CT:250/1A CT:500/1A
415V 415V
CURRENT TRANSFORMER
1.1 KV,1R, 4C x 120 SQMM, AL 1.1 KV,1R, 4C x 120 SQMM, AL
XLPE,ARMOURED CABLE XLPE,ARMOURED CABLE EARTHING
INDICATOR
LT PANEL 3 P+E, SPD TYPE-2, 50kA LT PANEL 3 P+E, SPD TYPE-2, 50kA SOCKET
(1 INVERTER) CT:250/1A (2 INVERTERS) CT:500/1A
PHASE IND. PHASE IND.
CLASS-1
15VA, MFM 230V,5A SOCKET 1NOS. CLASS-1
15VA, MFM 230V,5A SOCKET 1NOS. AC SPD, TYPE 2 IN ACDB
230V,15A SOCKET 1NOS. R Y B 230V,15A SOCKET 1NOS. R Y B
RASIN CAST RASIN CAST
NR 86 95 50N 51G
CT:250/1A
CLASS-5P20 15VA ON OFF TRIP NR 86 95 50N 51G ON OFF TRIP M ACB
51 51N 50 64R CT:500/1A
CLASS-5P20 15VA
51 51N 50 64R
E/F INDICATION E/F INDICATION
MCCB
RELEASE
MP TYPE WITH
O/C,S/C,E/F
50kA MCCB
4P, 415V, 500A,
RELEASE
MP TYPE WITH
O/C,S/C,E/F
50kA MCCB
4P, 415V, 250A,
EP M METER
4P, 415V, +/- 10%, 50HZ +/- 3%, 250 A, 50 KA FOR 1 SEC, AL, BUS BAR 4P, 415V, +/- 10%, 50HZ +/- 3%, 500 A, 50 KA FOR 1 SEC, AL, BUS BAR DRAWOUT TYPE
MP TYPE WITH
MP TYPE WITH
MP TYPE WITH
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
4P, 415V, 250A, 50kA MCCB
MP TYPE WITH
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
4P, 415V, 250A, 50kA MCCB
MP TYPE WITH
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
4P, 415V, 32A, MCCB
51 Inverse Time Over Current Relay 51N IDMT EARTH FAULT RELAY
1.1kV,1R x 4C x 35 SQMM, AL 1.1kV,1R x 4C x 35 SQMM, AL
XLPE, ARMOURED CABLE XLPE, ARMOURED CABLE
Trip Circuit Supervision Relay
SPARE
SPARE
MFM TOWARDS AUXILIARY LOAD MFM MFM TOWARDS AUXILIARY LOAD 95 86 Master Trip Relay
METER, CLASS-1 METER, CLASS-1 METER, CLASS-1
CT:250/1A CT:250/1A CT:250/1A
15VA 15VA 15VA
51G Ground Time Overcurrent 64R Ground” and “Hot” Fault
1.1 KV,1R, 4C x 120 SQMM, AL XLPE, 1.1 KV,1R, 4C x 120 SQMM, AL XLPE,
ARMOURED CABLE ARMOURED CABLE
MPPT:1 MPPT:2 MPPT:3 MPPT:4 MPPT:5 MPPT:6 MPPT:7 MPPT:8 MPPT:1 MPPT:2 MPPT:3 MPPT:4 MPPT:5 MPPT:6 MPPT:7 MPPT:8 MPPT:1 MPPT:2 MPPT:3 MPPT:4 MPPT:5 MPPT:6 MPPT:7 MPPT:8
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
11-JAN-2024
BASU MEHUL[C988]
1 of 5
AC SINGLE LINE DIAGRAM WORKSHOP_ SINGLE LINE DIAGRAM
SHT. No. 01 No. OF SHT. 02
Page 1 of 5
TO LT PANEL
TO LT PANEL
Module Inverter
FUSE 30A
-VE -VE
INV 1 STRING CONFIGURATION INVERTER ELECTRICAL WORKSHOP INV 1 STRING CONFIGURATION INVERTER MECHANICAL WORKSHOP
TO LT PANEL
121KVA @45°
INVERTER
MODULE : 665Wp
OUTPUT VOLTAGE: 415V
GEL-IN-HMEL-WS -OA-E-SLD-001
REV.
