FDAS MATRIX FOR FIRE LIFE AND SAFETY INTERFACE AT AVIDA VIREO TOWER 1

SYSTEM OUTPUTS
FACP Annunciation (control unit) LCD Annunciator Notification FDAS Interface

exteraction fan/blower(180 SECS DELAY)

Send Fire Alarm Signal On ALL FloorS/Levels


interfaces(spf, sef, ahu shutdown, elevator
Display Supervissory Status on LCD

Display Supervissory Status on LCD

to EMERGENCY EVACUATION SYSTEM


Actuate Supervisory LED Indicator

Actuate Supervisory LED Indicator

Pressuration Fan(180 SEC DELAY)


Send signal to activate Stair/Lift

Send Signal On to activate all FDAS


pressurization(180 SECS DELAY)
Send signal to Elevator Primary
Actuate Trouble LED Indicator

Actuate Trouble LED Indicator

Send signal to activate smoke


DisplayTrouble Status on LCD

DisplayTrouble Status on LCD

Activate NAC at floor on Fire


Actuate Alarm LED Indicator

Actuate Alarm LED Indicator


Display Alarm Status on LCD

Display Alarm Status on LCD

Send signal to activate stair


Recall(180 SECS DELAY)
( 180 SECS DELAY)

Activate all NAC

recall)
Any Addressable Smoke/Heat Detector l l l l l l l l l
COMPONENTS

Any Addressable Smoke Detector @ Elevator Lobby l l l l l l l l l


SYSTEM

Any Conventional Smoke/Heat Detector l l l l l l l l l


Manual Pull Station l l l l l l l l
SYSTEM INTERFACES
SYSTEM INPUTS

General Alarm Button l l l


Water Flow Switch l l l l l l l l l
Tamper Switch(GATE VALVE) l l l l
Fire Pump Run Status l l l l l
Fire Pump Power Failure l l l l
l l l l
INTEGRIT

FDAS Panels Secondary Power Supply Monitoring


SYSTEM

FDAS Trouble (Ground Fault, Short Cicuit) l l l l

NOTE:
1. Zoning will be per floor.
2.Notification appliance is strobelight for all common areas (Hallways, corridors, toilets, parking) and strobehorn for Mechanical Room, pump room, genset/HVSG/LVSG room
3. Back-up battery shall withstand 24 hours w/o alarm and can withstand 5 minutes continuous fire alarm.
4. Activation of Drill Button or General button at the FACP will activates all the strobe speaker, send signal to PA-BGM (Voice Evac) and all interfaces.
5. Activation of any conventional smoke/heat detector shall send signal its dedicated module. This module
will show its location.thru the FACP and SMP.
6. Pre-signal alarm sequence of 3 minutes (180 seconds) will be implemented.
8. FDAS to send signal to PA-BGM to activate Voice Evacuation/Voice Alert on Floor on FIre

* Notes:
1. Pre signal alarm sequence will be bypass by the following items
1. Two addressable smoke detectors/convetional module/waterflow switch trigger an alarm consecutively.
2. Push of manual push station.
3. Push of Fire drill/general button at FDAS panel.