Fire Prevention Department


PROJECT DESCRIPTION FIRE SAFETY PROVISIONS OCCUPANT LOAD CALCULATIONS General Directorate of Civil Defence
Ministry of Interior, State of Qatar
GENERAL:
THE PROJECT IS A BUILDING MATERIAL STORE (G+M) & ACCOMMODATIONS (1+2) &SHOWROOM (G) FIRE FIGHTING SYSTEM
&OFFICE (1 & GUARD ROOM (G)
MAINLY STORAGE &RESIDENTIAL &MERCANTILE &BUSINESS OCCUPANCY
AUTOMATIC SPRINKLER SYSTEM FLOOR AREA FACTOR OCCUPANT LOAD NUMBER OF MEANS OF
FLOOR LEVEL/SPACE USE OCCUPANCY/USE (SQ. M) (SQ. M/PERSON) (PERSONS)
COVERAGE: THROUGHOUT EXITS EGRESS
LOCATED IN BARAKAT AL AWAMER
PARTIAL PROTECTION; SPECIFY AREAS PROTECTED: __________________ GROUND FLOOR / BUILDING MATERIAL STORE STORAGE 468 27.9 17 3 DOORS

ü N/A GROUND FLOOR / SHOWROOM MERCANTILE 39.6 9.3 5 2 DOORS


NUMBER OF STOREY :

100 mm
MEZZANINE FLOOR / BUILDING MATERIAL STORE STORAGE 210.1 27.9 8 1 STAIRS
THE PROJECT COMPRISES OF BUILDING MATERIAL STORE (G+M & )ACCOMMODATIONS & )1+2(SHOWROOM FIRST FLOOR / OFFICE BUSINESS 66.8 9.3 8 1 STAIRS
MANUAL FIRE FIGHTING SYSTEM FIRST FLOOR / LABOR ACCOMMODATION RESIDENTIAL 72.00 18.6 4 1 STAIRS
(G& )OFFICE & 1(GUARD ROOM (G) SECOND FLOOR / LABOR ACCOMMODATION
FIRE HOSE REELS RESIDENTIAL 72.00 18.6 4 1 STAIRS
DESCRIPTION OF EACH BUILDING:
ü PORTABLE FIRE EXTINGUISHERS
GROUND FLOOR :MATERIAL STORE (STORAGE OCCUPANCY) N/A
ROOMS (RESIDENTIAL OCCUPANCY)
SHOWROOM (MERCANTILE OCCUPANCY)
MEZZANINE/FIRST FLOOR :ROOMS (RESIDENTIAL OCCUPANCY)
OTHER AUTOMATIC SUPPRESSION SYSTEM Officer's Signature
TYPE AREAS PROTECTED
MATERIAL STORE (STORAGE OCCUPANCY)
WATER SPRAY SYSTEM
REFERENCE NO:
OFFICE (BUSINESS OCCUPANCY)
SECOND FLOOR :ROOMS (RESIDENTIAL OCCUPANCY)
STORAGE USES THAT CAN BE CONSIDERED AS LOW HAZARD STORAGE
WATER MIST SYSTEM
CLEAN AGENT SUPPRESSION SYSTEM
FOAM SYSTEM
EGRESS CAPACITY CALCULATIONS N/2021/0005171 Reviewing Fire Safety Engineer Signature/Date

OCCUPANCIES INCLUDE THE FOLLOWING: DRY CHEMICAL SYSTEM CONSULTANT'S ENDORSEMENT:


