CAUSE AND EFFECT MATRIX FOR IG541 SYSTEM FOR RO ELECTRICAL BUILDING @ FIRST FLOOR

HOLD/DELAY (30 SEC) AGENT RELEASE

SIGNAL TO EMR (Signal for releasing the


ACTIVATE STROBE LIGHT (Visual alarm
TRANSMIT TROUBLE SIGNAL TO FACP

FACP (Building Fire Alarm Panel) from


TRANSMIT SUPERVISORY SIGNAL TO
(Building Fire Alarm Panel) from FECP

(Building Fire Alarm Panel) from FECP


TRANSMIT ALARM SIGNAL TO FACP

CLOSE SMOKE DAMPERS AND FIRE


FECP PANEL (IG541 Control Panel)

ACTIVATE STROBE/HORN

outside the room)

SMOKE DAMPERS
ACTIVATE BELL

IG541System)
INDICATED

FECP
ROOM NAME :- 11 KV CAPACITOR BANK-1

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

ROOM NAME :- 11 KV CAPACITOR BANK-2

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

ROOM NAME :- VFD OF MV MOTOR ROOM-1

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

ROOM NAME :- VFD OF MV MOTOR ROOM-2

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

ROOM NAME :- VFD OF MV MOTOR ROOM-3

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

ROOM NAME :- VFD OF MV MOTOR ROOM-4

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

ROOM NAME :- VFD OF MV MOTOR ROOM-5

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

ROOM NAME :- VFD OF MV MOTOR ROOM-6

ACTIVATION OF ANY ONE SMOKE DETECTOR IN THE ROOM X X X X


INPUT INITIATING DEVICE

ACTIVATION OF ANY TWO SMOKE DETECTOR IN THE ROOM X X X X1 X1

MANUAL RELEASE X X X X X2 X X2

ABORT SWITCH X X

SUPPRESSION DISCONNECT SWITCH X X

MAIN RESERVE SWITCH X X

DISCHARGE PRESSURE SWITCH (PFDS) X X X

LOW PRESSURE SWITCH (LPS) X

FECP in Fault condition X X

FECP power failure X X

X1 = Activate after 30 second

X2 = Activate after 15 second


SEQUENCE OF OPERATION MANUAL RELEASE OPERATION
A) ACTIVATION OF ANY ONE OF THE DETECTOR IN CIRCUIT WILL CAUSE ACTIVATION OF MANUAL RELEASE SWITCH WILL CAUSE

1. ALARM INDICATION ON FECP.


2. ALARM BELL WILL RING.
1. ALL OPERATION A,B&C ABOVE WITH 15 Sec. TIME DELAY
3. FIRE SIGNAL TO BUILDING FIRE ALARM PANEL.
4. SIGNAL TO CLOSE FIRE SMOKE DAMPER.

B) SIMULTANEOUS ACTIVATION OF A SECOND DETECTOR IN CIRCUIT WILL CAUSE ABORT SWITCH OPERATION.

IF THE MANUAL ABORT SWITCH IS ACTIVATED IN PRE DISCHARGE


1. PRE-DISCHARGE INDICATION ON FECP. PERIOD
2. STROBE HORN WILL ACTIVATE. 1. ABORT INDICATION ON PANEL.
3. STARTS COUNTDOWN OF SET TIME DELAY (30 Sec). 2. RELEASE OF GAS ON HOLD TILL THE SWITCH IS DEACTIVATED.
4. SIGNAL TO SHUT DOWN ELECTRICAL EQUIPMENT 3. AFTER THE ABORT IS DEACTIVATED, COUNTDOWN WILL START
FROM THE INITIAL TIME AND THEN GAS WILL RELEASE.

C) AT THE END OF SET TIME DELAY.

1. RELEASE INDICATION ON THE PANEL.


2. ACTIVATE THE ELECTROMAGNETIC RELEASE DEVICE TO RELEASE THE
GAS & SIMULTANIOUSILY SEND A SIGNAL TO RELATED ZONE SOLENOID
VALVE TO OPERATE THE SELECTOR VALVE PNEUMATICALLY TO OPERATE.
3. DISCHARGE SIGNAL IN THE FECP.
4. STROBE LIGHT ON THE ENTRANCE OF THE HAZARD.

Note:- Any Fault Alaram Recived. Rectify error from the field then reset the
panel.The will come to normal condition