase. Fig. 9 illustrates the Engineering, Vol. 5, No. 1, 2019.
[4] B. Özkaya, M. Döúo÷lu, U. Güvenç, O. Bingöl, “Static Voltage Stability
temporal evolution of voltages at bus 1 with and without Improvement using TCSC during Transient State in Power System,”
FACTS. When the load increases, a considerable voltage drop International Conferences on Science and Technology Engineering
took place at different buses. For instance, the voltage at node Science and Technology ICONST EST, PRIZREN KOSOVO, August
2019.
9 will drop from 0. 04pu and regain a value of 0.935pu
[5] A. Meddeb, N. Amor, M. Abbes, and S. Chebbi, “New Meta-heuristic
without the presence of FACTS. The system presents the same Approach for solving Reactive Power Dispatch Problem: A Case Study
voltage profile even with the presence of SVC. According to of the Tunisian Power Transmission System”, Energies, 2018, 11, 3321.
the integration of UPFC, the voltage reaches the value of [6] Singh, A. and Uddin Ahmad, A. ‘Control Reactive Power Flow with
UPFC Connected Using Different Distance Transmission Line’,
0.98pu with good damping of the oscillations. Furthermore, it Copyright to IJAREEIE DOI: 10.15662/IJAREEIE, 0409034,2015.
is difficult to improve network stability in the presence of a [7] S. Inkollu,V. Kota, “ Optimal setting of FACTS devices for voltage
single SVC. It has been observed that the system with UPFC stability improvement using PSO adaptive GSA hybrid algorithm,”
Engineering Science and Technology, an International Journal, Vol. 19,
is the better. The UPFC, independently, controls the voltage, Issue 3, pp. 1166-1176, September 2016.
the real and reactive power of the network. [8] A Siddique, Y. Xu, W. Aslam, M. Rasheed, “A Comprehensive Study
Finally, we note that when the fault is cleared, SVC action on FACTS Devices to Improve the Stability and Power Flow Capability
is not very significant for stability improvement and in Power System,” The Asia Power and Energy Engineering
Conference, 2019.
oscillations damping. Nevertheless, the UPFC achieves an [9] Raja Slochanal SM, Latha S, Chithiravelu, KA, “Novel approach of
effective damping. power flow analysis incorporating UPFC”, The 7th international power
engineering conference, vol.29(2), pp. 1-4, 2005
[10] Eurostag, Eurostag Software Release Notes, Tractebel-EDF, Release
5.1, Dec 2010
[11] Berrouk, F., Rachedi, B.A., Lemzadmi, A. Bounaya, K. and Zeghache,
H. (2014) ‘Applications of shunt FACTS controller for voltage stability
improvement’, International Conference on Electrical Sciences and
Technologies in Maghreb (CISTEM), November.
[12] Sharaf, A.M and Abdelsalam, A.A. (2011) ‘A novel facts based
dynamic voltage compensation scheme for smart electric grid
stabilization and efficient utilization’, Electrical and Computer
Engineering (CCECE), 24TH Canadian Conference.
[13] Bevrani, H. (2009) ‘Robust Power System Frequency Control’, ISBN
978-0-387-84877-8, Springer Science + Business Media, LLC.
[14] Biswas, P. (2012) ‘The Influence of Thyristor Controlled Phase Shifting
Transformer on Balance Fault Analysis’, International Journal of
Modern Engineering Research (IJMER), www.ijmer.com Vol.2, Issue.4,
July-Aug.
[15] Y. Sunday, J. Boyi, O. Ubeh, A. Saidu, M. Onimisi, “Transmission Line
Capacity Enhancement with Unified Power Flow Controller
Fig.9. Voltage magnitude at bus 1 with and without FACTS Considering Loadability Analysis,” ELEKTRIKA Journal o Electrical
Engineering, vol. 18, n°3, pp. 8-12, 2019.
[16] B. Liu, F. Liu, B. Zhai, H. Lan, “Investigating Continuous Power Flow
Solutions of IEEE 14-Bus System,” IEEJ trans. on electrical and
IV. CONCLUSION electronic engineering, vol.14, pp.157- 159, 2019.
A voltage stability improvement using FACTS devices
such as the UPFC and SVC has been proposed in this paper.