-Bricks WET CHEMICAL SYSTEM
KITCHEN/ RANGE HOOD EXTINGUISHING SYSTEM (AS PER NFPA 96)
-sand STAIR OR DOOR REQUIRED MINIMUM 1823
OTHER, SPECIFY; ________________________ MAXIMUM NUMBER ACTUAL WIDTH NUMBER OF
-Slate ü N/A FLOOR LEVEL/ SPACE USE
OCCUPANCY/
OF OCCUPANT
WIDTH/ PERSON WIDTH WIDTH
OF STAIRS OR STAIRS OR
USE (NFPA 101 OF STAIR OR REQUIRED
-Cement (PER FLOOR)
TABLE 7.3.3.1) DOOR (mm) BY CODE (mm)
DOORS PROVIDED DOORS PROVIDED
NFPA )170/220 (edition , 2012NFPA 80edition ,2013NFPA )101/5000(
GROUND FLOOR / BUILDING MATERIAL STORE STORAGE 17 5 85 810 5500+1000 3 EDITION TO BE 2015Ed .
BUILDING CLASSIFICATIONS (HABITABLE HEIGHT) : PREVIOUS QCD PLAN APPROVAL REF. NOS.: FIRE ALARM SYSTEM GROUND FLOOR / SHOWROOM MERCANTILE 5 5 25 810 1800+1000 2
MEZZANINE FLOOR / BUILDING MATERIAL STORE STORAGE 8 7.6 30.4 915 1400 1
ü AUTOMATIC FIRE ALARM SYSTEM
FIRST FLOOR / OFFICE BUSINESS 8 7.6 68.4 915 1200 1
ü MANUAL (call points / pull stations) FIRST FLOOR / LABOR ACCOMMODATION 915 1
HIGH-RISE BUILDING (28m) FSD-/PS-/N-/M-/R- ____________ SMOKE ALARMS (standalone devices)
RESIDENTIAL 4 7.6 30.4 1200

100 mm
SECOND FLOOR / LABOR ACCOMMODATION RESIDENTIAL 4 7.6 30.4 915 1200 1

MID-RISE BUILDING (>15m - <28m) ü N/A N/A

ü LOW-RISE BUILDING (<15m)


N/A SMOKE CONTROL SYSTEM NABIL ALDESSOUKY MOAHMED ALDESSOUKY

SMOKE MANAGEMENT (SHEVS) DOHA ELEAZ ENGINEERING CONSULTANTS

ü MECHANICAL NATURAL TEL .NO 70701830FAX 44423505PO BOX 91386

BUILDING DATA
APPLICATION:
CAR PARKS (Basement >500m² and/or >1 Level)
APPLICATION:
CAR PARKS (Basement >500m² and/or >1 Level)
DOORS/WINDOWS/OPENING SCHEDULES UPDA Reg.No./Grade: 1823 / A 26281803023
ENCLOSED PARKING STRUCTURES OPEN PARKING STRUCTURES
WAREHOUSE STORAGE AREAS WAREHOUSE STORAGE AREAS
04/10/2021
BUILDING NAME: BUILDING MATERIAL STORE (G+M) & ACCOMMODATIONS (1+2) FACTORY MANUFACTURING AREAS FACTORY MANUFACTURING AREAS WINDOW SCHEDULE LOCATION FIRE RATED 19/11/2019
ATRIA ATRIA
&SHOWROOM (G) &OFFICE (1 & GUARD ROOM (G) MALLS (with floor openings connecting more than 2 levels) MALLS TYPE PLAN WIDTH HEIGHT SILL DESCRIPTION
OCCUPANCY TYPE: ROOM: RESIDENTIAL OCCUPANCY üOTHERS, SPECIFY: _PANTRY & W/C_ STAIRWELLS (Smoke Vents: 1.5m² fixed-wall
N/A openings, max. 300mm below slab soffit)
SHOWROOM: MERCANTILE OCCUPANCY
OTHERS, SPECIFY: __________________
STORE: STORAGE OCCUPANCY SMOKE CONTAINMENT üN/A
ENTRANCE OF ROOMS 1.0 HR
OFFICE: BUSINESS OCCUPANCY ACTIVE SYSTEM (PRESSURIZATION)
APPLICATION:
HAZARD CLASSIFICATION: STORE : LOW HAZARD Single
STAIRWELLS
ROOMS& SHOWROOM & OFFICE :- ORDINARY HAZARD SMOKE-STOP LOBBIES Single
FIRE FIGHTING LOBBIES
NEW CONSTRUCTION: ü
YES _____ NO_____ : REMARKS: FOR LOCATION SEE PLAN

