SYSTEM OUTPUTS
FACP Annunciation (control unit) LCD Annunciator Notification FDAS Interface
recall)
Any Addressable Smoke/Heat Detector l l l l l l l l l
COMPONENTS
NOTE:
1. Zoning will be per floor.
2.Notification appliance is strobelight for all common areas (Hallways, corridors, toilets, parking) and strobehorn for Mechanical Room, pump room, genset/HVSG/LVSG room
3. Back-up battery shall withstand 24 hours w/o alarm and can withstand 5 minutes continuous fire alarm.
4. Activation of Drill Button or General button at the FACP will activates all the strobe speaker, send signal to PA-BGM (Voice Evac) and all interfaces.
5. Activation of any conventional smoke/heat detector shall send signal its dedicated module. This module
will show its location.thru the FACP and SMP.
6. Pre-signal alarm sequence of 3 minutes (180 seconds) will be implemented.
8. FDAS to send signal to PA-BGM to activate Voice Evacuation/Voice Alert on Floor on FIre
* Notes:
1. Pre signal alarm sequence will be bypass by the following items
1. Two addressable smoke detectors/convetional module/waterflow switch trigger an alarm consecutively.
2. Push of manual push station.
3. Push of Fire drill/general button at FDAS panel.