You are on page 1of 5

M 199 SPECIFICATIONS FOR MATERIALS

Standard Specification for

Precast Reinforced Concrete Manhole Sections

AASHTO DESIGNATION: M 199-931


(ASTM DESIGNATION: C 478-90b)

1. SCOPE1 T 22 Compressive Strength of an order, two separate and alternative


Cylindrical Concrete bases of acceptance are permitted for flat
Specimens slab tops as follows:
1.1 This specification covers precast
reinforced concrete manhole base T 280 Testing Concrete Pipe, 5.2.1 Acceptance on the Basis of Proof-
sections, riser sections, and Sections, or Tile of-Design Test-Acceptance of flat slab
appurtenances such as grade rings, tops 2.2 ACI Standard: tops will be on the basis of passing a
and special sections for use in sewer and proof-of-design test in accordance with
318 Building Code, Requirements Section 11. When agreed upon between
water works. for Reinforced Concrete the purchaser and the manufacturer,
1.2 A complete metric companion to certified copies of tests performed on
AASHTO M 199 has been developed-M identical tops shall be accepted instead of
199M; therefore, no metric equivalents 3. TERMINOLOGY
further proof-of-design acceptance tests.
are presented in this specification. In addition to such tests, the materials
NOTE 1-This specification is a manufacturing 3.1 Definitions-For definitions of terms comprising the flat slab tops shall
and purchase specification only, and does not relating to concrete pipe, see AASHTO conform in all respects to those required
include requirements for installation of metal M 262. for the riser sections.
frames, covers and gratings for access
purposes. 5.2.2 Acceptance on the Basis of
4. TYPES Rational Design-Acceptance of flat slab
tops will be on the basis of the
2. REFERENCED DOCUMENTS purchaser's approval of design
4.1 Precast risers and grade rings calculations and detailed drawings. The
manufactured according to this specifica- basis of design shall be in accordance
2.1 AASHTO Standards: tion shall be of one type, and precast tops with the appropriate section of the latest
M6 Fine Aggregate for Portland shall be of the following three types: revision of ACI 318. In addition to such
Cement Concrete 4.1.1 Concentric cone, designs and drawings, the materials
M 31 Deformed and Plain Billet- 4.1.2 Eccentric cone, and comprising the flat slab tops shall
Steel Bars for Concrete conform in all respects to those required
4.1.3 Flat slab top.
Reinforcement for the riser sections.
4.2 Precast base sections shall be the
M 32 Cold Drawn Steel Wire for 5.2.3 In addition to the requirements in
following two types:
Concrete Reinforcement either Sections 5.2.1 or 5.2.2, the
4.2.1 Base riser sections and separate minimum requirements of Section 7 shall
M 55 Welded Steel Wire Fabric for base slab, and
Concrete Reinforcement apply.
4.2.2 Base riser section with integral
M 80 Coarse Aggregate for floor.
Portland Cement Concrete 6. MATERIALS
M 85 Portland Cement
5. ORDERING INFORMATION
M 148 Liquid Membrane Forming 6.1 Reinforced Concrete-The reinforced
Compounds for Curing concrete shall consist of cementitious
Concrete 5.1 Unless otherwise designated by the materials, mineral aggregates, and water,
M 221 Welded Deformed Steel Wire purchaser at the time of, or before placing in which steel has been embedded in such
Fabric for Concrete an order, acceptance of precast concrete a manner that the steel and concrete act
Reinforcement manhole sections, will be on the basis of together.
tests of materials and inspection of 6.2 Cementitious Materials:
M 225 Deformed Steel Wire for completed product. Acceptability of
Concrete Reinforcement 6.2.1 Cement-Cement shall conform to
bases and risers covered by this
M 240 Blended Hydraulic Cements the requirements for portland cement of
specification shall be determined by the
AASHTO M 85, or shall be portland
M 262 Terms Relating to Concrete results of such tests of materials as are
blast-furnace slag cement or portland-
Pipe and Related Products required in Section 6; by crushing tests
pozzolan cement conforming to the
on concrete cores or cured concrete
M 295 Fly Ash and Raw or Calcined requirements of AASHTO M 240, except
cylinders; and by inspections of the
Natural Pozzolan for Use as a that the pozzolan constituent in the Type
finished manhole sections, including
Mineral Admixture in IP portland pozzolan cement shall be fly
amount and placement of reinforcement,
Portland Cement Concrete ash and shall not exceed 25 percent by
to determine its conformance with the
weight.
design prescribed in this specification
1 and its freedom from defect. 6.2.2 Fly Ash-Fly ash shall conform to
Agrees with ASTM C 478-90b, except for limiting
the requirements of Class F or Class C of
absorption testing to the 5-hour boil method and the 5.2 Unless otherwise designated by the
method of retest in case of failure of absorption AASHTO M 295.
purchaser at the time of, or before placing
specimens.