100 mm
OTHERS, SPECIFY: __________________
REPAIR OF EXISTING: YES _____ ü :
NO_____ ü N/A
AL-Furousiya street - front of Aspire zone
RENOVATION OF EXISTING: YES _____ ü :
NO_____
EMERGENCY POWER SUPPLY SYSTEM DOORS SCHEDULE
Tel: +974 44423505 Mobile:33785562
MODIFICATION OF EXISTING: YES _____ ü :
NO_____
DIESEL-ENGINE GENERATOR SET Fax: +974 44423505 P.o.Box 91386
RECONSTRUCTION OF EXISTING: YES _____ ü :
NO_____ OTHERS SPECIFY: ___________________ TYPE WIDTH HEIGHT DESCRIPTION LOCATION FIRE RATED E-mail: info@dohaeleaz.com WWW.DOHAELEAZ.NET
CHANGE OF OCCUPANCY: YES _____ ü :
NO_____ ü N/A
Double Door
ENTRANCE OF STORE --
CHANGE OF USE: YES _____ ü :
NO_____ ENTRANCE OF ROOMS
STAIR DOOR
1.0 HR
1.5 HR UPDA Reg.No./Grade: 336/C Qatar ID No.: 27463401642
ADDITION TO EXISTING: YES _____ ü :
NO_____ Single Door ENTRANCE OF SHOWROOM --
24/09/2020
MULTIPLE OCCUPANCY ü
YES _____ NO_____ : Validity: 25-09-2018 Validity:
Single Door ENTRANCE OF BATH --
- SEPARATED OCCUPANCY ü
YES _____ NO_____ :
SHUTTER DOOR -- --
- MIXED OCCUPANCY YES _____ ü :
NO_____
OTHER FIRE AND LIFE SAFETY PROVISIONS OWNER:
INCIDENTAL USES: YES _____ ü :
NO_____
NOTE: All Doors assembly in a means of egress shall conform to the general requirements of
SPECIFY____________ : FIRE FIGHTING AND RESCUE PROVISIONS
FIRE LIFTS / FIRE SERVICE ACCESS ELEVATORS (28m habitable height and/or 9.0m depth of basements)
SPECIAL STRUCTURE: YES _____ ü :
NO_____ AMBULANCE STRETCHER ACCOMMODATION ELEVATORS (18m habitable height; minimum car size
NFPA 101 Section 7.1
HISTORIC BUILDING: YES _____ NO ü
_____ : 610mm x 2130mm in horizontal open position)
FIRE FIGHTING LOBBIES (in every fire lift provisions; min. size 6.0m², 2.0m. least side dimensions)
OTHERS : (SPECIFY OTHER SCOPE OF WORKS) SMOKE-STOP LOBBIES (28m habitable height and/or 9.0m depth of basements;1.8m. least side dimensions)
ü FIREMAN'S ACCESS PANELS (Bldgs.10m habitable height and in Factory & Storage Bldgs.of any height)
DRAWING INDEX