01
WORKSHOP_ SINGLE LINE DIAGRAM
11-JAN-2024 INV 2 STRING CONFIGURATION INVERTER MECHANICAL WORKSHOP SHT. No. 02 No. OF SHT. 02
BASU MEHUL[C988]
2 of 5
Page 2 of 5
R0_STRING SIZING CALCULATION - WORKSHOP
MPPT wise AC
Inverter Module MPPT Module in No of MPPT wise DC/AC
No of Strings Cap @ 45
No. Wattage No series Modules DC Cap ratio
degree
665 1 19 2 38 25.27 15.13 1.671
665 2 20 1 20 13.3 15.13 0.879
665 3 20 2 40 26.6 15.13 1.759
1 Electrical 665 4 18 1 18 11.97 15.13 0.791
Workshop 665 5 18 1 18 11.97 15.13 0.791
665 6 17 1 17 11.305 15.13 0.747
665 7 17 1 17 11.305 15.13 0.747
665 8 17 1 17 11.305 15.13 0.747
Electrical Workshop 12 146 10 185 123.025 121.00 1.017
665 1 18 1 18 11.97 15.13 0.791
665 2 18 1 18 11.97 15.13 0.791
665 3 18 1 18 11.97 15.13 0.791
1
665 4 18 1 18 11.97 15.13 0.791
Mechanical
Workshop
665 5 18 1 18 11.97 15.13 0.791
665 6 18 1 18 11.97 15.13 0.791
665 7 0 0 0 0 15.13 0.000
665 8 0 0 0 0 15.13 0.000
12 108 6 108 71.82 121.00 0.594
665 1 18 1 18 11.97 15.13 0.791
665 2 18 1 18 11.97 15.13 0.791
665 3 18 1 18 11.97 15.13 0.791
2
665 4 21 1 21 13.965 15.13 0.923
Mechanical
Workshop
665 5 20 1 20 13.3 15.13 0.879
665 6 20 1 20 13.3 15.13 0.879
665 7 0 0 0 0 15.13 0.000
665 8 0 0 0 0 15.13 0.000
12 115 6 115 76.475 121.00 0.632
Mechanical Workshop 24 223 12 223 148.295 242.00 0.613
GRAND TOTAL 22 408 271.32 363 0.747438
11-JAN-2024
BASU MEHUL[C988]
3 of 5
Page 3 of 5
refer attached sheet
11-JAN-2024
BASU MEHUL[C988]
4 of 5
Page 4 of 5
1. 415V SYSTEM IS CONSIDERED.
2. ALL MFM SHALL BE PROVIDED WITH RS-485 PORT.
3. THE TERMINATION AT INTERCONNECTION SHALL BE DONE BASED ON DISCOM INPUT.
4. MENTIONED CABLE SIZES ARE TENTATIVE. SAME WILL BE UPDATED AS PER CABLE SIZING CALCULATION.
5. MULTI-FUNCTION METER IN ALL HT AND LT PANELS - SHALL BE AS PER FOLLOWING MIN. SPECIFICATIONS/
REQUIREMENTS: - MULTIFUNCTION LCD DISPLAY DIGITAL METER DISPLAYING VOLTAGE, AMPS, KWH, KW, P.F.,
ACTIVE, REACTIVE, APPARENT ENERGY, THDI&V, INDIVIDUAL HARMONICS - UPTO 31ST, 64 SAMPLES/CYCLE,
CURRENT AVERAGE, ACTIVE POWER, REACTIVE POWER AND APPARENT POWER, RS 485 PORT MODBUS RTU
PROTOCOL. ACTIVE ENERGY - CLASS 0.5S AS PER IEC 62053-2
6. MULTI-FUNCTION METER IN HT PANEL- SHALL BE AS PER FOLLOWING MIN. SPECIFICATIONS/ REQUIREMENTS:
TO EXISTING LT PANEL TO EXISTING LT PANEL MULTIFUNCTION LCD DISPLAY DIGITAL METER DISPLAYING VOLTAGE, AMPS, KWH, KW, P.F., ACTIVE, REACTIVE,
APPARENT ENERGY, THDI&V, INDIVIDUAL HARMONICS - UPTO 51ST , WAVEFORM CAPTURE, DETECTION OF
of WS-AS-331 of WS-AS-331 VOLTAGE SWELLS AND SAGS, 256 SAMPLES/CYCLE WITH ETHERNET PORT AND IEC61850 PROTOCOL,512MB
MEMORY. ACTIVE ENERGY - CLASS 0.2S IEC 62053-22 , REACTIVE ENERGY CLASS - 0.5S IEC 62053-24, POWER
FEEDER 1AR1 FEEDER 1AF1 FACTOR - CLASS 0.5 AS PER IEC 61557-12 COMPLYING TO IEC 61557-12, IEC 62053-22.