235
M 199 SPECIFICATIONS FOR MATERIALS

6.2.3 Allowable Combinations of 7.1.4.4 Minimum concrete thickness 8.1.1.7 The continuity of the circum
Cementitious Materials-The combination under the invert when the channel is cast ferential reinforcing steel shall not be
of cementitious materials used in the in a cured base section shall be 2 in. destroyed during the manufacture of the
concrete shall be one of the following: 7.1.4.5 Width of channel at top of the sections, except when lift holes or pipe
6.2.3.1 Portland cement only, benching shall be a minimum of the pipe openings are to be installed.
6.2.3.2 Portland blast furnace slag I.D. 8.1.1.8 If the splices are not welded, the
cement only, 7.1.4.6 Invert shall provide a positive reinforcement shall be lapped not less
flow between inlet to outlet pipes. than 20 diameters for deformed bars, and
6.2.3.3 Portland pozzolan cement only, 40 diameters for plain bars and
or 7.1.4.7 The minimum channel center line colddrawn wire. In addition, where
6.2.3.4 A combination of portland radius shall be the pipe inside diameter. lapped cages of welded-wire fabric are
cement and fly ash wherein the 7.2 Modified and Special Design: used without welding, the lap shall
proportion of fly ash is between 5 and 25 7.2.1 Manufacturers may submit to the contain a longitudinal wire.
percent by weight of total cementitious purchaser, for approval prior to 8.1.1.9 When splices are welded and are
material (portland cement plus fly ash). manufacture, designs other than those not lapped to the minimum requirements
6.3 Aggregates-Aggregates shall described in Section 7. If such approval is above, pull tests of representative
conform to AASHTO M 6 and M 80, obtained, then such manhole sections specimens shall develop at least 50
except that the requirement for gradation must meet all of the tests and percent of the minimum specified
shall not apply. performance requirements specified by strength of the steel, and there shall be a
6.4 Admixtures and Blends-Admixtures the purchaser in accordance with minimum lap of 2 in. For butt-welded
and blends may be used with the Sections 11 and 12. splices in bars or wire, permitted only
approval of the purchaser. 7.2.2 If permitted by the purchaser, the with helically wound cages, pull tests of
manufacturer may request approval of representative specimens shall develop at
6.5 Steel Reinforcement-Reinforcement
designs of special sections, such as least 75 percent of the minimum
shall consist of wire conforming to
reducers and bases. specified strength of the steel.
AASHTO M 32 or M 225, or of wire
fabric conforming to AASHTO M 55 or 8.1.2 Longitudinal Reinforcement-Each
M 221, or of bars of Grade 40 steel line of circumferential reinforcement
8. REINFORCEMENT
conforming to AASHTO M 31. shall be assembled into a cage that shall
contain sufficient longitudinal bars or
8.1 Base, Riser, and Conical Top members, to maintain the reinforcement
7. DESIGN Sections: in shape and position within the form to
8.1.1 Circumferential Reinforcement: comply with permissible variations in
7.1 Designs: Section 8.1.1.
8.1.1.1 The circumferential
7.1.1 The minimum compressive reinforcement may consist of either one 8.1.3 Joint Reinforcement-Either the