100 mm
AREA STATEMENT WINDOWS FOR RESCUE (In every room or space >23.2m² that is subject to student occupancy in Educational
Occupancies & in every room or space subject to clients occupancy in Day-care Occupancies)
ü FIRE ENGINE ACCESS ROADS (4.0m clear width / 4.5m unobstructed vertical clearance)
S.NO. DWG.NO. TITLE SIZE SCALE AL TARBAT COMPANY
ü FIRE ENGINE HARDSTANDING (min. size 6.0m x 15.0m; 45 ton stationary load capacity) 1 LSP-01/11 COVER PAGE NTS
FIRE COMMAND CENTER (in high-rise buildings and in any provisions of smoke control and/or emergency
communication system; min. size 9m²) 2 LSP-02/11 LOCATION & SITE PLANS 1:100
OTHERS SPECIFY:______________________________________________________
______________________________________________________ 3 LSP-03/11 GROUND FLOOR PLAN 1:100
AREA STATMENT
SUBDIVISION OF BUILDING SPACES (SMOKE COMPARTMENTS/FIRE BARRIERS) 4 LSP-04/11 FIRST FLOOR PLAN A1 1:100
PIN NUMBER 91210273 PLOT AREA 998 Sqm EDUCATIONAL OCCUPANCIES (with aggregate floor area of >2800m² and/or 91m building length or width;
BUILDING MATERIAL STORE (G+M) smoke partitions:1-hr fire resistance rating) 5 LSP-05/11 SECOND FLOOR PLAN 1:100
HEALTHCARE OCCUPANCIES (two smoke compartments in every story used by inpatients for sleeping or
GROUND FLOOR 468 Sqm treatment or any use with occupants >50; size limit of one compartment 2100m²; travel distance from any point 6 LSP-06/11 STAIRCASE FLOOR PLAN 1:100
MEZZANINE FLOOR 210.1 Sqm
to a door in a smoke barrier, 61.0m; smoke barriers: 1-hr fire resistance rating)
AMBULATORY HEALTHCARE OCCUPANCIES (every story into not less than 2 smoke compartments; size 7 LSP-07/11 ROOF PLAN 1:100 Project:
limit of one compartment 2100m², travel distance from any point to a door in a smoke barrier, 61.0m; smoke
SHOWROOM (G) & OFFICE (1) 8 LSP-08/11 FRONT & REAR ELEVATIONS 1:100
barriers: 1-hr fire resistance rating)
SHOWROOM (G) 39.6 Sqm DETENTION AND CORRECTIONAL OCCUPANCIES (two smoke compartments in every story used for
sleeping by residents or other story with occupants >50; max. 200 residents in any smoke compartment; travel 9 LSP-09/11 RIGHT & LEFT ELEVATIONS 1:100
OFFICE(G) +STAIRS (G+1) 66.8 Sqm distance from any room door required as exit access to a door in a smoke barrier, 46m; travel distance from any
point in a room to a door in a smoke barrier, 61.0m; smoke barriers: shall have structural fire resistance) 10 LSP-10/11 SECTIONS & GUARD ROOM 1:100
ACCOMMODATION (G+2) ü RESIDENTIAL OCCUPANCIES: HOTEL, DORMITORY AND APARTMENT BUILDINGS (guest rooms, guest BUILDING MATERIAL STORE (G+M) & ACCOMMODATIONS (G+2)
suite, dormitory rooms or apartment dwelling units, separated from each other by walls and floors constructed as 11 LSP-11/11 DETAILS NTS
&SHOWROOM (G) &OFFICE (1) & GUARD ROOM (G)

100 mm
ACCOMMODATION (G) 72.00 Sqm
fire barriers of min.1-hour fire resistance rating or 1/2-hour fire resistance rating in buildings protected
ACCOMMODATION (1) 72.00 Sqm throughout with automatic sprinklers system)

ACCOMMODATION (2)

STAIR CASE
72.00 Sqm
13.00 Sqm
OTHERS SPECIFY:______________________________________________________
______________________________________________________ LEGEND & SYMBOLS
Note. Please mark/check the applicable provision (box) and show or demonstrate the provisions on Plans.
GUARD ROOM (G) 17.00 Sqm

NO: OF PARKING 2 Nos. 1 HOURS FIRE BARRIER / FIRE COMPLEMENTATION Location: BARAKAT AL AWAMER PIN No.: 91210273
COVERED AREA 596.6 Sqm
2 HOURS FIRE BARRIER / FIRE COMPLEMENTATION
BUILT UP AREA FAR = 1.03 1030.5 Sqm Area: 91 Street: --- Plot No: ---
% OF COVERED AREA 59 % TRAVEL DISTANCE
REQUIRED SUBMISSION AFTER LIFE SAFETY PLAN APPROVAL Title:
FIRE SAFETY / BUILDING PLAN
ü FIRE FIGHTING (FF)
mm

FIREMAN'S ACCESS PANELS


150

150 mm

ü FIRE ALARM (FA)


FIRE FIGHTING ACCESS
DO NOT OBSTRUCT

AIR CONDITIONING, VENTILATION AND SMOKE CONTROL SYSTEM


BUILDING TYPE OF CONSTRUCTION N/A EXIT EXIT SIGN COVER PAGE
MV MECHANICALLY VENTILATED

BUILDING/ TYPE OF CONSTRUCTION Notes:


BASED ON THE THE CLASSIFICATION OF OCCUPANCY, HABITABLE HEIGHT & HAZARD CONTENTS, Revision: 00 Scale: Drawing No.:
A MINIMUM TYPE OF CONSTRUCTION SHALL BE TYPE II (222) AS PER NFPA 5000. " Emergency lighting facilities for means of egress shall be provided in accordance with NFPA 101 Section 7.9."
(NFPA 5000, SEC. 7.2.3) Date: JULY-2021 NTS LSP-01/11