7. 2 NOS OF CABLE WILL RUN FROM STRING , 1 WILL BE POSITIVE 1 WILL BE NEGATIVE.
8. FOR AC OUTPUT SIDE FAULT (LINE TO GROUND), RCMU SHALL DETECT LEAKAGE CURRENT & TRIP THE
ASSOSIATED INVERTER . LINE TO LINE FAULT SHALL BE CLEARED THROUGH DSP. DURING THIS OTHER INVERTER'S
1.1 KV,1R, 4C x 120 SQMM, AL 1.1 KV,1R, 4C x 120 SQMM, AL REMAIN UNAFFECTED & OPERATIONAL.
9. EARTH LEAKAGE PROTECTION SHALL BE PROVIDED BOTH AC & DC SIDE. ON DC SIDE INSULATION RESISTANCE
XLPE,ARMOURED CABLE XLPE,ARMOURED CABLE MEASUREMENT PROTECTION IS PROVIDED. IF INVERTER RESISTANCE IS BELOW 500KOHM, INVERTER SHALL TRIP.
10. ON DC SIDE NO CONTACTOR/ MCCB IS PROVIDED. ONE NO TWO POLE DC OFF LOAD SWITCH PROVIDED FOR 2
MPPT'S. ITS LOCATION IS AT THE BOTTOM SIDE OF INVERTER.
CT:250/1A CT:500/1A
415V 415V
CURRENT TRANSFORMER
1.1 KV,1R, 4C x 120 SQMM, AL 1.1 KV,1R, 4C x 120 SQMM, AL
XLPE,ARMOURED CABLE XLPE,ARMOURED CABLE EARTHING
INDICATOR
LT PANEL 3 P+E, SPD TYPE-2, 50kA LT PANEL 3 P+E, SPD TYPE-2, 50kA SOCKET
(1 INVERTER) CT:250/1A (2 INVERTERS) CT:500/1A
PHASE IND. PHASE IND.
CLASS-1
15VA, MFM 230V,5A SOCKET 1NOS. CLASS-1
15VA, MFM 230V,5A SOCKET 1NOS. AC SPD, TYPE 2 IN ACDB
230V,15A SOCKET 1NOS. R Y B 230V,15A SOCKET 1NOS. R Y B
RASIN CAST RASIN CAST
NR 86 95 50N 51G
CT:250/1A
CLASS-5P20 15VA ON OFF TRIP NR 86 95 50N 51G ON OFF TRIP M ACB
51 51N 50 64R CT:500/1A
CLASS-5P20 15VA
51 51N 50 64R
E/F INDICATION E/F INDICATION
MCCB
RELEASE
MP TYPE WITH
O/C,S/C,E/F
50kA MCCB
4P, 415V, 500A,
RELEASE
MP TYPE WITH
O/C,S/C,E/F
50kA MCCB
4P, 415V, 250A,
EP M METER
4P, 415V, +/- 10%, 50HZ +/- 3%, 250 A, 50 KA FOR 1 SEC, AL, BUS BAR 4P, 415V, +/- 10%, 50HZ +/- 3%, 500 A, 50 KA FOR 1 SEC, AL, BUS BAR DRAWOUT TYPE
MP TYPE WITH
MP TYPE WITH
MP TYPE WITH
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
4P, 415V, 250A, 50kA MCCB
MP TYPE WITH
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
4P, 415V, 250A, 50kA MCCB
MP TYPE WITH
O/C,S/C,E/F RELEASE
O/C,S/C,E/F RELEASE
4P, 415V, 32A, MCCB
51 Inverse Time Over Current Relay 51N IDMT EARTH FAULT RELAY
1.1kV,1R x 4C x 35 SQMM, AL 1.1kV,1R x 4C x 35 SQMM, AL
XLPE, ARMOURED CABLE XLPE, ARMOURED CABLE
Trip Circuit Supervision Relay
SPARE
SPARE
MFM TOWARDS AUXILIARY LOAD MFM MFM TOWARDS AUXILIARY LOAD 95 86 Master Trip Relay
METER, CLASS-1 METER, CLASS-1 METER, CLASS-1
CT:250/1A CT:250/1A CT:250/1A
15VA 15VA 15VA
It is noted that several points which have been commented and corrected in other area SLDs are not incorporated here. This is not 51G Ground Time Overcurrent 64R Ground” and “Hot” Fault
acceptable. It leads to wastage of efforts at our end. Please ensure this doesn't happen again.
