Professional Documents
Culture Documents
Supplying Power For Electric Fire Pumps
Supplying Power For Electric Fire Pumps
Learning Objectives
1. Know which codes dictate how to specify power for fire pumps.
2. Understand how to coordinate the numerous codes involved.
NFPA 101, 2012 Edition. Just like NFPA 5000, NFPA 101 Chapter 11
(special structures and high-rise buildings) requires that fire pumps be
part of the standby system and comply with NEC 701. Also, 11.8.6
requires that the emergency command center monitor the fire pump
status.
NFPA 110, 2010 Edition. NFPA 110 classifies fire pumps as part of Level
I systems, which are essential to the safety of human life (see A.4.4.1).
This standard refers to NFPA 20 for the installation of fire pumps.
NFPA 20, 2013 Edition. NFPA 20 covers all stationary fire pumps, but
Chapter 6 details electrical fire pumps.
Had any shutdowns for longer than 4 hours in the previous year
Experienced power outages that were not caused by natural
disasters or grid management failure
Been supplied by overhead conductors.
NFPA 20 Chapter 9 concerns the performance
and testing of electrical equipment between the source and the pump.
Even though the fire pumps run infrequently, Chapter 9 requires that all
power supplies for the fire pumps be sized based on a continuous duty
cycle. Chapter 9 also prohibits the use of phase converters as they are
not considered reliable power sources. Thus, it’s necessary to use a
single phase motor and fire pump controller if the source is single phase.
NFPA 20 also requires an alternate power source for the primary fire
pump if the building’s height is beyond the reach of the fire department’s
equipment. However, this requirement is waived if a backup pump is
installed on the premises. If the alternate power source is a standby
generator system, it must have enough capacity to carry the full load of
the fire pump and other emergency loads. The generator must also be
able to support the fire pump auxiliary system, such as a jockey pump,
and have a fuel supply that can provide 8 hours of fire pump continuous
operation.
Although the scope of Article 695 has not changed, important revisions
have been made through the years. One of the most important revisions
is the requirement of reliable power for electric fire pumps installed in a
campus-style arrangement. This arrangement includes multiple buildings
often powered by a medium-voltage distribution system.
NEC 695.3 requires that a reliable power source supply power for an
electric fire pump. While NEC does not define a reliable power source,
the definition in NFPA 20, described above, can apply. The reliable power
source must also be able to carry the locked rotor current of the fire pump
motor and the full load current of the accessory equipment if the
accessory equipment is connected to the same power source. This
reliable power source could be an individual source that in turn could be
one of the following:
If the utility power source is not reliable, multiple sources can be used.
Alternate sources could be another separate utility feed or a standby
generator or both. The generator does not need to be sized for the locked
rotor current of the fire pump—only for the full load current of the fire
pump(s) and the associating loads. Remember that NFPA 20 Chapter 9
requires the power source to be sized for the continuous duty of the fire
pump.
Best practices
NEC 695.6(G) does not permit ground fault protection of the fire pump.
Again, this is done to allow continuity of power to the fire pump circuit.
Work with the fire marshal. When designing power for an electrical fire
pump, make sure you talk to the fire marshal about the fire pump room
location. In the case of a fire, the fire department will enter the pump room
to monitor the pump activity, so the pump room needs to be accessible,
preferably from the outside.
Eduard Pacuku is electrical project engineer at Jacobs Engineering,
where the majority of his time is spent designing electrical distribution
systems for universities (including laboratories), health care facilities, and
data centers. He has extensive experience with fire pump installations.