strength of the concrete in the manhole or two lines of steel, the total area per tongue or groove of the joint shall
base, riser, and top sections shall be 4000 vertical foot of which shall be not less contain circumferential reinforcement
psi. The minimum wall thickness shall be than 0.0025 times the inside diameter in equal in area to that of a single line
one-twelfth of the internal diameter of the inches. within the wall of the section.
riser or largest cone diameter. The access 8.1.1.2 A line of circumferential 8.1.4 Reinforcement Cover-The
opening in cone or top sections shall be a reinforcement for any given total area exposure of the ends of the reinforcement
minimum of 24 in. in diameter. may be composed of two layers if the stirrups or spacers that have been used to
7.1.2 Flat slab tops shall have a layers are not separated by more than the position the cages during the placement
minimum thickness of 6 in. for risers up thickness of one cross member plus '/, in. of the concrete, shall not be a cause for
to and including 48 in. in diameter and 8 The two layers shall be tied together to rejection.
in. for larger diameters. form a single cage. All other 8.2 Grade Rings:
7.1.3 Base slabs or floors shall have a specification requirements such as laps, 8.2.1 Circumferential Reinforcement-
minimum thickness of 6 in. for risers up welds, and tolerances of placement in the The circumferential reinforcement shall
to and including 48 in. in diameter and 8 wall of the manhole, risers, and tops, etc., have an equivalent area of not less than
in. for larger diameters. shall apply to this method of fabricating a 0.07 in.2/vertical ft but not less than 0.024
line of reinforcement. in .2 in any one grade ring.
7.1.4 Base sections with precast
benched inverts may be cast as 8.1.1.3 Where one line of circular 8.3 Base Slabs and Floors:
monolithic casting or as a secondary reinforcement is used, it shall be placed
8.3.1 A layer of reinforcement shall be
casting in a cured base section with the in the center third of the wall.
placed above the midpoint, and shall
following minimum dimensions. 8.1.1.4 Where two lines of circular have a minimum area of 0.12 in.'/linear ft
7.1.4.1 Minimum slope of ½ in./ft from reinforcement are used, each line shall be in both directions.
the channel to the I.D. of manhole wall so placed that the protective covering
8.3.2 The minimum protective cover
for the benching. over the circumferential reinforcement in
over the reinforcement shall be 1 in.
the wall of the section shall be I in.
7.1.4.2 Minimum channel invert depth of 8.4 Flat Slab Tops:
one-half of the pipe inside diameter. 8.1.1.5 The location of the reinforcement
shall be subject to the permissible 8.4.1 A layer of reinforcement shall be
7.1.4.3 Minimum concrete thickness variations in dimensions given in Section placed near the bottom surface so that the
from the invert to the bottom of the 12. protective cover over the reinforcement
integral base section shall be 4 in. when shall be 1 in. Flat slab tops manufactured
precast monolithic as a benched unit. 8.1.1.6 The spacing center to center of
without a joint or other indication of the
circumferential reinforcement in a cage
top or bottom of the slab shall be
shall not exceed 6 in.
manufactured with two layers of steel
236
M 199 SPECIFICATIONS FOR MATERIALS