1. The cable sizes indicated for power evacuation to Owner's switchboard for both 121KVA and 242KVA are same. 1Rx4Cx120 sqm AL. We
understand it is a drafting error. Please recheck the cable sizes w.r.t cable sizing as per tender requirement.
2. Indicate class of MFM, associated CT for the outgoing feeder to Owner's swbd as per tender.
3. Only one feeder is indicated for auxiliary loads. Please clarify:
a. feeder for UPS
b. Feeder for motors for water cleaning and its motor starters
1.1 KV,1R, 4C x 120 SQMM, AL XLPE, c. feeder for AC and other loads 1.1 KV,1R, 4C x 120 SQMM, AL XLPE,
ARMOURED CABLE ARMOURED
4. As per tender, ACB has to be provided for all feeders above 400A (refer clause 5.3.13 of 6-51-0099). Accordingly, please provide ACB for CABLE
mechanical workshop ACDB.
5. Please clarify if the LT and metering panels are outdoor or indoor. From cable routing it seems indoor.
6. indicate analogue ammeter and voltmeter in outgoing feeder to Owner's system.
7. Indicate Ct and MFM in all feeders in 415V swbd as per tender.
8. As per tender SLD, 2 nos feeders are reqd for DC UPS. Gensol proposed AC UPS which is acceptable. But the UPS shall have 2 nos
STRING INVERTER incomers. gensol shall update this clause in all SLDs.
STRING INVERTER STRING INVERTER
121KVA @ 9. Please clarify the purpose of 64R in this relay. 121KVA @ 121KVA @
45deg C INVERTER 01 10. Add note numerical relay shall be communicable with IEC 61850. 45deg C INVERTER 01 45deg C INVERTER 02
121 kVA 11. Pls indicate the power panel feeder/ outgoing number for space heater power supply to switchboards. 121 kVA 121 kVA
3Ø,415V,50Hz 12. Gensol to confirm that the Owner's feeder where power shall be interfaced is SFu and hence no control cabling between Gensol's
3Ø,415V,50Hz 3Ø,415V,50Hz
outgoing and Owner's incoming is envisaged.
MPPT:1 MPPT:2 MPPT:3 MPPT:4 MPPT:5 MPPT:6 MPPT:7 MPPT:8
13. Further comments provided during switchboard vendor drawing review shall be suitably updated in SLD. MPPT:1 MPPT:2 MPPT:3 MPPT:4 MPPT:5 MPPT:6 MPPT:7 MPPT:8 MPPT:1 MPPT:2 MPPT:3 MPPT:4 MPPT:5 MPPT:6 MPPT:7 MPPT:8
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
11-JAN-2024
BASU MEHUL[C988]
5 of 5
AC SINGLE LINE DIAGRAM WORKSHOP_ SINGLE LINE DIAGRAM
SHT. No. 01 No. OF SHT. 02
Page 5 of 5