Table 11 Provision of terminal units, AVSUs and local alarms

Department O2 N2 O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm


Accident and Emergency 1 set (1) 1 set hp/lp (9)
Resuscitation room, per trolley space 2 2 – 2 – 2 2 – 2 sets*
Note: One set either side of the trolley space, if installed in
fixed location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.

3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs
Major treatment/plaster room per trolley space 1 1 1p 1 1p 1 1 – 1 set/8 TUs
Post-anaesthesia recovery per trolley space 2 – – 2 – 2 – – 2 sets*
Note: One set either side of the trolley space, if installed in
fixed location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Treatment room/cubicle 1 – – – – 1 – – 1 set/8 TUs
Operating department 1 set (1)
Anaesthetic rooms (all) 1 1 – 1 – 1 1 –
Operating room, orthopaedic:
For anaesthetist 2 1 – 2 – 2 1 – 1 set per suite 1 set per suite
(2)(3) hp/lp (10)
For surgeon – – – – 4 2 – – –

Note: Orthopaedic surgery is normally performed in operating
rooms provided with ultra-clean systems. Such systems are much
more effective in terms of airflow when provided with partial
walls. These walls may be effectively used to include terminal
units that can be supplied by rigid pipework. Such installations
do not suffer from excessive pressure loss when surgical air is
required at high flows.
Operating room, neurosurgery
Anaesthetist 2 1 – 2 – 2 1 – 1 set per suite 1 set per suite
(2)(3) hp/lp (10)
Surgeon – – – – 2 2 – –
Note: If multi-purpose pendants are used, there may be some
loss of performance of surgical tools because of bore restrictions
and convolution of the flexible connecting assemblies at the
articulated joints.
15
16

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
Department O2 N2 O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm
Operating room, general surgery etc
Anaesthetist/surgeon (see (14) regarding CO2) 2 2 – 2 2p 2 2 – 1 set per suite 1 set per suite
(2)(3) hp/lp (10)
Note: Terminal units installed in separate pendants: p = project
team option where some orthopaedic overspill surgery may be
performed.
Post-anaesthesia recovery, per bed space 2 – – 2 – 2 – – 2 sets* (5) 1 alarm for both
sets of AVSUs (11)
Note: One set either side of the bed space, if installed in fixed
location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Equipment service room per work space 1 1 – 1 1 1 1 – 1 set 1 set hp/lp (12)
Maternity department 1 set (1) 1 set (9)
LDRP room (normal/abnormal) 1 set per 6–8
rooms (5)
Mother 1 – 1 – – 2 – –
Baby (per cot space) (allow for 2 cots only) 1 – – 1 – 1 – –
Operating suite:
Anaesthetist 1 1 – 1 – 1 1 – 1 set 1 set hp/lp (10)
Obstetrician – – – – – 2 – –
Paediatrician (per cot space) (allow for 2 cots only) 1 – – 1 – 1 – –
Post-anaesthesia recovery (per bed space) 1 – – 1 – 1 – – 1 set 1 set (11)
Equipment service room** per work space 1 1 1 1 – 1 1 – 1 set 1 set (12)
Neonatal unit, per cot space 2 – – 2 – 2 – – 2 sets* 1 for both sets of
AVSUs (11)
Note: One set either side of the bed space, if installed in fixed
location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Equipment service room** per work space 1 – – 1 – 1 – – 1 set 1 set (12)
In-patient accommodation:
Single bed room 1 – – – – 1 – – 1 set for ward 1 set (11)
unit
Multi-room, per bed space 1 – – – – 1 – –
Nursery, per cot space 1 – – – – 1 – –
Provision for 2 cots only irrespective of number of cot spaces
Department O2 N2 O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm
Diagnostics departments 1 set (1) 1 set (9)
Special procedures room 1 1 – 1 – 1 1 – 1 set 1 set (10)
Anaesthetic room 1 1 – 1 – 1 1 – 1 set
Holding and recovery 1 – – 1p – 1 – – 1 set
Ultrasound 1 – – – – 1 – – 1 set
Fluoroscopy 1 – – – – 1 – – 1 set

3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs
Urography 1 – – – – 1 – – 1 set
Tomography 1 – – – – 1 – – 1 set
Magnetic resonance imaging (MRI) suite 1 1 – 1 – 1 1 – 1 set 1 set (10)
CAT room 1 1 – 1 – 1 1 – 1 set 1 set (10)
Angiography 1 1 – 1 – 1 1 – 1 set 1 set (10)
Endoscopy 1 1 – 1 – 1 1 – 1 set 1 set (10)
Lineac bunkers 1 1 – 1 – 1 1 – 1 set 1 set (10)
General purpose rooms 1 – – – – 1 – –
In-patient accommodation 1 set for the
ward unit (1)
Single-bed room 1 – – 1 – 1 – – 1 set (11)
1 – – 1 – 1 – –
Multi-bed room, per bed space 1 – – 1 – 1 – –
Treatment room
(Appropriate for adult acute, children and the elderly) 1 – – 1 – 1 – –
Renal
Per dialysis station 1 – – 1 – 1 – –
Per bed space 1 – – 1 – 1 – –
Critical care area 1 set (1) 1 set (11)
Per bed space 4 2p 2p 4 4 2p 2p 2 sets* (4)

Note: One set either side of the bed space, if installed in fixed
location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Equipment service room, per work space 1 1p 1p 1 1 1p 1 set 1 set (12)
Coronary care unit (CCU)
2 sets* (4)(6)(7)
17

Per bed space 4 4 4 1 for both sets of


AVSUs (11)
18

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
Department O2 N2 O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm
High dependency unit (HDU)
Per bed space 4 4 4 2 sets* (4)(6)(7) 1 for both sets of
AVSUs (11)
Burns unit 2 2p 2p 2 2 2p 2 sets* (4)(6)(7) 1 for both sets of
AVSUs (11)
Adult mental illness accommodation 1 set (1)
Electro-convulsive therapy (ECT) room 1 1 1 1 1 1 set (2) 1 set hp/lp (10)
Post-anaesthesia recovery, per bed space 1 1 1 1 set (1) 1 set (11)
Adult acute day care accommodation 1 set
Treatment room:
Anaesthetist 1 1p 1p 1 1p 1 set 1 set hp/lp
Surgeon 2 if (p) (10)
Post anaesthesia recovery, per bed space 1 1p 1 1 set 1 set (11)
Day patient accommodation 1 set (1)
Single bed room 1 1 1 set (1)(13) 1 set hp/lp (11)
Multi-bed room, per bed space 1 1
Treatment room 1 1p 1
Endoscopy room 1 1p 1p 1 1p 1 set (2)(13) 1 set (10)
Fracture clinic
Plaster room 1 1 1p 1p 1 1 1 set (1) 1 set (9)
Oral surgery, orthodontic department 1 set (1) 1 set hp/lp if (p)
(9)

Consulting/treatment room, type 1 1 1p 1 Dental † 1p 1 set/4–6 rooms


air
Consulting/treatment room, types 2 and 3 1 1 † 1 set/4–6 rooms
will be
required
Recovery room, per recovery position 1 1 1 1 set
Appliance laboratory, per workstation 1 1p 1 1 1 1p 1 set 1 set hp/lp (11)
Out-patient department
Treatment room/cubicles 1 1p 1p 1 1p 1 set (1)(8) 1 set hp/lp if (p)
(9)