reinforcement, one located near the meet the strength requirements. The Not more than 10 percent of the cylinders
bottom surface and one near the top curing chamber shall be so constructed as tested shall fall below the specified
surface so that the protective cover over to allow full circulation of steam around design strength. In no case shall any
each layer is 1 in. the entire manhole base, riser, or top. cylinder tested fall below 3200 psi. If
8.4.2 A layer of reinforcement shall 10.2.2 Water Curing-Concrete manhole cores are drilled from the wall of the
have a minimum area of 0.12 in.2/linear sections may be water-cured by covering manhole sections and tested, they shall be
ft in both directions. with water-saturated material or by a cut and tested in accordance with the
system of perforated pipes, mechanical requirements of AASHTO T 280. The
8.4.3 Openings in flat slabs shall be average compressive strength of all cores
additionally reinforced with a minimum sprinklers, porous hose, or by any other
approved method that will keep the tested shall be equal to or greater than the
of the equivalent of 0.20 in .2 of steel at specified design strength of the concrete.
90 degrees. Straight rods used to manhole bases, risers, and tops moist
during the specified curing period. In no case shall any core tested fall below
reinforce opening shall have a minimum 3200 psi.
length equal to the diameter of the 10.2.3 The manufacturer may, at his
opening plus 2 in. option, combine the methods described in When the cores cut from a section of
Sections 10.2.1 to 10.2.4 provided the manhole section successfully meet the
required concrete compressive strength is strength test requirement, the core holes
9. JOINTS attained. shall be plugged and sealed by the
manufacturer in a manner such that the
10.2.4 A sealing membrane conforming manhole section will meet all of the
9.1 The reinforced concrete manhole to the requirements of AASHTO M 148 requirements of this specification.
base and riser sections, excepting grade may be applied and should be left intact Manhole sections so sealed shall be
rings, shall be designed and formed with until the required strength requirements considered as satisfactory for use.
male and female ends, so that when the are met. The concrete at the time of
manhole base, riser, and top are application shall be within 10°F of the NOTE 2-Concrete of such low water content
assembled they will make a continuous atmospheric temperature. All surfaces that it cannot be properly consolidated by the
and uniform manhole, compatible with shall be kept moist prior to the methods prescribed herein is not covered by
the tolerances given in Sections 12.3 and this method. Provisions for specimens and
application of the compounds and shall
methods of testing will be found in the
12.4. be damp when the compound is applied. standards concerned. There ate concretes that
can be consolidated by external vibrations, but
10. MANUFACTURE additional forces on the surface are required to
11. PHYSICAL REQUIREMENTS embed the coarse aggregate thoroughly and
consolidate the mixture. For such mixtures the
10.1 Mixture-The aggregates shall be 11.1 Test Specimens-The specified following procedures may be followed: Using
sized, graded, proportioned, and mixed external vibration fill 6 by 12-in. cylinder
number of specimens required for the molds in 3-in lifts using a 10-lb cylindrical
with such proportions of cementitious tests shall be furnished without charge by surcharge, or 3 by 6-in cylindrical molds in 2-
materials and water as will produce a the manufacturer, and shall be selected at in lifts using a 2.5-lb cylindrical surcharge.
homogeneous concrete mixture of such random by the purchaser and shall be The surcharge should have a diameter ¼ in.
quality that the manhole sections will from manhole sections that would not less than the inside of the mold.
conform to the test and design otherwise be rejected under this Simultaneously each lift should be compacted
requirements of this specification. All specification. The selection shall be made by external vibration with the surcharge on the
concrete shall have a water-cementitious at the point or points designated by the top surface of the concrete, until the mortar
materials ratio not exceeding 0.53 by begins to ooze around the bottom of the
purchaser when placing the order. surcharge.
weight. Cementitious materials shall be 11.2 Number and Type of Test
as specified in Section 6.2 and shall be Required-A purchaser may require 11.3.2 Absorption-The absorption of a
added to the mix in a proportion not less compression test specimens in the specimen from the wall of the section, as
than 470 lb/yd', unless mix designs with a amount of 5 percent of the total order, but determined in accordance with AASHTO
lower cementitious materials content not to exceed two cylinders for each day's T 280 shall not exceed 9 percent of the
demonstrate that the quality and production. One flat slab top for each dry mass. Each specimen shall be a piece
performance of the pipe meet the design shall be tested if Section 5.2.1 has broken from the wall or a core drilled
requirements of this specification. been designated as the basis of from the wall, shall have a minimum area
10.2 Curing-Manhole sections shall be acceptance, unless the purchaser has of 9 in' as measured on one surface of the
subjected to any one of the methods of indicated otherwise. section wall and a thickness equal to the
curing described in Sections 10.2.1 to section wall and shall be free of visible
11.3 Concrete Strength: cracks. When the initial absorption
10.2.4 or to any other method or
combination of methods approved by the 113.1 Compressive Strength- specimen from a section fails to conform
purchaser, that will give satisfactory Compression tests for satisfying the to this specification, the manufacturer
results. The manhole bases, risers, and minimum specified concrete strength shall be allowed a retest on two
tops shall be cured for a sufficient length requirement may be made on either additional specimens from the same
of time so that the concrete will develop standard rodded concrete cylinders or section for each specimen that failed. The
the specified compressive strength at 28 cylinders compacted and cured in a section shall be acceptable only when all
days or less. similar manner to the manhole sections of the retest specimens meet the
or, at the option of the manufacturer, on absorption requirements.
10.2.1 Steam Curing-Manhole sections cores drilled from the wall of the
may be placed in a curing chamber, free manhole sections. If cylinders are tested,
11.3.3 Retest of Manhole Sections-When
of outside drafts, and cured in a moist not more than 20 percent of the concrete
they shall be tested in accordance with test specimens fail to pass the
atmosphere maintained by the injection AASHTO T 22. The average
of steam for such time and such requirements of this specification, the
compressive strength of all cylinders manufacturer may cull his stock and may
temperature as may be needed to enable tested shall be equal to or greater than the
the manhole bases, risers, and tops to eliminate whatever quantity of manhole
specified design strength of the concrete.
237
M 199 SPECIFICATIONS FOR MATERIALS

