ISO Standard Power (as per ISO 3046-1) of engine,(obtained after deducting power loss due to essential dependent auxiliaries )
P 126.00 kW 1. 61565G Engine Rated Power is 114.8 kW ± 5 %
iso 1 2. ConsideringPrimePower Requirement of 125 kVA (i.e. Max. kVA Rating) 3. Engine Max. Power at 110 % Load is 126kw ± 5 % kW 4. For Calculation 110 % Load Mean Engine Power Value is considered however it will have ± 5 % Tolerance Deration on account of site conditions (refer datasheet for ambient conditions)as per ISO 3046 -1 Temperature (around the engine & alternator) 1.76 kW Considered 350 Meter altitude & Ambient temp. 51°C as per detail shared (Deration Factor 0.958) Attitude (d1) kW Humidity (d2) 0 kW Not Applicable 2 CW Temp.(d3) 0 kW Not Applicable Inlet Losses (d4) 0 kW Not Applicable Exhaust back Pressure (d5) 0 kW Not Applicable However if in installation Exhaust Piping after silencer is made at site then back pressure on engine Should not be more than 6 kPA Total Deration (Pderation =d1+d2+d3+d4+d5) 1.76 kW Service Power (as per ISO 3046-1) of the engine (i.e.at stated 3 conditions) P =P -P 124.2 kW Service iso deration 4 Power Loss in Alternator Under stated conditions 3.13 kW Considered Main Alternator efficiency 92 % as per details shared (Palt) 5 Power Consumed by essentials independent auxiliary 1.33 kW Fan Power Consumption (Paux) 6 Transmission losses (PTrans) 0 kW 7 Any Other Power Loss applicable to the offered DG 0 kW set (Pmisc) 8 Net Output for electrical consumption (Poutput) Poutput= kW (Minimum) 119.78 kW Considering 125 kVA as Prime Rating (i.e. Max. kVA Rating) & PF 0.8 Actual Power required from engine (PActual) 9 P =P +P +P +P +P 124.2 kW Actual output alt aux Trans misc
Comment :- PService is Less than the Pactual
Bidder shall Ensure that PService ≥ PActual and shall Furnish calculations / supporting documents post order