Activation of Sounder
Common Supervisory
sounder in hearing-
indicator & audible
Affected floor
CAUSE EFFECT
signal
signal
signal
floor
Basement Floor
Activation of one smoke detector (if acknowledged D3 D3
within
15sec)
×
Activation of one smoke detector (if not acknowledged
within 15sec)
×
×
Activation of Manual Call Point or Heat Or Multi
sensoror
Double Knock ( 2 smoke detecor)
×
×
Alarm signal from Sprinkler Flow Switch
×
×
Electrical/Diesal Pump Run Status
×
ZCV closed
×
× × ×
ZCV closed
×
General
Faults in devices & Loops
×
CO Detectors
×
Duct Detectors
×
The control of
Notes dampers
Ensure that activation of FM200 should also close immediately connected
directly to
the dampers on room. If applicable, provide separate column or FM200 panel
sequence of operation for to close
this output. immediatelty
when the
To avoid operational issues, it is recommended to provide activation
To be of
FM200
disscuss with
individual solenoid valve in each kitchen to shut-
Eng. Alaa
off in case of gas leak in the affected kitchen/area only. To be
disscuss with
Eng. Alaa
It is assumed that breaker shut off means shut off electric power To be
to the affected cooking appliances. disscuss with
Eng. Alaa
Otherwise, please confirm.
Ensure that normal lighting is not turned off.
× × × Signal to Car park Fresh
D3
air Fan to stop
× × × × × × × × × × Activation of Stair
D3
D3
D3
Alarm Cause & Effect Matrix
Pressurization fans
× × × Activation of smoke
management in typical
D3
D3
HVAC Control
floors
D3
D3
D3
designated alternate
Floor
D3
D3
D3
D3
D3
D3
floor
D3
D3
D3
Access Doors