sections he desires and must so mark with a thickness greater than 4 in., the opposite wall of the manhole riser or
them that they will not be shipped. The maximum variation shall be ± 10 percent cone shall be 18 in. measured at the
required tests shall be made on the of the thickness or ± ⅝ in whichever is center face of the step.
balance of the order and the manhole the lesser. In no case, however, shall the 13.6 Testing and Acceptance:
sections shall be accepted if they conform cover over the reinforcement be less than
to the requirements of this specification. ¾ in. The preceding minimum cover 13.6.1 Vertical and horizontal load test
limitation does not apply to the mating procedures for manhole steps shall be in
11.4 Flat Slab Top-The flat top test accordance with AASHTO T 280. The
procedure shall be in accordance with surfaces of the joint.
manufacturer furnishing manhole
AASHTO T 280. The ultimate test load 12.5.2 Area-Steel areas that are 0.005 sections with steps under this
shall, be at least 130 percent of the dead in.'-/linear ft less than that called for by specification shall furnish all facilities
load on the slab and at least 217 percent the design will be considered as meeting and personnel necessary to carry out the
of the live-plus impact load on the slab. the required steel area. tests as required in Section 10 of
The dead load is the weight of the AASHTO T 280.
column of earth over the slab plus the
weight of the riser supported by the slab. 13. MANHOLE STEPS AND 13.6.2 The horizontal pull out load shall
The live load is the maximum anticipated LADDERS be 400 lb.
wheel load that may be transmitted 13.6.3 The vertical load shall be 800 lb.
through the riser to the slab. The slab 13.1 Access through manholes may be 13.6.4 One installed manhole step of the
shall be required to support the test load by steps that are cast, mortared, or type to be used on a project shall be
without failure. Failure is defined as the attached by mechanical means into the tested unless certified test results are
inability of the slab to resist an increase walls of riser or conical top sections or by available.
in the applied test load. ladder. Ladders shall conform to the 13.6.5 The step shall be acceptable if the
11.5 Test Equipment-Every requirements of the Occupational Safety following requirements are met:
manufacturer furnishing manhole and Health Standards, U.S. Department
of Labor. 13.6.5.1 The step remains solidly
sections under this specification shall
embedded after application of the
furnish all facilities and personnel 13.2 Manhole steps that are cast, horizontal load test.
necessary to carry out the tests in mortared, or attached by mechanical
AASHTO T 280. means into the walls of riser or conical 13.6.5.2 The step sustains a permanent
top sections shall meet the requirements set of ½ in. or less after application of the
of Sections 13.3 through 13.6. vertical load test.
12. PERMISSIBLE VARIATIONS 13.6.5.3 No cracking or fracture of the
13.3 Design:
step nor spalling of the concrete is
12.1 Internal Diameter-The internal 13.3.1 Steps in riser and conical top evident.
diameter of manhole sections shall not sections shall be aligned in each section
so as to form a continuous ladder with 13.6.6 If certified test results are not
vary more than 1 percent available and the step selected fails to
rungs equally spaced vertically in the
12.2 Wall Thickness-The wall assembled manhole at a maximum design conform to the test requirements, the
thickness shall be not less than that distance of 16 in. apart. manufacturer may select two other steps
described in the design by more than 5 for retests. If either of these steps fail, the
percent or ± 3/16 in., whichever is the 13.3.2 Steps shall be embedded in the steps shall be rejected.
greater. A wall thickness greater than that riser or conical top section wall a
shown in the design shall not be cause for minimum distance of 3 in.
14. REPAIRS
rejection. 13.4 Materials:
12.3 Length of Two Opposite Sides- 13.4.1 When dissimilar types of
Variations in laying lengths of two materials are used in the steps, 14.1 Manhole sections may be
opposite sides of manhole sections shall appurtenances and fastenings, the repaired, if necessary, because of
be not more than ⅝ in. materials shall be treated to prevent imperfections in manufacture or damage
deleterious effects. during handling and will be acceptable if,
12.4 Length of Sections:
13.4.2 That portion of the step in the opinion of the purchaser, the
12.4.1 The underrun in length of a repaired manhole sections conform to the
section of manhole base, riser, or conical projecting into the riser or cone opening
shall be free of splinters, sharp edges, requirements of this specification.
top shall be not more than ¼ in./ft of
length with a maximum of ½ in. in any burrs, or projections which may be a
one section. hazard. 15. INSPECTION
12.4.2 The vertical spacing and vertical 13.5 Dimensions:
alignment between adjacent manhole 13.5.1 Ferrous metal steps not painted or 15.1 The quality of materials, the
steps and horizontal distance from the treated to resist corrosion shall have a process of manufacture, and the finished
inside wall to the center line of a manhole minimum cross sectional dimension of 1 manhole sections shall be subject to
step may vary 1 in. from the design in. inspection and approval by an inspector
dimensions. 13.5.2 The minimum width of rungs or employed by the purchaser.
12.5 Position or Area of cleats shall be 10 in. NOTE 3-Experience has shown that
Reinforcement: 13.5.3 The rung or cleat shall project a successful performance of this product
12.5.1 Position-For sections with a 4-in. minimum clear distance of 4 in. from the depends on the type of bedding and backfill
wall of the riser or cone section measured and the care in the field installation of the
thickness or less, the maximum variation
from the point of embedment. manhole and connecting pipes. The purchaser
in the position of the reinforcement from is cautioned that he should require inspection
that described in Section 8 shall be ± 10 13.5.4 The minimum clear distance at the construction site.
percent of the thickness or ± ¼ in., between the rung or cleat and the
whichever is the greater. For sections
238
M 199 SPECIFICATIONS FOR MATERIALS

16. REJECTION adversely affect the function of the 17. PRODUCT MARKING
manhole.
16.1 Manhole sections shall be subject 16.1.3 The planes of the ends of the 17.1 The following information shall
to rejection on account of failure to manhole sections are not perpendicular to be legibly marked on each manhole
conform to any of the specification their longitudinal axis, within the limits section:
requirements. In addition, individual of the variations given in Sections 12.3
and 12.4. 17.1.1 MH and specification
sections of manhole sections may be designation,
rejected because of any of the following: 16.1.4 Damaged or cracked ends, where
such damage would prevent making a 17.1.2 Date of manufacture, and
16.1.1 Fractures or cracks passing
through the wall, except for a single end satisfactory joint. 17.1.3 Name or trademark of the
crack that does not exceed the depth of 16.1.5 Any continuous crack having a manufacturer.
the joint. surface width of 0.01 in. or more and 17.2 Marking shall be indented into
16.1.2 Defects that indicate mixing and extending for a length of 12 in. or more, the manhole bases, risers, and top
molding not in compliance with Section regardless of position in the section wall. sections or shall be painted thereon with
11.1, or surface defects indicating waterproof paint.
honeycombed or open texture that would

239

You might also like